t THE CLEVELAND ELECTR P.O. Box 5000 - CLEVELAND, OHIO 44101 - TELEPHONE (216) 622-9800 - lLLUMINATING BLDG.
- 55 PUBLIC SOUARE Serving The Best Location in the Nation anuary 16, 1987 MURRAY R. EDELMAN PY-CEI/01E-0263 L SR VICE PRESIDENT NUCUAR Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Perry Nuclear Power Plant Docket Nos. 50-440; 50-441 IE Bulletin 85-03, MOV Test Program Scope
Dear Sir:
The Cleveland Electric Illuminating Company, in our letter of May 14, 1986 (PY-CEI/01E-0206 L), identified our participation with the BWR Owners Group (BWROG) to develop a generic BWR position for meeting the requirements of IE Bulletin 85-03.
The Owners Group response was submitted to Mr. Taylor by letter BWROG-8645 dated September 2,1986.
Our program is being implemented and is consistent with the requirements of the Owners Group response.
The valves to be tested in accordance with this Bulletin were tabulated in our May 14 letter. Two additional valves (IE12F052 A&B) have been added to the test scope, and the revised table is attached. The balance of our program remains as previously described.
In an October 10, 1986 letter to the BWROG, OIE expressed a concern with the BWROG ground rules used to select valves for further evaluation and testing.
Valves with no active safety action were excluded; OIE was concerned that such valves may be out of normal position when an accident occurs, requiring opening or closing against differential pressure.
CEI included all motor-operated valves in high pressure injection systems irrespective of normal valve position or safety actions. The OLE concerns are addressed by the CEI program and therefore, are not applicable to Perry.
Please call if you have any questions.
Very truly u r.,
Y s
Murray R. Edelman Senior Vice President Nuclear Group MRE:nje Attachment ec: Jay Silberg, Esq.
Paul Leech (2) fL [j K. Connaughton Region III y
8701210288 870116 Il PDR ADOCK 05000440 0
Attachment PY-CEI/01E-0263 L Page 1 of 3 Perry High Pressure ECCS Motor-Operated Valve Data Operator Data Valve Data Vendor Valve Vendor Type Maximum MPL No.
Size, Type RPM Functional Description Diff. Pressure 1E12F0052 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 1040 PSID A&B 10", GLOBE SMB-2 COOLING MAIN STEAM TO RHR 1700 RPM HEAT EXCHANGER ISOLATION lE22F0001 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 100 PSID 16", GATE SMB-00 CONDENSATE STORAGE TANK TO 1750 RPM HPCS PUMP SUCTION 1E22F0004 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 1575 PSID 12", GATE SB-3 TO REACTOR PRESSURE VESSEL 1700 RPM INJECTOR VALVE 1E22F0010 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 1575 PSID 10", GLOBE SMB-4 SYSTEM PUMP RECIRCULATION 1730 RPM TO CONDENSATE STORAGE TANK 1E22F0011 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 1575 PSID 10", GLOBE SMB-4 SYSTEM PUMP RECIRCULATION 1730 RPM TO CONDENSATE STORAGE TANK IE22F0012 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 1575 PSID 4",
GATE SB-0 SYSTEM MINIMUM FLOW TO 3400 RPM SUPPRESSION POOL 1E22F0015 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 100 PSID 24", GATE SB-1 SUCTION FROM SUPPRESSION 3450 RPM POOL 1E22F0023 GE/ ANCHOR DARLING LIMITORQUE HIGH PRESSURE CORE SPRAY 1575 PSID 12", GLOBE SMB-4 SYSTEM TEST TO SUPPRESSION POOL lE51F0010 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 75 PSID 6",
GATE SMB-00 COOLING PUMP TO CONDENSATE 1900 RPM STORAGE TANK ISOLATION VALVE lE51F0013 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 1400 PSID 6",
GATE SMB-1 COOLING PUNP DISCHARGE VALVE I
,e.
Attachment PY-CEI/01E-0263 L Page 2 of 3 Perry High Pressure ECCS Motor-Operated Valve Data Operator Data Valve Data Vendor Valve Vendor Type Maximum MPL No.
Size, Type RPM Functional Description Diff. Pressure 1E51F0019 ROCKWELL LIMITORQUE REACTOR CORE ISOLt. TION 1400 PSID 2",
GLOBE SMB-000 COOLING MINIMUM FLOW TO 1900 RPM THE SUPPRESSION POOL 1E51F0022 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 1100 PSID 4",
GLOBE SMB-0 COOLING PUMP RETURN TO THE 1900 RPM CONDENSATE STORAGE TANK ISOLATION VALVE 1E51F0031 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 75 PSID 6",
GATE SMB-00 COOLING SUCTION FROM THE 1900 RPM SUPPRESSION POOL ISOLATION VALVE 1E51F0045 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 1177 PSID 4",
GLOBE SMB-0 COOLING TURBINE STEAM SUPPLY VALVE 1E51F0046 ROCKWELL LIMITORQUE REACTOR CORE ISOLATION 1400 PSID 2",
GLOBE SMB-000 COOLING PUMP DISCHARCE TO 1900 RPM AUXILIARY EQUIPMENT COOLANT LOOP 1E12F052 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 1040 PSID A&B 10", GLOBE SMB-2 COOLING MAIN STEAM TO 1700 RPM RRR HEAT EXCHANGER ISOLATION 1E51F0063 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 741 PSID 10", GATE SMB-1 COOLING AND RZSIDUAL HEAT 1900 RPM REMOVAL SYSTEM STEAM SUPPLY ISOLATION VALVE 1E51F0064 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 1177 PSID 10", GATE SB-1 COOLING AND RESIDUAL HEAT 3450 RPM REMOVAL SYSTEM STEAM SUPPLY ISOLATION VALVE i
l L
"=
Attachment PY-CEI/01E-0263 L Page 3 of 3 l'
Perry High Pressure ECCS Motor-Operated Valve Data I
Operator Data Valve Data Vendor Valve
' Vendor Type Maximum
'MPL No.
Size, Type RPM Functional Description Diff. Pressure 1E5 ' 68 BORG-WARNER LIMITORQUE REACTOR CORE ISOLATION 30 PSID 12", GATE SMB-0 COOLING TURBINE EXHAUST TO j
1900 RPM SUPPRESSION POOL ISOLATION 1E51F0076 ROCKWELL LIMITORQUE REACTOR CORE ISOLATION 1177 PSID 4
1",
GLOBE SMB-000 COOLING STEAM WARMUP LINE 1700 RPM ISOLATION AND BYPASS FOR 1E51F0063 1E51F0077 ROCKWELL LIMITORQUE REACTOR CORE ISOLATION 30 PSID 1.5", GLOBE SMB-000 COOLING SYSTEM: VACUUM RELIEF i
1700 RPM FOR REACTOR CORE ISOLATION I
COOLING TURBINE EXHAUST j
1E51F0078 ROCKWELL LIMITORQUE REACTOR CORE ISOLATION 30 PSID 2",
GLOBE SMB-000 COOLING SYSTEM: VACUUM RELIEF j
1700 RPM FOR REACTOR CORE ISOLATION COOLING TURBINE EXHAUST 1851F0510 CE LIMITORQUE REACTOR CORE ISOLATION 1177 PSID 4",
GATE SMB-000 COOLING TURBINE TRIP 1900 RPM THROTTLE 4