ML20214S940

From kanterella
Jump to navigation Jump to search
Forwards Request for Addl Info Re Util 831104,841119 & 850523 Responses to Generic Ltr 83-28,Item 2.2 (Part 2), Vendor Interface (Program for All Safety-Related Components)
ML20214S940
Person / Time
Site: Rancho Seco
Issue date: 06/01/1987
From: Knighton G
Office of Nuclear Reactor Regulation
To: Andognini G
SACRAMENTO MUNICIPAL UTILITY DISTRICT
References
GL-83-28, NUDOCS 8706100061
Download: ML20214S940 (3)


Text

s 9

! 1JUN 1337 Q ~ 3 /2 -

Mr. G. Carl Andognini Chief Executive Officer, Nuclear Sacramento Municipal Utilities District 14440 Twin Cities Road Herald, California 95638-9799

Dear Mr. Andognini:

SUBJECT:

ITEM 2.2 (PART 2) 0F GENERIC LETTER 83-28 The Sacramento Municipal Utility District responded to Item 2.2 (Part 2)

" Vendor Interface (Program for all Safety-Related Components)" of Generic Letter 83-28 by responses dated November 4,1983, November 19, 1984, and May 23, 1985. We have reviewed these submittals and find that we need additional information to complete our review. Please respond to the enclosed request for additional information.

The reporting and/or recordkeeping requirements contained in this letter affect fewer than ten respondents; therefore OMB clearance is not required under P.L.96-511.

Sincerely, Orig lnal signhd by:

George IV. KnigMan George W. Knighton, Director Project Directorate V Division of Reactor Projects - III/IV/V

& Special Projects

Enclosure:

As stated cc:

See next page DISTRIBUTION

DocketJ11e, NRC & Local PORs GMHolahan JLee GKalman 0GC-Eethesda EJordan JPartlow ACRS (10)

PD5 Plant file DRSP//DV DR f/1:PDV GKolpan GW nighton 5/]V/87 6/ t /87 0FFICIAL RECORD COPY 8706100061 B70601 PDR ADOCK 05000312 P

PDR

G 9

Mr. G. Carl Andognini Rancho Seco Nuclear Generating Chief Executive Officer, Nuclear Station Sacramento Municipal Utility District cc:

Mr. David S. Kaplan, Secretary Mr. John Bartus and General Counsel Ms. JoAnne Scott Sacramento Municipal Utility Federal Energy Regulatory Commission District 825 North Capitol Street, N. E.

6201 S Street Washington, D.C.

20426 P. O. Box 15830 Sacramento, California 95813 Thomas A. Baxter, Esq.

Shaw, Pittman, Potts & Trowbridge-2300 N Street, N.W.

Washington, D.C.

20037 Mr. John V. Vinguist Acting Manager, Nuclear Licensing Sacramento Municipal Utility District Rancho Seco Nuclear Generating Station 14440 Twin Cities Road Herald, California 95638-9799 Mr. Robert B. Borsum Babcock & Wilcox Nuclear Power Generation Division Suite 220, 7910 Woodmont Avenue Bethesda, Maryland 20814 Resident Inspector / Rancho Seco c/o U. S. N. R. C.

14440 Twin Cities Road Herald, California 95638 Regional Administrator, Region V U.S. Nuclear Regulatory Connission 1450 Maria Lane, Suite 210 Walnut Creek, California 94596 Mr. Joseph 0. Ward, Chief Radiological Health Branch State Department of Health Services 714 P Street, Office Building #8 Sacramento, California 95814 Sacramento County Board of Supervisors 827 7th Street, Room 424 Sacramento, California 95814 Ms. Helen Hubbard P. O. Box 63 4

Sunol, California 94586 4

I

il Y

REQUEST FOR ADDITIONAL INFORMATION ITEM 2.2 (PART 2) " VENDOR INTERFACE (PROGRAMS FOR ALL SAFETY-RELAltu COMPONENTSi" RANCHO SECO NUCLEAR GENERATING STATION, UNIT 1 Review of the licensee's responses dated November 4,1083, November 19, 1984 and May 23, 1985 for item 2.2 (Part 2) of Generic letter 83-28, discloses the need for additional information as follows:

A.

The licensee describes the NUTAC/VETIP program. This is not sufficient.

The licensee should describe how their procedures were revised to imple-ment and incorporate the NUTAC/VETIP program to compensate for the lack of a vendor interface for safety-related equipment.

B.

The staff finds the NUTAC/VETIP program acceptable for those instances where a vendor interface cannot be practicably established, e.g., where a vendor has gone out of business. However, the licensee should commit to establish a program to periodically contact vendors of key components (such as auxiliary feed pumps, safety-related batteries, ECCS pumps and safety-related valve operators) to facilitate the exchange of current technical information.

In the case of the diesel generator and safety-related switchgear vendors, a formal interface such as that with the NSSS vendor should be established if practicable, i

i I

-