ML20211B394

From kanterella
Jump to navigation Jump to search
Forwards Addl Info Re Tech Spec Improvement Program on Protective Devices for non-Class 1E Circuits Connected to Class 1E Power Sources.Info Will Be Formally Incorporated in Future FSAR Amend
ML20211B394
Person / Time
Site: Seabrook  
Issue date: 10/14/1986
From: George Thomas
PUBLIC SERVICE CO. OF NEW HAMPSHIRE
To: Novak T
Office of Nuclear Reactor Regulation
References
SBN-1213, NUDOCS 8610170224
Download: ML20211B394 (16)


Text

.

George S. Thomas UI vice President-Nuclear Production PLhIc Service of New Hampshire SBN-1213 New Hampshire Yankee Division T.F. B7.1.2 October 14, 1986 United States Nuclear Regulatory Commission Washington, DC 20555 Attention:

Mr. Thomas M. Novak, Acting Director Division of PWR Licensing-A

References:

(a) Construction Permits CPPR-135 and CPPR-136, Docket Nos. 50-443 and 50-444 (b) PSNH Letter SBN-1190 dated September 10, 1986, "Seabrook Station Technical Specification Improvement Program,"

J. DeVincentis to T. M. Novak.

Subj ect : Seabrook Station Technical Specification Improvement Program

Dear Sir:

Reference (b) provided a draf t FSAR Section 16.3 which contained those items included in Standard Technical Specifications which have been removed from the Seabrook Station Technical Specifications. Additional discussions with the NRC staff have necessitated the inclusion of additional information in this FSAR Section. This information is provided as Enclosure 1 and will be formally incorporated into the Seabrook Station FSAR in a future amendment.

Should you have any questions concerning this matter, please contact Mr. Warren Hall at (603) 474-9574, extension 4046.

Very truly yours, Geor e S. Thomas Enclosure cc: Atomic Safety Licensing Board Service List 01 p

4 861014-

\\

A-M 05000443;.

O 9DR _.. i)

^~

\\

\\

P.O. Box 300. Seabrook, NH 03874. Telephone (603) 474-9574

9 Requirement 7 - Fire Suppression Water Systems The fire suppression water systems required to be operable by the Seabrook Station Fire Protection Program shall be operable in accordance with TR7-3.7.9.1.

Requirement 8 - Spray and/or Sprinkler System The spray and/or sprinkler systems required to be operable by the Seabrook Station Fire Protection Program shall be operable in accordance with TR8-3.7.9.2.

Requirement 9 - Fire Hose Stations The fire hose stations required to be operable by the Seabrook Station Fire Protection Program shall be operable in accordance with TR9-3.7.9.3.

Requirement 10 -' Yard Fire Hydrants and Hydrant Hose Stations The yard fire hydrants and hydrant hose stations required to be operable by the Seabrook Station Fire Protection Program shall be operable in accordance with TR10-3.7.9.4.

Requirement 11 -- Fire Rated Assemblies The fire rated assemblies required to be operable by the-Seabrook Station Fire Protection Program shall be operable in accordance with TR11-3.7.9.5.

Requirement 12 - Fire Detection Instrumentation The fire detection instrumentation required to be operable by the Seabrook Station Fire Protection Program shall be operable in accordance with TR12-3.3.3.7.

Requirement 13 - Containment Penetration Conductor Overcurrent Protection The containment penetration conductor overcurrent protective devices required by Technical Specification 3.8.4.2 shall be as shown in FSAR Table 16.3-8.

Requirement 14 - Motor Operated Valves Thermal Overload Protection The thermal overload protection for motor operated valves required by Technical Specification 3.8.4.3 shall be as shown in FSAR Table 16.3-9.

Requirement 15 - Protective Devices for Non-Class IE Circuits Connected to Class IE Power Sources The protective devices for Non-Class IE circuits connected to Class IE power sources required by Technical Specification 3.8.4.2 shall be as shown in FSAR Table 16.3-10.

C

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS 1E CIRCUITS CONNECTED TO CLASS 1E POWER SOURCES CT Secondary Verification Device Number Test Current Time System and Location (amps)

(seconds)

Powered Instant Instant Long-time Long-time 1.

