VIRGINIA ELECTRIC AND POWER' COMPANY NORTH ANNA POWER STATION UNIT 2 1986' ANNUAL STEAM GENERATOR INSERVICE'INPECTION REPORT G

05000339

.a 9

i

.E.

~

~ VIRGINIA ELECTRIC AND POWER COMPANY,

~

' NORTH ANNA NUCLEAR POWER STATION UNIT NO. 2 1986 ANNUAL STEAM GENERATOR INSERVICE INSPECTION REPORT EDDY CURRENT EXAMINATION I

' During 1986 the steam generator - tubes were' examined once.

This examination occurred during the February refueling outage. Tubes in "A" "B",

and

'_'C". steam generators were examined during _ the outage.

The

' material that follows presents the results of the examinations.

These-l

~

result's include the number and extent of the tubes examined, the location -

and percent of wall-thickness penetration for - each indication : of _ an imperfection, and the identification of the tubes that were plugged. Also included are a "Tubesheet Cross Section Plot" (Figure 1) and " Tube Support Plate /Tubesheet Nomemclature" (Figure 2).

i k-4

.h

7_

c f' &,

.a REFUELING OUTAGE - FEBRUARY 1986 STEAM GENERATOR "A"

. EXAMINATION

SUMMARY

In "A" Steam Generator there were 197 tube examinations from the ' nlet i

' side. -193 tubes were examined to the seventh support plate on the outlet side. and. 4 tubes were examined full length (tubesheet-to-tubesheet).

This is approximately 6. percent of the available tubes.

Two-tubes-were found to have discontinuity indications between 20% and 40% through wall.

-~No tubes were plugged. Refer to the table below for details.

%1VD Location Row-Column Remarks 25 HTS

  • R17C91-28

' HTS

  • R17C91 39 2H R45C36 Plugged 86 HTS R03C06 Plugged
  • Denotes tube with multiple indications.

e

_-,m-._y.,.,

,_r,.

y,,...,_

y

,_,.__.---,.,--,.-.-.,,7-_.

REFUELING OUTAGE - FEBRUARY 1986 STEAM GENERATOR "B"

-EXAMINATION

SUMMARY

In "B" Steam Generator there were 813 tube examinations from the inlet side. 97 tubes were examined to the seventh support plate on the outlet side and 716 tubes were examined ' full length (tubesheet-to-tubesheet).

This is approximately_ 25 percent of the available~ tubes.

One-tube was

- found to have a discontinuity indication less than 20% through wall. One tube was found to have a discontinuity indication between 20% ~ and 40%

through wall.

One tube was. plugged.

Refer to the-table below for -

details.

- %'1VD Location Row-Column Remarks

<20 HTS-1H R13C41 21 2AVB R17C29 96-7H-1AVB R02C05.

Plugged

3.,

.+,-

s.

.g REFUELING OUTAGE.- FEBRUARY 1986 STEAM GENERATOR "C" EXAMINATION

SUMMARY

.In "C" Steam Generator there'were 907 tube examinations from the' inlet side. 191 tubes were' examined to the seventh support plate on -the outlet side and. 716. tubes were. examined full length -(tubesheet-to-tubesheet).

This is approximately 27 percent of the available tubes. Two tubes were found to have discontinuity indications less than 20% through wall. Six tubes were plugged. Refer to the table below for details.

7.*1VD Location Row-Column Remarks

. 20 HTS R17C09

<20 2H R40C32 75 7H-1AVB R02C36 Plugged

,80 7H-1AVB~

  • R02C58 Plugged'

.85 7H-1AVB-

  • R02C56 Plugged

.p 91

-7H-1AVB

  • R02C56 Plugged 95

~7H-1AVB R02C46 Plugged

'96 HTS R02C08 Plugged

  • Denotes tube with multiple indications.

~. -

O

. =

t c

~~k

/

M

\\

- se

~

,f

\\

S

-u 0

--- a l

=

1 j

- as

- OB b

-O 8,

12 g

-e E

i sb

-=

o a-81a-W 8s8 b<a er i{g

,\\

-a g

18 i

>=

a

. og

\\

~.

103 !

'~

)

FIGURE 2

Tube Support Plate /Tubesheet Nomenclature t

8 8

2AVB 3AVB 1AVB 4AVB 7H %

-7C III II 6H -

-6C lll ll SH 5C lll ll 4H 4C Iil iI 3H 3C lll ll l

2H 2C 1C 1H HTS i

Westinghouse Series 51 Inlet Outlet

-