r g oog)

UNITED STATES

+

[

h NUCLEAR REGULATORY COMMISSION g.

5

'j WASHINGTON, D. C. 20555

%,e...*/

TENNESSEE VALLEY AUTHORITY DOCKET NO.

50-327 SE0UnYAH NUCLEAR PLANT, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 51 License No. DPR-77 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for arendment to the Sequoyah Nuclear Plant, Unit 1 (the facility) Facility Operating License No. DPR-77 filed by the Tennessee Valley Authority (licensee), dated April 7, 1986, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's regulations as set forth in 10 CFR Chapter I; 8.

The facility will operate in conformity with the license, as amended, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (il that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is hereby amended by page changes to the Appendix A Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. OPR-77 is hereby amended to read as follows:

l l

t 8612090649 861202

^

PDR ADOCK 05000327 P

PDR

- (2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 51 are hereby incorporated into the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

\\b\\

B. J. Youngblood, Director PWR Pro.iect Directorate #4 Division of PWR Licensing-A Attachment" Appendix A Technical Specification Changes Date of Issuance: December 2, 1986 i

PWR#/fkWR-A PWR.

WR-A PWR DPWR-A OGC/PJ"T{

RJYy,(gblood PWR WWR-A MD Rr/mac JHo

'ch CS hie

%t n

11/j /86 11 (Q86 11

/86 11/2[/86 11/ /86 ECR/D R

~

RKSingh 11/19 /86

-g ATTACHf!ENT TO LICEf;SE APENDMENT NO. 51 ftCILITY OPERATIf4G LICEhSE f;0. DPR-77 00CVET NO. 50-327 Replace the following page of the Appendiy "A" Technical Specifications with the enclosed page. The revised page is identified by kendment number and ccntains vertical lines indicatirg the areas of change.

k>enced Page 3/4 2-2 e

l l

l l

t

POWER DISTRIBUTION LIMITS l'

SURVEILLANCE REQUIREMENTS 4.2.1.1 The indicated AXIAL FLUX DIFFERENCE shall be determined to be within its limits during POWER OPERATION above 50% of RATED THERMAL POWER by:

a.

Monitoring the indicated AFD for each OPERABLE excore channel at least once per 7 days when the AFD Monitor Alarm is OPERABLE.

b.

Monitoring and logging the indicated AXIAL FLUX DIFFERENCE for each OPERABLE excore channel at least once per hour for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 30 minutes thereafter, when the AXIAL FLUX DIFFERENCE Monitor Alarm is inoperable.

The logged values of the indicated AXIAL FLUX DIFFERENCE shall be assumed to exist during the interval preceding each logging.

4.2.1.2 The indicated AFD shall be considered outside of its limits when at least 2 OPERABLE excore channels are indicating the AFD to be outside the limits.

i SEQUOYAH - UNIT 1 3/4 2-2 Amendment No.

51

4 T.i-g b

%u

+a.

4 c.

.m J---.4e

_mA

  • e w

p.ha e

4 s--_.

!crecy~ 'o,,

UNITED STATES

~

f g

NUCLEAR REGULATORY COMMISSION E

WASHWGTON, D. C. 20666 g;

r a

o TENNESSEE VALLEY AUTHORITY DOCKET NO. 50-328 SEQUOYAH NUCLEAR PLANT, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 43 License No. DPR-79 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment to the Sequoyah Nuclear Plant, Unit 2 (the facility) Facility Operating License No. DPR-79 filed by the Tennessee Valley Authority (licensee), dated April 7, 1986, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's regulations as set forth in i

10 CFR Chapter I; B.

The facility will operate in conformity with the license, as amended, the provisions of the Act, and the rules and regulations of the Commission;

. C.

There is reasonable assurance (f) that the activities authorized by i

this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; 1

D.

The issuance of this amendment will-not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is hereby amended by page changes to the Appendix A i

Technical Specifications as indicated in the attachment to this license l

amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-79 l

is hereby amended to read as follows:

4 I

- (2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 43 are hereby incorporated into the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license anendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION W\\

B. J. Youngblood, Director PWR Pro.iect Directorate #4 Division of PWR Licensing-A Attachment Appendix A Technical Specification Changes Date of Issuance: December 2, 1986 PWR#4DNWR-A PWR.

WR-A PW DPWR-A OGC/ PETS P

PWR-A MDan 7mac JHo ich CS _41e SU N B

o blood

.11/j /86 1

/86 11 T/86 11/ff/86 I

6 ECR/DP BKSingh 11/\\9/86

i 9

ATTACHMENT TO LICEtlSE Al:Et:DMENT NO. 43 i

FACILITY OPERATING LICENSE NO. DPR-79 DOCKET li0. 50-328 Peplace the following page of the Appendix "A" Technical Specifications with the enclosed page.

The revised page is identified by knendment nurber and contains vertical lines indicating the areas of change, k.iended Page 3/4 2-2 O

~

POWER DISTRIBUTION LIMITS Y

SURVEILLANCE REQUIREMENTS 4.2.1.1 The indicated AXIAL FLUX DIFFERENCE shall be determined to be within its limits during POWER OPERATION above 50% of RATED THERMAL POWER by:

a.

Monitoring the indicated AFD for each OPERABLE excore channel at least once per 7 days when the AFD Monitor Alarm is OPERABLE, and b.

Monitoring and logging the indicated AXIAL FLUX DIFFERENCE-for each OPERABLE excore channel at least once per hour for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 30 minutes thereafter, when the AXIAL FLUX DIFFERENCE Monitor Alarm is inoperable.

The logged values of the indicated AXIAL FLUX DIFFERENCE shall be assumed to exist during the interval preceding each logging.

4.2.1.2 The indicated AFD shall be considered outside of its limits when at least 2 OPERABLE excore channels are indicating the AFD to be outside the limits.

I i

i SEQUOYAH - UNIT 2 3/4 2-2 Amendment No. 43

{