r o

Appendix NOTICE OF VIOLATION Union Electric Company Docket No. 50-483 As a result of the inspection conducted on May 28-31 and June 14, 1985, and in accordance with the General Policy and Procedures for NRC Enforcement Actions, (10 CFR Part 2, Appendix C), the following violation was identified:

10 CFR 50, Appendix B, Criterion V requires that activities affecting quality be prescribed by instructions, procedures, or drawings of a type appropriate to the circumstances.

Contrary to the above, Residual Heat Removal (RHR) Operations Surveillance Procedure OSP-EJ-P001A, RU, "Section XI RHR Training "A" Operability" prescribed testing that resulted in degradation of both RHR subsystems beyond that allowed by Technical Specification 3.5.2.

This is a Severity Level IV violation (Supplement 1).

The inspection showed that action had been taken to correct the identified violation and to prevent recurrence.

Consequently, no reply to this notice of violation is required and we have no further questions regarding this matter.

,,h a J'h%'e Dated

/ Juis A. Reyes',/ Chief

};/OperationsBranch 8507120361 850708 PDR ADOCK 05000483 G