e q
ev 8 Effective Date INFORMATION ONLY ANNbNCIATOR RESPONSE AR-952 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 WDB ANNUNCIATOR RESPONSE APPROVED BY: Interpretation tact h,
IAM. Y (S1tNATURE ON FILE)
/
O DATE:
N kh
\\"#
l INTERPRETATION COMTACT:
Manager, Nuclear Plant in 18s!A H s8 h a ~
Operations Support F
. _ _ _ ___.= __
i TABLE OF CONTENTS SECTION PAGE L O PU R P0 S E................................................................., 1
2.0 REFERENCES
1 2.1 IMPLEMENIING REFERENCES............................................ 1 2.2 DEVELOPMENibt REFERENCES........................................... 1 i
3. 0 PERSONNEL INDOCTRINATION................................................ 1 4.0 INSTRUCTIONS............................................................
1 5.0 FOLLOW-UP ACTIONS..................................,....................
1 ENCLOSURE i -
1 An n u n ci ato r Re s Pon s e............................................. 2 i
(
4 d
J d
4 4
J
(
A d
E J '
t
.i
-AR-952 Rev. 8 Page i
1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the WD-WP Lampbox.
1.2
~~
Establish operator actions for valid Annt.aciator alarms on the WD-WP Lampbox.
1.3 Establish a referance to other procedures which address operator actions for valid Annunciator alarms on the WD-WP Lampbox.
2.0 REFERENCES
l.
2.1 IMELEMENTING REFERENCES None 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-050.
3.0 PERSONNEL INDOCTRINATION None 4.0 INSTRUCTIONS 4.1 Respond to alarms on the WD-WP Lampbox as indicated on Enclosure 1 Annunciator Response.
5.0 FOLLOW-UP ACTIONS None O
AR-952 Rev. 8 Page 1
O ENCLOSURE 1 (Page 1 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-2 B-1-2 DECAY HEAT PIT SUMP LEVEL EXTRA HIGH INDICATED CONDITION:
- LEVEL OF DH SUMP 3B> 3' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- DH PIT SUMP PUMP 3B (WDP-38) AUTO-START ALARM DH PIT SUMP PUMP 3B RUN INDICATING LAMPS
- SUMP LEVEL INDICATION ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
O'
- CHECK THAT DH SUMP PUMP 3B IS RUNNING
- CHECK DH SUMP PUMP 3B VALVE LINEUP
- INVESTIGATE DRAINS TO DH PIT SUMP FOR ABNORMAL DRAINAGE DISCUSSION:
THIS ALARM IN CON] UNCTION WITH WDP-3B RUNNING COULD INDICATE A LARGE LEAK IN THE 'B' DH PIT. NOTIFY CORTROL ROOM OPERATOR IMMEDIATELY,
REFERENCES:
DWG 208-060 WD-10 SENSING ELEMENT: WD-134-LS O
AR-952 Rev, 8 Page 2
[]
ENCLOSURE 1
()
(Page 2 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-3 B-1-3
~~~~
AUX BLDG SUMP PUMP 3A AUTO-START INDICATED CONDITION:
- AUX BLDG SUMP LEVEL >2.5'
- AUX BLDG SUMP PUMP 3A (WDP-4A) IS SELECTED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- POSSIBLE AUX BLDG SUMP LEVEL EXTRA HIGH ALARM
- PUMP DISCHARGE PRESSURE ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM. IF FREQUENCY OF AUTO-STARTS IS EXCESSIVE, CHECK VALVE LINEUP OF SYSTEMS DRAINING TO SUMP AND DETERMINE SOURCE.
DISCUSSION:
IF WDP-4A RUNS FOR AN EXCE a vE PERIOD OF TIME, THIS COULD INDICATE PUMP DEGRADATION OR A LARGE LEAK IN THE AUXILIARY BUILDING.
NOTIFY CONTROL ROOM OPERATOR IF RUN TIME IS EXCESSIVE.
REFERENCES:
DWG 208-060 WD-11 SENSING ELEMENT: WD-132-LS O
AR-952 Rev. 8 Page 3
gQ ENCLOSURE 1
(,/
(Page 3 of 15)
RA0 WASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-4 B-1-4 AUX BLDG SUMP
~'"~--
PUMP 3A TRIP INDICATED CONDITION:
- PUMP AUTO-STOPS IF AUX BLOG SUMP LEVEL <1.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM INVESTIGATE VALVE LINEUP / SWITCH POSITION IF AUX BLDG SUMP LEVEL EXTRA HIGH ALARM EXISTS.
