ML20214Q525

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs,Revising Table 3.3.7.5-1 Re Accident Monitoring Instrumentation for Safety/Relief Valve Position Indicators
ML20214Q525
Person / Time
Site: Hope Creek 
Issue date: 06/01/1987
From:
Public Service Enterprise Group
To:
Shared Package
ML20214Q338 List:
References
NUDOCS 8706050062
Download: ML20214Q525 (1)


Text

r

.f TABLE 3.3.7.5-1 ACCIDENT MONITORING INSTRUMENTATION n

o MINIMUM APPLICABLE m"

REQUIRED NUMBER CHANNELS OPERATIONAL INSTRUMENT OF CHANNELS OPERABLE CONDITIONS ACTION 1.

Reactor Vessel Pressure 2

1 1,2,3 80 2.

Reactor Vessel Water Level 2

1 1,2,3 80 3.

Suppression Chamber Water Level 2

1 1,2,3 80 4.

Suppression Chamber Water Temperature

  • 2 2

1,2,3 80(a) 5.

Suppression Chamber Pressure 2

1 1,2,3 80 6.

Drywell Pressure 2

1 1,2,3 80 7.

Drywell Air Temperature 2

1 1,2,3 80 8.

Primary Containment Hydrogen /0xygen Concentration w1 Analyzer and Monitor 2

1 1,2,3 80 Y

9.

Safety / Relief Valve Position Indicators (C) 2/ valve **

1/ valve ** 1,2,3 80 l

10.

Drywell Atmosphere Post-Accident Radiation Monitor 2

1 1,2,3 81 11.

North Plant Vent Radiation Monitor #

1 1

1,2,3 81 12.

South Plant Vent Radiation Monitor #

1 1

1,2,3 81 13.

FRVS Vent Radiation Monitor #

1 1

1,2,3 81 14.

PrimaryCoginnentIsolationValvePosition Indication 2/ valve 1/ valve 1,2,3 82

  1. High range noble gas-monitors.
  • Average bulk pool temperature.
    • Acoustic monitoring and tail pipe temperature.

(a) Suppression chamber water temperature instrumentation must satisfy the availability requirements specified in Specification 3.6.2.1.

(b)0ne channel consists of the open limit switch, and the other channel consists of the closed limit switch.

(c) The acoustic monitor for FOl3H SRV may be inoperable until September 21, 1987 without applying the shutdown requirement of ACTION 80(a).

8706050062 870601 DR ADOCK 0500 4

.