Rev 1 to 22S-B-11X-0068, Determination of Heat Load Assemblies F50D & Z33A
ML20210C262
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 07/13/1999
From: Launi C
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20210C260 List:
References
22S-B-110X-0068, 22S-B-110X-0068-R01, NUDOCS 9907260011
Download: ML20210C262 (5)


Text

-

W Enclosure Calculation Number 22S-B-110X-0068 Replacement Pages l

I l

l 9907260011 990719 PDR ADOCK 05000295 P

PDR

1 CALCULATION TITLE PAGE Calculation No.:

22S-B-110X-0068 DESCRIPTION CODE: N00 DISCIPLINE CODE:

N ZION NUCLEAR STATION SYSTEM CODE:

SF TITLE:

Determination of the Heat Load for Assemblies F50D and Z33A Safety Related Augmented Quality C

tien-Srfiiv Related REFERENCE NUMBERS Type Number Type Number PROG ORIGEN2.1 AEDV NPNT&R PROJ l0436-003 COMPONENT EPN:

DOCUMENT NUMBERS:

EPN Compt Type Doc Type /Sub Type Document Number REMARKS:

REV.

REVISING APPROVED DATE NO.

ORGANIZATION PRINT / SIGN 0

S&L W.J. Johnson / (Signature on Rev. 0) 6/14/99 C.M. Launi / ([ ///yj;37

'73/7 1

S&L i

k l

l l

l

i i

CALCULATION NO. 22S-B-110X-0068 PAGE NO.: 2 REVISION SUMMARIES REV: 0 REV1SION

SUMMARY

OriginalIssue. Affected Pages: 1 to 12, A1 to A7, Bl to B1, and Cl to C5 ELECTRONIC CALCULATION DATA FILES:

(Program Name, Version, File name ext / size /date/ hour /: min)

ORIGEN2.1 F50D.OUT / 653949 / 6/4/99 /16 / :47, ORIGEN2.1 Z33A.OUT / 629783 / 6/4/99 /16 / :48 Prepared by:

D.L. Marsh / (Signature on Rev. 0)

Print / Sign Date Reviewed by:

A.G. Klazura / (Signature on Rev. 0)

Print / Sign Date Type of Review 5

Detailed Alternate Test Supplemental Review Required

[] YES (NEP-12-05 documentation attached) x NO Supervisor (Signature on Rev. 0)

DO ANY ASSUMPTIONS IN THIS CALCULATION REQUIRE LATER VERIFICATION O YES

@ NO Tracked by:

REV: 1 REVISION

SUMMARY

Correct Typographical Errors. Affected Pages: 9 and 12 ELECTRONIC CALCULATION DATA FILES:

(Program Name, Version, File name ext / size /date/ hour /: min)

ORIGEN2.1 F50D.OUT / 653949 / 6/4/99 /16 / :47, ORIGEN2.1 Z33A.OUT / 629783 / 6/4/99 /16 / :48 Prepared by:

D. L. Marsh /

/

7/I3/99 Print / Sign

}

Date

/h 7//3/06 i

Reviewed by:

W. J. Johnson /

Print /Sig?F ~//

Da'te Type of Review Detailed Alternate Test J

Supplemental Review Required YES (NEP-12-05 documentation attached) x NO I

Supervisor 2kh-bm 7-/3 #f l

vu AN r A33vmruvad IN t rud tattuta uun nequint taien verai-ita nuw U i es

@ NO 1

l Tracked by:

The reviewer's signature mdicates comphance with S&L procedurc SOP-0402 and the ventication of, as a mmamum, the followmg items. correctness of math for manually prepared calculations. appropriateness ofinput data. appropriateness of assumptions, and appropriateness of the calculation method.

j 1

l l

l

COMMONWEALTH EDISON COMPANY

~

CALCULATION NO. 22S-B-110X-0068 PROJECT NO. 10436-003 PAGE NO. 9 D.P., = 12/31/99 - 02/28/97 = 1036 days 6-13 D.P., = 04/30/00 - 02/28/97 = 1157 days 6-14 l

The ORIGEN2.1 output units are Watts /MTU. The conversion factors which are applied t the i

output of ORIGEN2.1 to convert the units from Watts /MTU to Btu /Hr./ Assembly are as follows:

)

1 Watt = 1 J/s (Reference 5.4, Pg.1-33) 1 J = 9.47817E-04 Btu (Reference 5.4, Pg.1-34) 3600 second = 1 Hour 0.460 MTU/ Assembly for F50D 0.462 MTU/ Assembly for Z33A As an example, for fuel assembly F50D on 02/28/97, the total heat load (sum of Actinides and l

Daughters and Fission Products) from the output of ORIGEN2.1 is 8.230E+04 Watts /MTU. This is converted to Btu /hr/ Assembly in Equation 6.1-15.

8.230E + 04 Watts,1(J/sec.), 9.47817E - 04 Btu,3600sec.,0.460 MTU =1.292E + 05 Btu /hr/ Ass.

MTU 1 Watt 1J l hr.

Assembly REVISION NO.

I

COMMONWEALTH EDISON COMPANY l

CALCULATION NO. 22S-B-110X-0068 PROJECT NO. 10436-003 PAGE NO. 12 FINAL Table 6. Heat Load for Fuel Assembly F50D Decay' Dates Actinides and Daughters, Fission Products, Total, Watts

Total, Watts per MTU Watts per MTU per MTU Btu /hr./Assm.

t 02/28/97 1.083E+04 7.147E+04 8.230E+04 1.292E+05 12/31/97 1.632E+03 -

1.101E+04 1.264E+04 1.984E+04 12/31/98 8.302E+02 5.989E+03 6.819E+03 1.070E+04 04/30/99 7.429E+02 5.ll3E+03 5.856E+03 9.191E+03 06/30/99 7.126E+02 4.742E+03 5.455E+03 8.561E+03 09/30/99 6.792E+02 4.257E+03 4.936E+03 7.748E+03 11/30/99 6.631E+02 3.979E+03 4.642E+03 7.286E+03 12/31/99 6.562E+02 3.849E+03 4.505E+03 7.071E+03 04/30/00 6.363E+02 3.405E+03 4.041E+03 6.343E+03 Table 7. Heat Load for Fuel Assembly Z33A Decay Dates Actinides and Daughters, Fission Products, Total, Watts

Total, Watts per MTU Watts per MTU per MTU Btu /hr/Assm.

l 02/28/97 3.182E+03 1.793E+04 2.111E+04 3.328E+04 12/31/97 1.354E+03 8.357E+03 9.711E+03 1.531E+04 12/31/98 8.097E+02 4.969E+03 5.779E+03 9.110E+03 04/30/99 7.498E+02 4.310E+03 5.060E+03 7.976E+03 06/30/99 7.289E+02 4.027E+03 4.756E+03 7.497E+03 09/30/99 7.056E+02 3.656E+03 4.362E+03 6.876E+03 11/30/99 6.942E+02 3.441 E+03 4.135E+03 6.519E+03 12/31/99 6.893E+02 3.341 E+03 4.030E+03 6.353E+03 l

04/30/00 6.749E+02 2.996E+03 3.671E+03 5.787E+03 l

l REVISION NO.

1 L