Amends 88 & 74 to Licenses NPF-4 & NPF-7,respectively, Revising Tech Spec Section 4.7.14 by Increasing Frequency for Fire Pump Diesel Engine Surveillance & Deleting Portion of Surveillance Concerning Starting 24-volt Battery Bank
ML20214F057
Person / Time
Site: North Anna  
Issue date: 11/12/1986
From: Rubenstein L
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20214F058 List:
References
NUDOCS 8611250178
Download: ML20214F057 (10)


Text

-

7-se asc e 4

'c, UNITED STATES'

!5,,.g. j NUCLEAR REGULATORY COMMISSION r

, 'M,p% ' V./

November 12, 1986 W AswsNGTON. D C. 20$$8

's e

"IPGIN A ELECTEIC AND POWEP COMDANY CLC DCtti',!ON ELECTRIC COOPEDATIVE DOCKET NO. 50-338

~

NOPTH ANNA POWEF STATION, UNIT NO. 1 AMEND!'EET TO FACILITY OPE 9ATING LICENSE Amendment No. 88 License No. NPF t 1.

The Nuclear Reculatory Commission (the Commission) has fourd that:

'A.

The;applicatier for amendeert by Virginia Electric ard Power Correny, et al., (the licensce) dated Junc 30, 1986. complies with the stend-6 and requirements of the Atomic Energy Act of 1954, as amended f he t

Act), ard the Commission's rules and regulations set forth in l') CFC Chapter I; P.,

The facility will operate in conformity with the appl'ication, the provisions of the Act, and the rules and reaulations of the Commission; C.

There is reasonable assurance (1) that the activities authorized by this amendnent can be conoucted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the com nr.

defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable recuirenerts have been satisfied.

8611250178 861112 PDR ADOCK 0500 8

P

e i

-2.

2.

Accordingly, the license is amended by charges to the Technical Speci-fications as indicated in the attachment to this license amendment, and paragraph ".D.(?) of Facility Operating License No. NPF-4 is hereby i

arended to read as follors:

(2) Technical Specifications The Technical Specifications centained in Appendices A and B, as revised through Amendment No. 88

. are hereby incorporcted in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as cf the date of its issuance.

FOR THE NUCLEAP. REGULATOP.Y COMMISSION WS.Kdc%

Lester S. Rubenstein, Director l

PWR Project Directorate *?

l Division of PWP. Licensing-A

Attachment:

Changes to the Technical Specifications i

Date of Issuance: N3vember 12, 1986

L ATTACPVENT TO LICENSE AMENr.MFNT NO. 88 TO FACILITY OPERATING t ICEf;SE NO. NPF-4 DOCKET NO. 50-338 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page as indicated.

The revised page is identified by amendment numbar and contains vertical lines indicating the area o" change.

The corresponding overleaf pace is also provided to maintain document completeness.

Page 3/4 7-77 3/4 7-78 O

l i

l i

l i

PLANT SYSTEMS 6

S'IRVEILLANCE REQUIREMENTS (Continued)

At least once per 3 years by performing a flow test of the system in 9

accordance with Chapter 5, Section 11 of the Fire Protection Handbook, 14th Edition, published by the National Fire Protection Association.

4.7.14.1.2 The fire pump diesel engine shall be demonstrated OPERABLE:

At least once per 31 days by verifying:

a.

1.

The fuel storage tank contains at least 220 gallons of fuel, and 2.

The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow.

b.

At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank is within acceptable limits specified in Table 1 of ASTM 0975-74 when checked for viscocity, water and sediment.

At least once per 18 months, during shutdown, by subjecting the c.

diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for the class of service.

4.7.14.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:

At least once per 7 days by verifying that:

a.

1.

The electrolyte level of each battery is above the plates, and 2

The overall battery voltage is > 24 volts, b.

At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.

NORTH ANNA - UNIT 1 3/4 7-77 Amendment No. 3,88 i

_~

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) c.

At least once per 18 months by verifying that:

1 The batteries and battery racks show no visual indication of physical damage or abnormal deterioration, and 2.

The battery-to-battery and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material.

O NORTH ANNA - UNIT 1 3/4 7-78 Amendment No. 3,88

  1. p ** *%q'g UNITED STATES"

! Y.,

f; i NUCLEAR REGULATORY COMMISSION e, \\ k,;#.f f e

v. As.m.cToy c. c. rocss i

g j

VIRGINIA ELECTRIC AND POWER COMPAr'Y OLD DOMINI 0f: ELECTRIC CCCFERATIVE DOCKET N0. 50-339 NORTH ANNA POWER STATION, UNIT NO. 2 APENDMENT TO FACILITY OPEPaTING LICENSE Amendment No. 74 License No. NPF-7 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Virginia Electric and Power Comps.y.

o et al., (the licensee) datec June 30, 1986, complies with the stardards and requirements of the Atomic Energy Act of 19Ea, as amended (the Act), and the Commissior.'s rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity vith the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without e'idancering the health and safety of the public, and (ii) that such activities will be conducted in complicrce with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFP Part 51 of the Commission's reculations and all applicable requirements have been satisfied.

4 2.

Accordingly, the license is amended by changes to the Technical Speci-fications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-7 is hereby amended to read as follows:

4 (2) Technical Specifications i

The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 74

, are hereby incorporated in the license.

The licersee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date cf its issuance.

FOR THE NUCLEAR REGULATOPY COMMISSION

.S. f b

tester S.

.ubenstein, Director PWP Pro,iect Directorate *?

Division cf pWD Licensing-A

Attachment:

Changes to the Technical Specifications Date of issuance: November 12, 1986

, +, - -.

ATTACWFNT TO LICEf'SE AMENDMEf 7 NO. 74 4

TO FACILITY OPEPAT!fG LICENSE NC. NPF-7 DOCKET NO. 50-339 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page as indicated. The revised page is identified by amendnent number and contains vertical lines indicating the area of change.

The corresponding overleaf page is also provided to maintain document completeness.

Pace 3/4 7-6?

e

'l I

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) g.

At least once per 3 years by performing a flow test of the system in accordance with Chapter 5, Section 11 of the Fire Protection Handbook, 14th Edition, published by the National Fire Protection Association.

4.7.14.1.2 The fire pump diesel engine shall be demonstrated OPERABLE:

a.

At least once per 31 days by verifying; 1.

The fuel storage tank contains at least 220 gallons of fuel, and 2.

The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow.

b.

At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank is within the acceptable limits specified in Table 1 of ASlM 0975-74 when checked for viscocity, water and sediment.

c.

At least once per 18 months, during shutdown, by subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for the class of service.

4.7.14.1.3 The fire pump diesel startisg 24-volt battery bank and charger shall be demonstrated OPERABLE:

a.

At least once per 7 days by verifying that:

1.

The electrolyte level of each battery is above the plates, and 2.

The overall battery voltage is greater than or equal to 24 volts.

b.

At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.

NORTH ANNA - UNIT 2 3/4 7-61

PLANT SYSTEMS a

SURVEILLANCE REQUIREMENTS (Continued) c.

At least once per 18 months by verifying that:

1.

The batteries and battery racks show no visual indication of physical damage or abnormal deterioration, and 2.

The battery-to-battery and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material.

NORTH ANNA - UNIT 2 3/4 7-62 Amendment No. 74

__