Grants Relief from Tech Spec Requirement Re Degraded Grid Voltage Setpoints While Plant in Modes 4 & 5 & Until Setpoints Adjusted,Per 860611 Request
ML20211H249
Person / Time
Site: Fermi 
Issue date: 06/13/1986
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Agosti F
DETROIT EDISON CO.
References
NUDOCS 8606230419
Download: ML20211H249 (2)


Text

dk

'a g

June 13, 1986 Docket No. 50-341 The Detroit Edison Company ATTN:

Frank E. Agosti Vice President Nuclear Operations 6400 North Dixie Highway Newport, MI 48166

Dear Mr. Agosti:

This relates to your request dated June 11, 1986, for an emergency amendment to the Fermi 2 Technical Specifications Regarding the Degraded Grid Voltage Setpoints, and the response dated June 13, 1986 from Robert M. Bernaro, NRR.

You have identified that the setpoints for the Division I degraded grid voltage i

protection system in your Technical Specifications are nonconservative with the result that some of the motors on motor operated valves might be damaged in the event of a low-grid voltage on the 120 KV line feeding the-switchyard.

This condition renders Division I-technically inoperable.

As documented in Mr. Bernaro's June 13, 1986 letter, this condition has been reviewed by the Office of Nuclear Reactor Regulation and it has been determined that it is acceptable for an interim period until a Technical 4

Specification change can be made and the setpoints adjusted to an appropriate value.

Based on my review of this matter, I conclude that this situation will not adversely affect public health and safety. Accordingly, I am granting you relief from the applicable Technical Specification requirement while the plant is in modes 4 and 5 and until such time as a change is granted and the setpoints are appropriately adjusted.

Sincerely, 1

James G. Keppler Regional Administrator cc: See Attached Distribution i

V L

j B606230419 860613 i

PDR ADOCK 05000341 glg p

PDR

k-:%'

The Detroit Edison Company June 13, 1986 Distribution cc:

J. E. Conen, Licensing Engineer P.a4. Marquardt, Corporate Legal Department e

DCS/RSB (RIDS)

Licensing Fee Management Branch Resident Inspector, RIII Ronald Callen, Michigan i

Public Service Commission Harry H. Voight, Esq.

Nuclear Facilities and Environmental Monitoring Section Monroe County Office of Civil Preparedness i

i RIIL RI i

Norelius/ls K@pler l'

6/\\h/86 6/ ky86

.