DISCUSSION:
THIS IS AN EXPECTED ALARM IF WDP-4A IS MANUALLY STARTED AND AUXILIARY BUILDING SUMP LEVEL <1.5'.
INVESTIGATE ANY OTHER REASON FOR PUMP TRIP,
REFERENCES:
DWG 208-060 WD-11 SENSING ELEMENT: WD-132-LS AR-952 Rev. 8 Page 4
- (}/
t ENCLOSURE _1 (Page 4 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-5 B-1-5 WASTE GAS COMP SEAL LEAK DR TK LOW LEVEL INDICATED CONDITION:
- LOW LEVEL OF 8" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- POSSIBLE RMA-2(G) OR RMA-3 ALARM OPERATOR ACTION FOR A VALID ALARM:
- BLEED AIR OFF WDV-1030 TO CLOSE DISCUSSION:
WDV-1031 SHOULD BE USED TO MANUALLY CONTROL DRAIN POT LEVEL IF WDV-1030 FAILS TO CONTROL,
REFERENCES:
DWG 208-060 WD-135 SENSING ELEMENT: WD-357-LS2 O
AR-952 Rev. 8 Page 5
4 ENCLOSURE 1 (Page 5 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-6 B-1-6 AUX BLDG SUMP PUMP 3B AUTO START INDICATED CONDITION:
- AUX BLDG SUMP LEVEL >2.5'
- AUX BLDG SUMP PUMP 38 (WDP-48) IS SELECTED REDUNDANT INDICATION WhICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- POSSIBLE AUX BLDG SUMP LEVEL EXTRA HIGH ALARM
- PUMP DISCHARGE PRESSURE ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM. IF FREQUENCY OF AUTO-STARTS IS EXCESSIVE, CHECK
-VALVE LINEUP OF SYSTEMS DRAINING TO SUMP AND DETERMINE SOURCE.
DISCUSSION:
IF WDP-4B RUNS FOR AN EXCESSIVE PERIOD OF TIME, THIS COULD INDICATE PUMP DEGRADATION OR A LARGE LEAK IN THE AUXILIARY BUILDING. NOTIFY CONTROL ROOM IF RUN TIME IS EXCESSIVE.
REFERENCES:
DWG 208-060 WD-12 SENSING ELEMENT: WD-132-LS 4
k./
AR-952 Rev. 8 Page 6
= -.
[
ENCLOSURE 1
\\.
(Page 6 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-7 B-1-7 AUX BLDG SUMP PUMP 3B TRIP INDICATED CONDITION:
l
- PUMP AUTO-STOPS IF AUX BLDG SUMP LEVEL <1.5' 4
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR, VALID ALARM:
- NORMAL FUNCTION ALARM INVESTIGATE VALVE LINEUP / SWITCH POSITION IF AUX BLDG SUMP LEVEL EXTRA HIGH ALARM EXISTS.
DISCUSSION:
THIS IS AN EXPECTED ALARM IF WDP-4B IS MANUALLY STARTED AND AUXILIARY BUILDING SUMP LEVEL <1.5'.
INVESTIGATE ANY OTHER REASON FOR PUMP TRIP.
REFERENCES:
DWG 208-060 WD-12 SENSING ELEMENT: Wr'-132-LS f~~
s AR-952 Rev. 8 Page 7
/7 L/
ENCLOSURE 1 (Page 7 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-8 B-1-8 WASTE GAS SAMPLING ANALYZER PANEL IN ALARM INDICATED CONDITION:
- LOSS OF 120 VAC POWER TO GAS ANALYZER PANEL l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- POWER INDICATING LAMP ON PANEL IS OUT
- GAS FLOW <0.2 SLPM l
OPERATOR ACTION FOR A VALID ALARM:
- CHECK PANEL POWER SUPPLY SWITCH h
- CHECK 480 VAC SUPPLY BREAKER ON REACTOR MCC 382 d
- CHECK PUMP OPERATION AND VALVE ALIGNMENT DISCUSSION:
THIS ALARM MAY INDICATE A NEED TO PERFORM AN ALTERNATIVE MEANS OF SAMPLING. NOTIFY CONTROL ROOM OPERATOR IMMEDIATELY.