4.16 kV Circuit Breaker Bus 5 - Overcurrent Trip Devices - IAC Relays Start-up Feed 72.2-79.8 0.03 FW Pump 12 9.3-10.7 FW-P-113 1

I f

1

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Long-time Long-time II.

480V a.

Unit Substation Bus ES3 Secondary 9600*

.48.84 EDE Breaker 4800 10-28 Bus E63 Secondary 9600*

.48.84 EDE Breaker 4800 10-28 MCC E511 Feeder 3600*

.14.35 EDE Breaker 1800 10-30 liCC E523 Feeder 3600*

.14.35 EDE Breaker 1800 10-30 Pressurizer Heater 2000-3000 0.11 RC Back-up Group A 1800 7-35 RC-PP-6A MCC E611 Feeder 3600*

.14.35 EDE Breaker 1800 10-30 i

Pressurizer Heater 2000-3000 0.11 RC Back-up Group B 1800 7-35 RC-PP-6B 1

(*) - Short time value.

l 2

4

,.~,.n

.,,,.,n.~

-., +,. - -

,,,7

.-,.n

.-e,

' ~

TECHNICAL REQUIREHENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS 1E CIRCUITS CONNECTED TO CLASS 1E POWER SOURCES (Continued) 3 Test Verification Setpoint

-Time System (amps)

(seconds)

Powered Instant Instant I

Long-time Long-time III. Motor Control Centers a.

Type HE3 Thermal-Magnetic Circuit Breaker MCC-E513 Security Lighting Panel 450-1400 0.067 EL ED-MM-170C 120 18-75 Power Receptacles 450-1400 0.067 300 18-75 t.

Cooling Tower SWGR RM 300-980 0.067 SWA Train A Heater SWA-UH-112 45 6-70 Cooling Tower SWGR RM 300-980 0.067 SWA Train A Heater SWA-UH-113 45 6-70 SW System Process Heat Tracing 300-980 0.067 HT Dist. Panel HT-CP-428 45 6-70 25KVA XM4R for 450-1400 0.067 ED Lighting Panel ED-X-29 210 18-75 Cooling Tower Fan 51A 300-980 0.067 SW Gear Red. Imrs. Heater 45 6-70 SW-H-67A 15 KVA XM4R for Sec.

450-1400 0.067 SFD and Fire Det. Power Panel 120 18-75 SFD-PP-179 15 KVA XM4R for 24 450-1400 0.067 Circuit Distr. Panel 120 18-75 l

1 4

.~

m_.._,

._,,_-__,_-...__.,_m.

,,.._.,r

_-s_._

m,

.._-..._.._-,m._

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System-(amps)

(seconds)

Powered Instant Instant Long-time Long-time-III. Motor Control Centers (Continued) a.

Type HE3 Thermal-Magnetic Circuit Breaker (Continued)

MCC-E514 Security Lighting 300-980 0.067 ED Panel EDHMM-159E 60 6-70 j

Lighting Panel 450-1400 0.067 ED ED-MM-159D 120 18-75 1

Lighting Panel 450-1400 0.067 ED ED-MM-159C 120 18-75 15 KVA XFMR for Sec.

450-1400 0.067 SFD and Fire Det. Power Panel 120 18-75 SFD-PP-180 MCC-E641 Cooling Tower SWGR RM 300-980 0.067 SWA Train B Heater 45 6-70 SWA-UH-Il4 Cooling Tower SWGR RM 300-980 0.067 SWA Train B Heater 45 6-70 SWA-UH-IIS SW System Process 300-980 0.067 HT Heat Tracing Distr. Panel 45 6-70 HT-CP-429 Cooling Tower Fan SIB 300-980 0.067 SW

^

Gear Red. Imts. Heater 45 6-70 SW-H-67B Cooling Tower Fan SIB 300-980 0.067 SW Cear Red. Imrs. Hester 45 6-70 2-SW-H-67B 4

I 1

y

--v--

-y-.-.-

-.w,

.,.~,,,,.

...,,---,--,-.--,-,--+-.%-1,-.z.-mmm,-,,..,----,.-,,---c--,-c-#,,..y--m,,,--,

- - ~..

,m

...mre.~,.r-.w-.

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered 1

Instant Instant Long-time Long-time III. Motor Control Centers (Continued) b.

