i y-GPU Nuclear Corporation NUOIMf 100 Interpace Parkway Parsippany, New Jersey 07054-1149 (201)263-6500 May 14, 1987 TELEX 136-482 5000-87-1256 Writer's Direct Dial Number:
U.S. Iluclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555 Gentlemen:
Subject:
Oyster Creek Nuclear Generating Station Docket flo. 50-219 ilRC Inspection Report 50-219/87-07 Response to Notice of Violation Attachment A to this letter provides our response to the Notice of Violation described in the subject inspection report.
Should you require further information please contact Brenda De!!erchant, OC Licensing Engineer at (609)971-4642.
Very ruly yours, b
F. W'Ison s.
Vice President Technical Functions RFW:BD: dad (0490A) cc: 11r. William T. Russell, Administrator NRC Resident Inspector Region I Oyster Creek fluclear Generating Station U.S. Nuclear Regulatory Conmission Forked River, NJ 08731 631 Park Avenue King of Prussia, PA 19406 ftr. Alexander Dronerick William V. Johnston, Acting Director U.S. Nuclear Regulatory Connission Division of Reactor Safety 7920 Norfolk Avenue, Phillips Bldg.
U.S. Nuclear Regulatory Connission Bethesda, !!D 20014 Region I
!! ail Stop tio. 316 631 Park Avenue King of Prussia, PA 19406
@ 2ggock
/
O sht C
GPU Nuclear Corporation is a subsidiary of General Pubhc Utikties Corporation b
ATTACH!!EllT A
-Violation:
10 CFR 50, Appendix B, Criterion VI requires that neasures shall be established to control the issuance of drawings affecting quality. The measures shall assure that drawings, including changes, are reviewed for adequacy and approved for release.
The licensee's procedure no. 5000-A0it-7312.02, titled As Built Drawings requires updating of drawings'to incorporate changes to the plant configuration. The licensee's standard DS-010, titled Checking Drawings also contains provisions to reference all affected drawings.
Contrary to the above, control roon drawing, GE 237E726, was not updated to incorporate the plant nodification which installed blind spectacle flanges that provide containnent isolation for the main steam drain. The work package BA 323402 and Safety Evaluation tio. 323402-001 Rev. 1, also neglected to reference this applicable drawing.
Response-Clarification:
Flanges Y-1-57 and Y-1-58 were incorporated in revision 34 of drawing GE-237-E-726 under authority of FCil C04962 dated February 26, 1987. The cause for the initial failure was identified in the finding eg; the nodification package did not identify the drawing as affected.
In addition, the flange information is duplicated on two drawings, BR-2002 and GE-237-E-726. The checker of drawing BR-2002, revision 25 (which did incorporate the change) provided correct notification in a timely manner.
However, he failed at turnover to identify the subject drawing as being affected.
Cause:
GPUll believes this is an isolated occurrence. CPUll judges that the principal cause was the failure of the modification package to identify the directly affected reference drawing.
In addition, the Design and Draf ting staff failed to recognize that GE-237-E-726 required revision when they completed the As-Built docunentation. Technical Functions Engineering Services has taken steps to ensure that the requirenents of DS-002, section 5.2.1.5.e are strictly enforced.
1.
Drafting Standard DS-002 has been revised to require that construction drawings must all carry a note stating which other drawings are affected by construction of the subject drawing.
In order to ensure no nisunderstanding, the wording of the note has been prescribed. Where no drawings are affected the note is still required and will state "none".
46889
sg
~f. N Zi-GPUN 11anagers, ~ Project Engineering, have been' advised that Engineering Services ED&CC personnel.are being required to audit for;
.the existence'of~the-(above)-note.- Releases which'do not comply will' be rejected.
3..
GPUN Supervisors,-Design.and Drafting, have-been directed to specifically review checked As Built Drawings to ensure that affected-drawings are identified as a part.of future As Built Drawing revision-releases. > Additionally they will be sensitized to the-
. existence of duplicateiinformation on some 0yster Creek-drawings such
~
that more than one drawing may be affected.
~The appropriate revision-to DS-002 will be released before liay 30, 1987.=
1,1emorandum EPS-131 (notifying lianagers-Pioject Engineering) was released i
on April-16, 1987.
Additionally, GPUN had previously initiated a drawing update program intended in part to reduce the amount of redundant information contained'
-in controlled drawings. This program is ongoing and will continue into 1988. This program should also serve to reduce the-likelihood of repetition of this violation.
Future Prevention:
1 GPUN judges that the imediate corrective action steps described above will also minimize further violations.
(0490A) 4680g