_ _ _ - _ _ _ _ _ _ _ _ _ _

matoo p

t UNITEG) STATES S

NUCLEAR REGULATORY COMMISSION

=

f WASHINGTON, D.C. 30MH001

  • s...../

l SOUTHERN NUCLEAR OPERATING COMPANY. INC.

GEORGIA POWER COMPANY l

OGLETHORPE POWER CORPORATION MUNICIPAL ELECTRIC AUTHORITY OF GEORGIA CITY OF DALTON. GEORGIA VOGTLE ELECTRIC GENERATING PLANT. UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 98 License No. NPF-68 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment to the Vogtle Electric Generating Plant, Unit 1 (the facility) Facility Operating License No. NPF-68 filed by Southern Nuclear Operating Company, Inc. (Southern Nuclear), acting for itself, Georgia Power Company, Oglethorpe Power Corporation, Municipal Electric Authority of Georgia, and City of Dalton, Georgia (the licensees), dated June 13,1997, as supplemented by letter dated July 18,1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter 1:

B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assuratice (l) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements h9ve been satisfied, 9709020356 970826 PDR ADOCK 05000424 P

PDR

2-2.

Accordingly, the license is hereby amended by page changes to the Technical Speelfications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-68 is hereby amended to read

)

as follows:

Technical Soecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 98, and the Environmental Protection Plan contained in l

Appendix B, both of which are attached hereto, are hereby incorporated into l

this license. Southem Nuclear shall operate the facility in accordance with the l

Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of its date of issuance and shall be implemented prior to or after initial entry into Mode 3 (in accordance with the provisions of the note to the Applicability for LCO 3.4.10) following the fall 1997 refueling outage.

FOR THE NUCLEAR REGULATORY COMMISSION r

i

\\

97 He ert N. Berkow, Director Project Directorate 112 Division of Reactor Projects l/Il Office of Nuclear Reactor Regulation

Attachment:

Technical Specification Changes Date of Issuance:

August 26, 1997

g88800 j

O 3*

c UNITED STATES

)

NUCLEAR REGULATORY COMMISSION

  • s.,

j$

WASHINGTON, D.C. 30MH001 SOUTHERN NUCLEAR OPERATING COMPANY. INC.

GEORGIA POWER COMPANY 1

QGLETHORPE POWER CORPORATION MUNICIPAL ELECTRIC AUTHORITY OF GEORGIA CITY OF DALTON GEORGIA VOGTLE ELECTRIC GENERATING PLANT. UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 76 License No. NPF-81 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment to the Vogtle Electric Generating Plant, Unit 2 (the facility) Facility Operating License No. NPF 81 filed by Southern Nuclear Operating Company, Inc. (Southern Nuclear), acting for itself, Georgia Power Company, Oglethorpe Power Corporation, Municipal Electric Authority of Georgia, and City of Dalton, Georgia (the licensees), dated June 13,1997, as supplemented by letter dated July 18,1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the common defense and securi;y or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2-2.

Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF 81 is hereby amended to read as follows:

)

i Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 76. and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto, are hereby incorporated into this license. Southern Nuclear shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is eff.,ctive as of its date of issuance and shall be implemented prior to or after initial entry into Mode 3 (in accordance with the provisions of the note to the Applicability for LCO 3.4.10) following the spring 1998 refueling outage, l

FOR THE NUCLEAR REGULATORY COMMISSION 4-Mg Herbert N. Berkow, Director y Project Directorate ll 2 Division of Reactor Projects 1/ll Office of Nuclear Reactor Regulation

Attachment:

Technical Specification Change Date of lasuance: August 26, 1997

=

W

0 l

I ATTACHMENT TO LICENSE AMENDMENT NO. 98 FACILITY OPERATING LICENSE NO. NPF 68

)

D SCKET NO. 50-424 4

88Q TO LICENSE AMENDMENT NO. 7$

FACILITY OPERATING LICENSE NO. NPF-81_

DOCKET NO. 50 425 Replace the following page of the Appendix "A" T schnical Specifications with the enclosed page.

The revised page is identified by Amendment "smber and contains a vertical line indicating the area of change.

Remove g

3.4 20 3.4 20

Pressurizer Safety Valves 3.4.10 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.10 Pressurizer Safety Valves LCO 3.4.10 Three pressurizer safety valves shall be OPERABLE with lift settings h 2410 psig and s 2510 psig.

1 APPLICABILITY:

MODES 1, 2, and 3.

i


NOTE-----------------------------

The lift settings are not required to be within the LCO limits during MODE 3 for the purpose of setting the pressurizer safety valves under ambient (hot conditions.

This exception is allowed for 54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> follow)ing entry into MODE 3 provided a preliminary cold setting was made prior to heatup.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One pressurizer safety A.1 Restore valve to 15 minutes valve inoperable.

OPERABLE status.

B.

Required Action and 8.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met,

&MQ QB B.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Two or more pressurizer safety valves inoperable.

Vogtle Units 1 and 2 3.4-20 Amendment No. 98 (Unit 1)