ML20212A512

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Re Current Restrictions on Disposal of Accident Generated Water
ML20212A512
Person / Time
Site: Crane 
Issue date: 02/25/1987
From:
GENERAL PUBLIC UTILITIES CORP.
To:
Shared Package
ML20212A456 List:
References
NUDOCS 8703030367
Download: ML20212A512 (4)


Text

F INDEX LIMITING CONDITIONS FOR OPERATION SECTION PAGE 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 A.C.

SOURCES...............................................

3.8-1 3.8.2 ONSITE POWER DISTRIBUTION SYSTEMS A.C. Distribution..........................................

3.8-4 D.C.

Distribution..........................................

3.8-4 3.9 RADIOACTIVE WASTE STORAGE 3.9.1 SPENT FUEL STORAGE POOL "A" WATER LEVEL MONITORING.........

3.9-1 3.9.2 SPENT FUEL STORAGE POOL "A" WATER LEVEL....................

3.9-1 3.9.3 FUEL TRANSFER CANAL (DEEP END) HATER LEVEL MONITORING......

3.9-1 3.9.4 FUEL TRANSFER CANAL (DEEP END) HATER LEVEL.................

3.9-2 3.9.12.1 FUEL HANDLING BUILDING / AUXILIARY BUILDING AIR CLEANUP SYSTEMS..................................................

3.9-2 3.9.13 ACCIDENT GENERATED WATER...................................

3.9-3 3.10 CRANE OPERATIONS 3.10.1 CONTAINMENT BUILDING.......................................

3.10-1 3.10.2 FUEL HANDLING BUILDING.....................................

3.10-1 SURVEILLANCE REQUIREMENTS 4.0 APPLICABILITY....................................................

4.0-1 THREE MILE ISLAND - UNIT 2 V

0703030 Q$$$20 PDil AD gapp P

1.0 DEFINITIONS CORE ALTERATION 1.15 CORE ALTERATION shall be the movement or manipulation of any reactor component (including fuel) within the reactor pressure vessel with the vessel head removed and fuel in the vessel. Suspension of CORE ALTERATION shall not preclude completion of movement of a component to a safe conservative position.

LOSS-T0 AMBIENT 1.16 LOSS-T0 AMBIENT is a passive cooling mode by which decay heat, generated by the reactor core, is removed and transferred to the surrounding environment by air and passive components (i.e., Reactor Vessel) inside the Reactor Building.

ACCIDENT GENERATED WATER 1.17 DELETED 1.18 LICENSED OPERATOR (0L) - any individual who possesses an NRC operator's license pursuant to Title 10, Code of Federal Regulations, Part 55, " Operators Licenses."

1.19 SENIOR LICENSED OPERATOR (SOL) - any individual who possesses an NRC Senior Operator's license pursuant to Title 10, Code of Federal Regulations, Part 55, " Operators Licenses."

1.20 FUEL HANDLING SENIOR LICENSE 0 OPERATOR (SOL-FH) - an individual licensed by the Nuclear Regulatory Commission to supervise fuel handling and core alterations operations.

THREE MILE ISLAND - UNIT 2 1-4

7_

t

~

LIMITING CONDITIONS FOR OPERATION 3.9.12.2 The Auxiliary Building Air Cleanup Exhaust System shall be OPERABLE with exhaust ventilation flow through the HEPA filters during system operation. The Auxiliary Building Air Cleanup Exhaust System is OPERABLE when two of the four system air cleanup exhaust fans are OPERABLE.

APPLICABILITY:

RECOVERY MODE ACTION:

a.

With the Auxiliary Building Air Cleanup Exhaust System inoperable due to flow requirements, return the flow to within acceptable limits within four (4) hours or; b.

With the Auxiliary Building Air Cleanup Exhaust System inoperable (other than as allowed in Paragraph 3.9.12.2.a above), suspend all operations involving movement of liquid and gaseous radioactive wastes in the Auxiliary Building (other than sampling evolutions required by the Technical Specifications or RECOVERY OPERATIONS PLAN) until the system is restored to OPERABLE status.

ACCIDENT GENERATED WATER 3.9.13 DELETED l

l l

i l

THREE MILE ISLAND - UNIT 2 3.9-3 l

C 4

bases 3/4.9 RADIOACTIVE WASTE STORAGE 3/4.9.1 SPENT FUEL STORAGE POOL "A" HATER LEVEL MONITORING Spent Fuel Storage Pool Water "A" Level Monitoring instrumentation has been provided to assure the capability to monitor water level in the Spent Fuel Storage Pool "A".

3/4.9.2 SPENT FUEL STORAGE POOL "A" HATER LEVEL The water level in the Spent Fuel Storage Pool "A" has been established to limit the dose rate, due to the storage of Canisters, to acceptable levels.

3/4.9.3 FUEL TRANSFER CANAL (DEEP END) HATER LEVEL MONITORING Fuel Transfer Canal Water Level Monitoring instrumentation has been provided to assure the capability to monitor water level in the deep end of the Fuel Trardfer Canal.

3/4.9.4 FUEL TRANSFER CANAL (DEEP END) HATER LEVEL The water level in the Fuel Transfer Canal (deep end) has been established to limit the dose rate, due to the storage of the plenum assembly and Canisters, to acceptable levels.

3/4.9.12 FUEL HANDLING BUILDING / AUXILIARY BUILDING AIR CLEANUP SYSTEMS The requirements for the Fuel Handling / Auxillary Building Air Cleanup Systems to be operating or OPERABLE ensure that all radioactive material released from the 11guld radioactive wastes being stored in the new radwaste storage tanks which have been installed in the spent fuel storage pool or elsewhere in the Auxillary Building will be filtered through the HEPA filters prior to release to the atmosphere.

3/4.9.13 ACCIDENT GENERATED WATER DELETED THREE MILE ISLAND - UNIT 2 B 3/4 9-1