Notice of Deviation from Insp on 861208-19
ML20207S365
Person / Time
Site: Peach Bottom 
Issue date: 03/11/1987
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20207S351 List:
References
50-277-86-25, NUDOCS 8703190316
Download: ML20207S365 (1)


Text

-.

s APPENDIX B NOTICE OF DEVIATION Philadelphia Electric Company Docket No.

50-277/50-278 Peach Bottom Atomic Power Station License No. DPR-44 Unit 2 & 3 As a result of an -inspection conducted on December 8-19, 1986, the following deviation from the licensee Final Safety Analysis Report (FSAR) commitment was identified.

FSAR Section 8.7.4.2 states, " Low battery voltage is annunciated in the main control room".

FSAR Section 8.7.5 states, "The system is tested and inspected as required during the life of the plant to demonstrate its capability to provide power to the safety related loads".

Contrary to the above, as of December 17, 1986, the low voltage battery annunciation generated from the DC undervoltage relays, which is required to confirm capability of the DC Buses to provide power to the safety related loads, was not tested or inspected.

This is a deviation applicable to Units 2 & 3.

Philadelphia Electric Company is hereby requested

+.o submit to this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in reply, including:

(1) the reason for the deviation, (2) the corrective steps which have been taken and the results achieved; (3) corrective steps which will be taken to avoid further deviations; and (4) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending this response time, i

t 0FFICIAL RECORD COPY IR PB2 86 0001.2.0 11/29/80 0703190316 870311 PDR ADOCK 05000277 C