February 9, 1987 s
Mr. F. R. Standerfer Vice President / Director Three Mile Island Unit 2 GPU Nuclear Corporation P.O. Box 480 Middletown, Pennsylvania 17057
Dear Mr. Standerfer:
Subject:
Three Mile Island Nuclear Station Unit 2 Operating License No. DPR-73 Docket No. 50-320 Approval of Exemption from 10 CFR 50, Appendix A
\\
General Design Criteria 17 and 19 We have reviewed your request dated December 10, 1986, for exemption from the requirements of 10 CFR 50 Appendix A, General Design Criteria (GDC) 17 and 19, regarding provisions for onsite electric power systems and control rooms. As discussed in the enclosed Exemption, TMI-2 is in long-term cold shutdown and is precluded from power operation.
In this mode and because of the current
[
condition of the facility, no actions on the part of control room personnel are
(
required to maintain the facility in a safe shutdown condition. Therefore, continuous manning of the control room is not necessary under accident condi-tions and continuous operability of the control room emergency air cleanup system need not be provided by an onsite backup emergency power source.
Additionally, as the control room emergency air cleanup system represents the only remaining load on the emergency diesel generators that was formerly important to safety, the diesel generators are no longer needed as an onsite electric power source necessary for maintenance of TMI-2 in a safe shutdown condition. We conclude that your request for exemption from GDC 17 and 19 of 10 CFR 50, Appendix A is appropriate and acceptable, as stated in the enclosed Exemption. Please note that a partial exemption to GDC 19 has been granted, consistent with your request. This Fyemption and the accompanying environmental assessment have been forwarded to the Office of the Federal Register for publi-cation.
Sincerely, W liia D. Travers, Director TMI-2 Cleanup Project Directorate Office of Nuclear Reactor Regulation
Enclosures:
1.
Exemption 2.
Environmental Assessment and Notice of Finding of No Significant Environmental Impact cc: See next page
- See previous concurrences.
Office:
TC/PBIU D/TMI2PD, CGC/Beth D/DPLB Concurrees:
RHall/jm WTravers LChandler*
FMiraglia Date:
1/15 /87 1/15 /87 1/22 /87 J/3 /87 8702180067 870209 DR ADOCK 05000320 p
- - w f
A v
Fl: R. : Standerfer.
' 2-February 9,1987-
~
~
cc: ~ T. F. Demitt -
' R. E. Rogan S;-: Levin J. E..Frew J. J. Byrne A. W. Miller
- Service Distribution List (See attached)'-
f r v ww
--wra-1 e
-m*m k<,-w
-- -, - - -w e-,--pe<.,
e = -,eeme- +c v p - m m _.
h 6 '.
s'
-Local'PDR TFI2 HQ r/f
.TMI Site r/f-FMiraglia WTravers RHall MMasnik 0GC/LChandler/Beth OGC/MWagner/Beth IAE-(5 Copies)-
TBarnhart (4 cys for each docket No.)
ACRS (10)
LFMB
l TMI-2 SERVICE LIST t:
l:
Dr. Thomas Murley Regional Administrator U.S. Department of Energy U.S. Nuclear Regulatory Commission P.O. Box 88-631 Park Avenue Middletown, PA 17057-0311~
King of Prussia, PA 19406 David J. McGoff 6
Sheldon J. Wolfe, Esq., Chairman Office of LWR Safety and L
Administrative. Judge Technology Atomic Safety and Licensing Board Panel NE-23 U.S. Nuclear Regulatory Commission U.S. Department of Energy Washington, D.C.
20555 Washington, D.C.
20545 Dr. Oscar H. Paris William Lochstet Administrative Judge 104 Davey Laboratory Atomic Safety and Licensing Board Panel Pennsylvania State University U.S. Nuclear Regulatory Commission University Park, PA 16802 Washington, D.C.
20555 Frank Lynch, Editorial Dr.' Frederick J. Shon The Patriot Administrative Judge 812 Market Street Atomic Safety and Licensing Board Panel Harrisburg, PA 17105 U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Robert B. Borsum Babcock & Wilcox Dr. Judith H. Johnsrud Nuclear Power Divisien Environmental Coalition en Nuclear Power Suite 220 433 Orlando Avenue 7910 Woodmont Avenue State College, PA 16801 Bethesda, MD 20814 Ernest L. Blake, Jr., Esq.
Michael Churchhill, Esq.
Shaw, Pittman, Potts, and Trowbridge PILCOP 2300 N Street, N.W.
1315 Walnut Street, Suite 1632 Washington, D.C.
20037 Phil6delphia, PA 19107 Atomic Safety and Licensing Board Panel Marvin I. Lewis U.S. Nuclear Regulatory Commission 7801 Roosevelt Blvd. f62 Washington, D.C.
20555 Philadelphia, PA 19152 Secretary Jane Lee U.S. Nuclear Regulatory Conmission 183 Valley Road Washington, D.C. 20555 Etters, PA 17319 Frederick S. Rice, Chairman Walter W. Cohen, Consumer Dauphin County Board of Commissioners Advocate Dauphin County Courthouse Department of Justice Front and Market Streets Strawberry Square, 14th Floor Harrisburg, PA 17101 Harrisburg, PA 17127 Thomas M. Gerusky, Director Mr. Edwin Kintner Bureau of Radiation Protection Executive Vice President Department of Environmental Resources General Public Utilities P.O. Box 2063 Nuclear Corporation Harrisburg, PA 17120 100 Interpace Parkway Parsippany, NJ 07054 Ad Crable Lancaster New Era US Environmental Prot. Agency 8 West King Street Region III Office Lancaster, PA 17601 ATTN:
EIS Coordinator Curtis Building (Sixth Floor) 6th and Walnut Streets Philadelphia, PA 19106
_