4 Docket No.:

50-369/370 IRAY 221986 MEMORANDUM FOR:

Darl Hood, Project Manager, Project Directorate #4 Division of PWR Licensing-A FROM:

Charles E. Rossi, Assistant Director for Technical Support Division of PWR Licensing-A

SUBJECT:

EICSB (PWR-A) INPUT FOR MCGUIRE UNITS 1 AND 2 TECHNICAL SPECIFICATION CHANGES, MPA B-90 Plant Name:

McGuire Nuclear Station, Units 1 and 2 Utility:

Duke Power Company Docket Nos.:

50-369, 50-370 TAC Nos.:

55361, 55362 Licensing Status:

OR Resp. Directorate:

PD4/DPA Project Manager:

Darl Hood Review Branch:

EICSB/DPA Review Status:

Incomplete By letter dated December 7,1985, Duke Power Company submitted proposed technical specification changes for the McGuire Nuclear Station, Units 1 and 2, in response to Generic Letter 85-09.

EICSB finds the proposed changes acceptable except for the following:

1.

The licencee should provide a proposed technical specification for testing the Reactor Trip Bypass Breaker prior, to each time it is put into service consistent with Generic Letter 85-09.

2.

The licensee should provide proposed technical specifications for verifying the operability of the Bypass Breaker Trip circuit (s) each refueling outage consistent with Generic Letter 85-09. is the SALP input for this review.

Cri;2

I v i57, Charles E. Rossi, Assistant Director for Technical Support Division of PWR Licensing-A l

Enclosure:

Distribution:

As stated Docket File 50-369/370 C. E. Rossi EICSB Rdg.

V. Benaroya cc:

T. Novak A. Toalston (PF)(2)

McGuire S/F B. J. Youngblood D. Lasher J. E. Knight