1
REFERENCES:
DWG 208-060 WD-131, WD-135 SENSING ELEMENT: PF RELAY WD-21-FIS i
O AR-952 Rev. 8 Page 8 4
O ENCLOSURE 1 (Page 8 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-1 B-2-1 AUX BLDG SUMP LEVEL EXTRA HIGH INDICATED CONDITION:
- LEVEL OF AUX BLDG SUMP >5.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- AUX BLDG SUMP PUMP 3A AND/OR 3B AUTO-START ALARMS
- SUMP PL'MP INDICATING LAMPS ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL 4
OPERATOR ACTION FOR A VALID ALARM:
O-
- CHECK THAT AUX BLDG SUMP PUMPS 3A AND/OR 3B ARE RUNNING
- CHECK SUMP PUMP VALVE LINEUP
- DETERMINE SOURCE OF WATER INTO SUMP DISCUSSION:
THIS ALARM IN CONJUNCTION WITH AN AUXILIARY BUILDING SUMP PUMP ALREADY RUNNING MAY BE AN INDICATION OF EITHER PUMP DEGRADATION OR A LARGE LEAK IN THE AUXILIARY BUILDING. NOTIFY CONTROL ROOM OPERATOR IMMEDIATELY.
REFERENCES:
DWG 208-060 WD-11 SENSING ELEMENT: WD-132-LS1 AR-952 Rev. 8 Page 9
3 7
.t-)
ENCLOSURE 1 (Page 9 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-2 B-2-2 WASTE TRANSF Pl'MP 3A AUTO START FAILURE INDICATED CONDITION:
- BLEED TANK 3A SELECTED ON FEED SELECT SWITCH (AND PULLED) l
- MUV-541 OPEN AND
- WASTE TRANSFER PUMP 3A (WDP-5A) NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- MUV-103 INDICATING LAMPS IN CONTROL ROOM
/3 OPERATOR ACTION FOR A VALID ALARM:
w,!
- CHECK VALVE LINEUP, SWITCH POSITIONS AND FEED PERMISSIVE CIRCUITS FOR CORRECT POSITIONS, DISCUSSION:
THIS ALARM WILL OCCUR IF WDP-5A IS SHUT DOWN FOR ANY REASON WHILE ATTEMPTING TO ADD TO THE RCS USING WDT-5A, NOTIFY CONTROL ROOM OPERATOR OF LOCAL INDICATIONS CONCERNING THE REASON FOR WDP-5A SHUTDOWN.
REFERENCES:
DWG 208-060 WD-13 l
SENSING ELEMENT: 42BIELAYF13MUV-541 J
AR-952 Rev. 8 Page 10
O ENCLOSURE 1 (Page 10 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-3 B-2-3 WASTE TRANSF PUMP 3A TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND PUMP NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP MOTOR OVERCURRENT
+
- PUMP STARTED LOCALLY THEN SELECTED FOR FEED g
OPERATOR ACTION FOR A VALID ALARM:
- CHECK FOR PUMP MOTOR OVERLOAD TRIP CONDITION
- CHECK VALVE LINEUP AND SWITCH POSITION
- CALL CGNTROL ROOM TO SEE IF PUMP SELECTED FOR FEED DISCUSSION:
IF WDP-5A WAS RUNNING FOR RCBT RECIRCULATION, A NEW SAMPLE REQUEST WILL HAVE TO BE CENERATED AFTER THE CAUSE OF THE PUMP TRIP IS DETERMINED AND
- RESOLVED,
REFERENCES:
DWG 208-060 WD-13, WD SENSING ELEMENT: CS/SC+CS/0 42B O
AR-952 Rev. 8 Page 11
4 q
ENCLOSURE _1 (Page 11 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-4 B-2-4 l
WASTE TRANSF PUMP 3B AUTO START FAILURE INDICATED CONDITION:
- MUV-541 OPEN AND-BLEED TANK 3B SELECTED ON FEED SEL
]
- WASTE TRANSFER PUMP 3B (WDP-58) NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- MUV-103 INDICATING LAMPS IN CONTROL ROOM Os OPERATOR ACTION FOR A VALID ALARM:
- CHECK VALVE LINEUP, SWITCH POSITIONS AND FEED PERMISSIVE CIRC FOR CORRECT POSITIONS.
DISCUSSION:
ATTEMPTING TO ADD TO THE RCS USING WDP-iB OF LOCAL INDICATIONS CONCERNING THE REASON FOR WDP-
REFERENCES:
DWG 208-060 WD-14 l
SENSING ELEMENT: 428 RELAY F2 3MUV-541 i
a.
l S.
