ML20211H049
| ML20211H049 | |
| Person / Time | |
|---|---|
| Site: | Byron |
| Issue date: | 10/29/1986 |
| From: | COMMONWEALTH EDISON CO. |
| To: | |
| Shared Package | |
| ML20211H046 | List: |
| References | |
| NUDOCS 8611040386 | |
| Download: ML20211H049 (1) | |
Text
-
'o PLANT SYSTEMS 3/4.7.4. ESSENTIAL SERVICE WATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.4.2 The Essential Service Water System Unit Crosstie shall be either open or capable of being opened from the Main Control Board as a flow-path between Units 1 and 2.
APPLICABILITY:
Modes 1, 2, 3, and 4.
ACTION:
a.
With one or both of the crosstie valve (s) closed and not capable of being opened from the Control Room, within 7 days restore the valve (s) to available status or open the affected valve (s), and maintain the affected valve (s) open; otherwise be in at least IlOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SIIUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
b.
The provisions of Specification 3.0.4 are not appliceble.
SURVEILLANCE REQUIREMENTS 4.7.4.2 The Essential Service Water System Unit Crosstic shall be demonstrated available:
a.
At least once per 92 days by cycling crosstie valves 1SX005 and 2SX005 or verify valve is locked open with power removed.
b.
The provisions of Specification 4.0.4 are not applicable.
8611040386 861029 PDR ADOCK 05000454 P
PDR Byron Units 1 and 2 3/4 7-12c
- 40/15