s l

DOSE SPECIFICATION 4.1-4 (RADIOACTIVE EFFLUENT RELEASE REPORT)

A Semiannual Radioactive Effluent Release Report covering the previous six months of operation operation of the Unit during the shall be submitted within 60 days after January 1 and July 1 of each year.

The radioactive effluent release report to be submitted 60 days after January 1 of each year shall also include an assessment of radiation doses to the hypothetical worst case individual from releases (including doses from primary effluent pathways and direct radiation) for the previous calendar year.

performed in accordance The assessment of radiation doses shall be (ODCM).

with the Off-site Dose Calculation Manual O

O 7 g-J 8611100409 860911 rl: -

PDR ADOCK 05000302

-45a-b PDR R

8

(. /3 DOSE CALCULATION 4.3-4

-U (RADIOACTIVE EFFLUENT RELEASE REPORT)

The individual and population doses are calculated using GASpAR (for gaseous effluents) and LADTAp (for liquid effluents) computer codes obtained from the Nuclear Regulatory Commission, and are revised to include site specific data whenever possible.

Both computer codes incorporate the calculational models and parameters documented in Regulatory Guide 1.109.

Direct radiation doses are taken from the plume Immersion pathway calculated by GASpAR.

Meteorological input data consisting of average relative concen-trations (X/Q's) and average relative deposition values (D/Q's) are provided by coupling GASpAR with the Nuclear Regulatory Commission computer code XOQDOQ (NUREG-0324,

" program for the Meteorological Evaluation of Routine Effluent Releases at Nuclear power Stations").

The summations of gaseous and liquid effluents and solid waste shipments listed in this Report are in accordance with the tables in Regulatory Guide 1.21 (Rev. 1,.6/74).

The summation of solid radioactive waste is derived from Radio-active Shipment Records and reported in accordance with Technical

{;

Specification Section 6.9.1.S(d).

O EVSDN 7

-53a-