r~

ENCLOSURE 2 NOTICE OF DEVIATION Georgia Power Company Docket No. 50-424 Vogtle License No. CPPR-108 The following deviation was identified during a Nuclear Regulatory Comission (NRC) inspection conducted on January 12-16, 1987.

Vogtle Electric Generating Plant (VEGP) FSAR paragraph 8.3.2.1.1 states that the capacity rating of the safety-related batteries are as follows:

A&B: 1947 Ah at 3-h rate C: 1983 Ah at 3-h rate D: 650 Ah at 3-h rate Contrary to the above, the capacity rating of the safety-related batteries that are installed are as follows:

A&B: 1674 Ah at 3-h rate C: 911 Ah at 3-h rate D: 590 Ah at 3-h rate Please provide in writing within 30 days of the date of this Notice a description of corrective actions regarding this deviation, actions taken to avoid further deviations, and the dates when these actions were or will be completed.

,9-FOR THE NUCLEAR REGULATORY COMMISSION OM

.f h

Virgil L. Brownlee, Chief Reactor Projects Branch 2 Division of Reactor Projects Dated at Atlanta, Georgia thisp4ayofg 19@

8703230539 870220 PDR ADOCK 05000424 G

PDR l-