AMPCAP Motor Circuit Protector MCC-E514 CW Pumps Lube 129-241 0.067 CW Booster Pump CW-P-136 c.

Type G30T Thermal Overload Relays MCC-E514 CW Pumps Lube 31 27-98 CW Booster Pump 46.5 12-40 CW-P-136 t

1 i

I 5

1

{

4

,s.--

.,,,-.,._.-,r.,,,,n,,

-,_.c.

.,,.,,,.,,,,~,_-,.w

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS 1E CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Long-time Long-time IV.

Low Voltage Circuit Breakers (125V de and 120V ac)

Type BQ Thermal Magnetic MCC-E512. 120V ac Distr. Panel 2

Circuit #13 150-420 0.067 ED 45 5-21 Circuit #14 150-420 0.067 ED 45 5-21 Circuit #15 150-420 0.067 ED 45 5-21 Circuit #16 150-420 0.067 ED 45 5-21 Circuit #17 150-420 0.067 FP 45 5-21 Circuit #18 150-420 0.067 FP 45 5-21 Circuit #19 150-420 0.067 FP i

45 5-21 l

Circuit #20 150-420 0.067 FAH 45 5-21 Circuit #21 150-420 0.067 LD 45 5-21 l

Circuit #22 150-420 0.067 EAH l

45 5-21 Circuit #23 150-420 0.067 LD 4

45 5-21 Circuit #24 150-420 0.067 EAH j

45 5-21 6

l t

, _ _ _ _ _. _ _ _. _ _ _ _ _. _ _. _ _.,.__.~

~

~

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS 1E CIRCUITS CONNECTED TO CLASS 1E POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Overload Overload IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac)

Type BQ Thermal Magnetic MCC-E621,120V ac Distr. Panel Circuit #13 150-420 0.067

.ED 45 5-21 Circuit #14 150-420 0.067 ED 45 5-21 Circuit #15 150-420 0.067 ED 45 5-21 Circuit #16 150-420 0.067 ED 45 5-21 MCC-E521,120V ac Distr. Panel Circuit #13 150-420 0.067 ED 45 5-21 Circuit #14 150-420 0.067 ED 45 5-21 Circuit #15 150-420 0.067 ED 45 5-21 i

Circuit #16 150-420 0.067 ED 45 5-21 circuit #17 150-420 0.067 FP 45 5-21 Circuit #18 150-420 0.067 FP 45 5-21 i

7

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS 1E CIRCULTS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Ove rload Overload IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac)

MCC-ES21, 120V ac Distr. Panel (Continued)

Circuit #19 150-420 0.067 FP 45 5-21 Circuit #20 150-420 0.067 FP 45 5-21 Circuit #21 150-420 0.067 FP 45 5-21 Circuit #22 150-420 0.067 FP 45 5-21 Circuit #23 150-420 0.067 FP 45 5-21 Circuit #24 150-420 0.067 FP 45 5-21 MCC-E612, 120V ac Distr. Panel Circuit #13 150-420 0.067 ED 45 5-21 Circuit #14 150-420 0.067 ED 45 5-21 Circuit #15 150-420 0.067 ED 45 5-21 Circuit #16 150-420 0.067 FAH 45 5-21 Circuit #18 150-420 0.067 EAH 45 5-21 Circuit #20 150-420 0.067 FAH 45 5-21 8

i

TECHNICAL REQUIREHENT ~ 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS 1E CIRCUITS CONNECTED TO CLASS 1E POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Overload Overload IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac)

MCC-E515, 120V ac Distr. Panel Circuit #13 150-420 0.067 ED 45 5-21 Circuit #14 150-420 0.067 MM 45 5-21 Circuit #15 150-420 0.067 FP 45 5-21 Circuit #16 150-420 0.067 ED 45 5-21 Circuit #17 150-420 0.067 FP 45 5-21 Circuit #18 150-420 0.067 FP 45 5-21 Circuit #19 150-420 0.067 FP 45 5-21 Circuit #20 150-420 0.067 FP 45 5-21 Circuit #21 150-420 0.067 FP 45 5-21 Circuit #22 263-980 0.067 ED 60 7-25 Circuit #23 150-420 0.067 ED 60 5-21 9

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Overload Overload IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac)

