ML20211J702

From kanterella
Jump to navigation Jump to search
Special Rept:On 860119,valid Failure Occurred on Diesel Generator 1A.Caused by Failure of Fuel Supply make-up Solenoid Valve to Open.Day Tank Manual Bypass Supply Valve Opened to Refill Day Tank
ML20211J702
Person / Time
Site: Catawba 
Issue date: 02/18/1986
From: Tucker H
DUKE POWER CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8611110225
Download: ML20211J702 (2)


Text

W A

DUKE PowEn GOMPANY S{/

P.O. DOx 33100 citAltLOTTE, N.C. 28242 IIAL H. TUCKER TEIEPHONE cro4> ora-4soi LU f[] N A10 : Is February 18, 1986 Dr. J. Nelson Grace, Regional Administrator U.

S.

Nuclear Regulatory Commission Region II 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323 Re:

Catawba Nuclear Station, Unit 1 Docket No. 50;-413 Q

Dear Dr. Grace:

Pursuant"to' Technical Specification 4?8.t171:3' ands 6.'9.2',

please find attached a Special Report concerning the valid failure of Diesel Generator 1A which occurred on January 19, 1986.

Very truly yours, W

y

/

W Hal B. Tucker RWO:slb Attachment cc:

Director Office of Inspection adn Enforcement U.

S. Nuclear Regulatory Commission Washington, D.

C.

20555 NRC Resident Inspector Catawba Nuclear Station

$s *b 8611110225 860218 PDR ADOCK 0500 3

0;71cla Copy S

g vg6

sty, e

14

.(j.

O,,

e n

SPECIAL REPORT DIESEL GENERATOR 1A VALID-FAILURE

,/,

t' V

On January 19, 1986 a valid failure occurred'on Diesel Generator

. i (D/G) 1 A.'

This valid failure was the fifth failure within the last 75 valid tests for the Catawba Unit 1 Diesel Generators.

Please

^

note that as.of January 19, 1986, the 1A'and 1B Diesel Generators had only completed 75 valid tests (this includes the five valid failures).

The failure occurred while the lA D/G was running in the fully

^~

loaded condition.

During the test, the fuel supply make-up x'

solenoid valve failed to open and provide fuel for the 1A D/G day tank.

Thirty-three minutes into the test, the lA D/G tripped due s

to a lack of fuel.

To correct the malfunction, the lA D/G day tank manual bypass supply valve was opened to refill the day tank.

In addition, an auxiliary. fuel oil pump was used to refill the 1A D/G fuel supply piping.

The lA D/G was restarted and verified ope'rable-by performing the 1A D/G operability periodic test.

The 1A D/G was.

. declared inoperable on January 19, 1986 at 2245 and was t,

w subsequently declared operable on January 20, 1986 at 1600.

,;n s

There fore, the 1A D/G was out of service for 17 hours1.967593e-4 days <br />0.00472 hours <br />2.810847e-5 weeks <br />6.4685e-6 months <br /> and 15

/

minutes.. At this time,-the surveillance testing interval is 3 days e,

which is in accordance with Section C.2.d.4 of Regulatory Guide-

c. ~

1.108' Revision 1 (Periodic Testing of Diesel Generator Units Used i

as Onsite Electric Power Systems at Nuclear Power Plants).

~

/

k h

'+

s

. -... _. -.