Docket No.:
50-443/444 Jgg 111986 l
MEMORANDUM FOR:
Victor Nerses, Seabrook Project Manager PWR Project Directorate #5 Division of PWR Licensinp-A FROM:
C. E.-Rossi, Assistant Director Division of PWR Licensing-A
SUBJECT:
EMERGENCY RESPONSE CAPABILITY - CONFORMANCE TO R.G. 1.97, REV.'3 Plant Name:
Seabrook Station, Unit Nos. I and 2 Docket Nos.:
50-443/444
- 1
' Utility:
Public Service of New Hampshire
,4't-Licensing Status:
OL Project Manager:
V. Nerses Review Branch:
EICSB/DPA Review Status:
Complete for Core Load We are transmitting herewith our subject safety evaluation with its-attachment, j
EG8G Idaho, Inc. Technical Evaluation-Report (TER) dated May 1986. Our safety evaluation is based on our review of EG8G's TER EGG-NTA-7256. We find the instrumentation provided by Public Service of New Hampshire for meeting the recomendations of Regulatory Guide 1.97 acceptable, except for the. variables accumulator tank level and pressure, containment sump water temperature, and quench tank temperature.
The applicant has committed to upgrade the accumulator tank level or pressure and containment sump water temperature instrumentation in accordance with Regu-latory Guide 1.97 prior to startup from the first refueling outage.. 'This is acceptable.
For quench tank temperature the applicant should provide additional-information on the existing range of the instrument or provide an expanded range prior to startup from the first refueling outage. is the SALP input for this review.
Original aignedby Charles E. Rossi, Assistant Director Division of PWR Licensing-A
Enclosures:
Distribution:
As stated Docket File No. 50-443/444 EICSB Rdg cc: See attached list WWLgavnkb(PFH2h 4
J. E. Kriight q
Contact:
F. Rosa.
J. Lazevnick, EICSB/DPA C. E. Rossi j
X24864 Seabrook S/F i
i E!CSB/DPA SL/EICSB/DPA BC/EICS)1LDEA JLa ick:ct JE ni FRosa g 4' ERossi j
a'.
1 6/i 86 6/ /D' 6 6 fit;/86 '
/ //86; OFFICIAL RECORD COPY
/ f80
/
h)
/
$/f 1
7-V. Nerses 2-cc:
T. Novak V. Noonan j
H. Walker J. Wing J. Joyce i
A. Udy (EG8G) i I
1 J
i i
j a
s 4