MCC-E615,120V ac Distr. Panel Circuit #13 150-420 0.067 ED 45 5-21 Circuit #14 150-420 0.067 MM 45 5-21 MCC-E641,120V ac Distr. Panel Circuit #1 150-420 0.067 ED 45 5-21 Circuit #2 263-980 0.067 EDE 60 7-25 MCC-E614, 120V ac Distr. Panel Circuit #2 150-420 0.067 SWA 45 5-21 Circuit. #3 150-420 0.067 SEC 45 5-21 Circuit #5 150-420 0.067 EDE 45 5-21 MCC-E514, 120V ac Distr. Panel Circuit #1 150-41' 0.067 ED 45 5-21 Circuit #2 150-420 0.067 ED 45 5-21 Circuit #3 150-420 0.067 ED 45 5-21 l

Circuit #4 150-420 0.067 ED 45 5-21 Circuit #5 263-980 0.067 ED 60 7-25 10

3 TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Overload Overload IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac)

MCC-E514,120V ac, Distr. Panel (Continued)

Circuit #6 263-980 0.067 ED 60 5-21 Circuit #7 150-420 0.067 SWA 45 5-21 i

circuit #10 150-420 0.067 SEC 45 5-21 l

Circuit #11 150-420 0.067 SEC 45 5-21 Circuit #12 150-420 0.067 SEC 45 5-21 Circuit #13 150-420 0.067 SEC i

45 5-21 Circuit #14 150-420 0.067 SEC 45 5-21 Circuit #15 150-420 0.067 FP 45 5-21 Circuit #16 150-420 0.067 SEC 45 5-21 circuit #17 150-420 0.067 ED

{

45 5-21 Circuit #18 150-420 0.067 FP 45 5-21 Circuit #19 150-420 0.067 ED 45 5-21 e

Circuit #21 150-420 0.067 SEC 45 5-21 11

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS'IE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered l

Instant Instant.

Overload Overload 4

IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac)

Type E2 Thermal Magnetic 120V ac Distr. Panel PP-1A circuit #10 300-980 0.067 ED 45

.4.5-70 q

120V ac Distr. Panel PP-1B Circuit #10 300-980 0.067 ED 45 4.5-70 120V ac Distr. Panel PP-lC J

Circuit #10 300-980 0.067 ED 45 4.5-70 Circuit #14 450-1260 0.067 ED 120 4.5-70 120V ac Distr. Panel PP-lD i

circuit #9 300-980 0.067 ED 45 4.5-70 I

120V ac Distr. Panel PP-lE Circuit #14 300-980 0.067 ED t

45 4.5-70 i

Circuit #20 450-1260 0.067 ED 180 4.5-70 120V ac Distr. Panel PP-1F t

Circuit #14 300-980 0.067 ED 45 4.5-70 i

l 12 l

I

.-. - - -, -.., -. - - ~..

---,,,...,--,,-,,--,,.--,-.,--,.w,,,,.-,-,.,-.,,,+.,,.,w..

-. -, - ~,,,, - - - -.., -. - - -

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant 4

Overload, Overload IV.

Low Voltage Circuit Breakers (Continued)

(125V de and 120V ac) 120V ac Distr. Panel PP-llF Circuit #11 263-980 0.067 MM 45 7-25 125V de Distr. Panel PP-lllB Circuit #18 450-1260 0.067 EDE 300 4.5-70 I

i i

l i

13 l'

-,.m

-. -. - - mmre y-,, w.,,--,-,,. n.,

.--e

.nr

-g-,---++-

- n

..--r,,--,------m.a-w.,-,,wn,--r.m-e-n,--,-


,--w a---v s.,,-

- ~.

,e--

I*

TECHNICAL REQUIREMENT 15 TABLE 16.3-10 PROTECTIVE DEVICES FOR NON-CLASS lE CIRCUITS CONNECTED TO CLASS lE POWER SOURCES (Continued)

Test Verification Setpoint Time System (amps)

(seconds)

Powered Instant Instant Long-time Long-time V.

125V de Circuit Breaker i

UPS ED-I-2A 2400-3600 0.11 EDE 1800 10-30 I

1 6

1 l

l 4

i s

+

}

i 1

+

i 14 1

l

,