A AR-952 Rev. 8 Page 12
4 O
ENCLOSURE 1 (Page 12 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE
_ _ _ ' WD-WP-2-5 8-2-5 WASTE TRANSF
-~~~
PUMP 38 TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND PUMP NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP MOTOR OVERCURRENT
- PUMP STARTED LOCALLY 1 HEN SELECTED FOR FEED OPERATOR ACTION FOR A VALID ALARM:
- CHECK FOR PUMP MOTOR OVERLOAD TRIP CONDITION CHECK VALVE LINEUP AND SWITCH POSITIOV u
CALL CONTROL ROOM TO SEE IF PUMP SELECTED FOR FEED DISCUSSION:
IF WDP-5B WAS RUNNING FOR RCBT RECIRCULATION, A NEW SAMPLE REQUEST WILL HAVE TO BE CENERATED AFTER THE CAUSE OF THE PUMP TRIP IS DETERMINED AND RESOLVED.
REFERENCES:
DUG 208-060 WD-14, WD-73 SENSING ELEMENT: CS/SC+CS/0 42B a
O AR-952 Rev. 8 Page 13
4 i
ENCLOSURE 1 (Page 13 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-C-2-6 B-2-6 WASTE TRANSF
~~~'~---
PUMP 3C AUTO START FAILURE j
INDICATED CONDITION:
I
- BLEED TANK 3C SELECTED ON FEE 0 SELECT SWITCH (AND PULLED)
\\
- MUV-541 OPEN AND
- WASTE TRANSFER PUMP 3C (WDP-50 NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- MUV-103 INDICATING LAMPS IN CONTROL ROOM
- q OPERATOR ACTION FOR A VALID ALARM:
1
- CHECK VALVE LINEUP, SWITCH POSITIONS AND FEED PERMISSIVE CIRCUITS FOR CORRECT POSITIONS.
DISCUSSION:
THIS ALARM WILL OCCUR IF WDP-SC IS SHUT DOWN FOR ANY REASON WHILE ATTEMPTING TO ADD TO THE RCS USING WDP-SC.
NOTIFY CONTROL ROOM OPERATOR OF LOCAL INDICATIONS CONCERNING THE REASON FOR WDT-SC SHUTDOWN.
REFERENCES:
DWG 208-060 WD-15 SENSING Et.EMENT: 42B RELAY F3 3MUV-541 4
- O AR-952 Rev. 8 Page 14
'l 4
?
ON ENCLOSURE 1 (Page 14 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-7 B-2 WASTE TRANSF PUMP 3C TRIP INDICATED CONDITION:
PUMP CONTROL SWITCH IN NOR-AFT-STGT POSITION AND PUMP NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY A ARM:
PUMP MOTOR OVERCURRENT PUMP STARTED LOCALLY THEN SELECTED (OR FEED O
OPERATOR ACTION FOR A VALID ALARM:
- CHECK FOR PUMP MOTOR OVERLOAD TRIP CONDITION
- CHECK VALVE LINEUP AND SWITCH POSITION
- CALL CONTROL ROOM TO SEE IF PUMP SELECTED FOR FEED DISCUSSION:
IF WDP-5C WAS RUNNING FOR RCBT RECIRCULATION, A NEW SAMPLE REQUEST WILL HAVE TO BE GENERATED AFTER THE CAUSE OF THE PUMP TRIP IS DETERMINED AND RESOLVED.
REFERENCES:
DWG 208-060 WD-15. WD-74 SENSING ELEMENT: CS/SC+CS/0 42B AR-952 Rev. 8 Page 15
1
(
O'-
ENCLOSURE 1 (Page 15 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-8 B-2-8 MISC RAD
--~""""----
WASTE TRANSF PUMP 3A TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND WDP-6A NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- CHECK VALVE LINEUP AND DETERMINE CAUSE OF PUMP MOTOR OVERLOAD TRIP
(
CONDITIONS DISCUSSION:
-THIS PUMP DOES NOT AUTO SHUT DOWN ON LOW MISCELLANEOUS WASTE STORAGE TANK (MWST) LEVEL.
IF PROCESSING TO THE ECST'S, CARE SHOULD BE TAKEN TO PREVENT RUNNING WDP-6A WITH NO LEVEL IN THE MWST.
REFERENCES:
DWG 208-060 WD-16 SENSING ELEMENT: CS/SC+CS/0 42B
\\
n)
L AR-952 Rev. 8 Page 16 (LAST PAGE)