_. One Fwst Nabonal Plaza Chcago, Illinois Address Reply to: Poel Omco Box 767 Chcago, Illinois 60000 - 0767 September 8, 1986 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, DC 20555
SUBJECT:
Braidwood Station UNIT 1 Commonwealth Edison Request Pursuant to 10 CFR 50.57 (c)
NRC DOCKET NO. 50-456
REFERENCES:
A.
August 18, 1986 Peter Thornton letter to ASLB providing motion for authorization of fuel loading and precritical testing B.
.D.
L. Farrar letter to H. R. Denton dated September 5, 1986
Dear Mr..Denton:
On September 5, 1986, Mr. M. Wallace and others of Commonwealth Edison. met with Messrs. R.
Loebel and B. Mann of your staff to discuss plans for special valve alignment and control during modes 6, 5,
4 and 3, while operating under the provisions described in our motion pursuant to 10 CFR 50.57 (c).
(Reference A)
Reference B was submitted following those discussions and provided the following attachments:
A.
Valves Isolating Direct Unborated Water Sources to Reactor Coolant System B.
Valves Isolating Other Unborated Water Sources On September 8, 1986, Messrs.
R.
Loebel and B. Mann of your staff contacted Mr. C.
Schroeder of Commonwealth Edison.
Following an evaluation of our construction status, we have determined that Commonwealth Edison can arrange its construction priorities to assure timely completion of both the OA and the OB Recycle Holdup Tanks (HUT).
This commitment responds to the question raised by your staif.
Attached please find revised valve lists to reflect this arrangement.
Should you have any questions concerning this matter, please contact this office.
0\\
8610070028 860908 PDR ADOCK 0500 6
g09q
^
F e '-
% One signed original and fifteen copies of this letter and the attachments are provided for your review.
Very tr ly yours, D. L. Farrar Director of Nuclear Licensing DLF/CWS/ jab Attachments cc: Braidwood NRC Resident Inspector Braidwood Project Director (RIII) - W.S. Little L. Olshan 2078K
r ATTACHMENT A VALVES ISOLATING DTRECT UNBORATED WATER SOURCES TO RCS Valve EPN P&ID/ Location Type Status ICVillB M64-4 B4 Air Operated Always Locked Closed ICV 8439 M64-4 C4 Manual Always Locked Closed ICV 8453 M64-4 D2 Manual Always Locked Closed ICV 8441 M64-4 B1 Manual Always Locked Closed OAB010 M65-5A D3 Manual Always Locked Closed ICV 8523A M64-6 C6 Manual Locked Closed Except When Sluicing Demineralizer Resin 1CV8515 M64-6 B5 Manual Locked Closed Except When Sluicing Demineralizer Resin 1CV8523B M64-6 C3 Manual Locked Closed Except When Sluicing Demineralizer Rosin 1CV8428 M64-4 D5 Manual Always Locked Closed
gr s-6 ATTACHMENT B VALVES ISOLATING OTHER UNBORATED WATER SOURCES I.
INDIRECT SOURCES OF UNBORATED WATER TO REACTOR COOLANT SYSTEM Valve EPN P&ID/ Location Type Status
'lSI8936 M61-1B E7 Manual Always Locked Closed ISI8931 M61-1B D7 Manual Locked Closed When RWST is Making-Up to RCS 1CV8434 M64-4 D4
~ Manual Locked Closed When RWST is Making Up to RCS OAB8494 M65-5A F3 Manual Locked Closed When Boric Acid Bat'ch Tank is Discharging 2AB8629B M65-1B A3 Manual Always Locked Closed 0AB009B M65-2A E6 Manual Always Locked Closed 0AB8557B M65-2A E4 Manual Always Locked Closed l
OAB023B M65-2A E3 Manual Always Locked Closed OAB8563A M65-2B D4 Manual Always Locked Closed 2AB023 M65-2C C8 Manual Always Locked Closed 2AB8551 M65-2C D8 Manual Always Locked Closed
- 2CV8553 M65-2C D7 Manual Always Locked Closed 2AB022 M65-2C C7 Manual Always Locked Closed 2PS142 M140-5 E8 Manual Always Locked Closed 1AB8629A M65-1B A3 Manual Locked Closed Exceot During OB HUT Makeup to RCS 1CV8553 M65-2C D7 Manual Locked Closed During OB HUT Makeup to RCS 1AB8551 M65-2C D7 Manual Locked Closed During OB HUT Makeup to RCS
p-l ATTACHMENT B (Cont.)
II.
OTHER CONSERVATIVE ACTIONS Valve EPN P&ID/ Location Type Status 1BR7053 M64-6 B8 Manual Always Locked Closed 1BR7054 M64-6 B7 Air Operated Always Locked Closed 2AB8468 M65-5A B6 Manual Always Locked Closed 2AB8465 M65-5A B4 Manual Always Locked Closed 1RH004C M62 F5 Manual Locked Closed Except When Shell Side Vent is Locked Closed 1RH004D M62 C6 Manual Locked Closed Except When Shell Side Vent is Locked Closed 1CV008A M64-4 B8 Manual Locked Closed Except When Shell Side Vent is Locked Closed 1CV032A M64-5 B2 Manual Locked Closed Except When Shell Side Vent is Locked closed ICV 032B M64-5 D2 Manual Locked Closed Except When Shell Side Vent is Locked Closed ICV 8527A M64-6 B6 Manual Locked Closed Except When Sluicing Domineralizer Rosin 1CV8521 M64-6 AS Manual Locked Closed Except When Sluicing Demineralizer Resin 1CV8527B M64-6 B4 Manual Locked Closed Except When Sluicing Demineralizer Rosin OAB8618A M65-3 E3 Manual Always, Locked. Closed OAB8618B M65-6 E3 Manual Always Locked Closed