Forwards Drawings Showing Modified Penetration Will Reuse Existing Isolation Valves NI-267A & NI-264B,redesigned as WL-1302A & WL-1301B,respectively,for 860514 Proposed Tech Specs Re Containment Isolation Valves
ML20207S006
Person / Time
Site: McGuire, Mcguire  
Issue date: 03/12/1987
From: Tucker H
DUKE POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 8703180413
Download: ML20207S006 (4)


Text

!1 n

.i Dmm POWER COMPANY P.O. box 33189 CHARIMrrE, N.C. S8949

%s;.

gg S a

-March 12, 1987 U.S.' Nuclear Regulatory Commission tDocument: Control' Desk Washington, D.C.

20555

Subject:

McGuire Nuclear Station, Units 1 and 2 Docket Nos. 50-369 and 50-370 Gentlemen By letter dated May 14, 1986, Duke Power. proposed changes to the McGuire Nuclear Station Technical Specifications for Containment Isolation Valves. The proposal, in part, sought to change the designation of penetration M348 from the " Upper Head Injection Test Line" to " PALS Discharge" upon physical deletion of the Upper Head Injection (UHI) system. ' Subsequent discussions between our respective staffs have

~

determined that Duke needs.co document conformance of the modification with

.GDC 56. As shown on the attached drawing, the modified penetration will reuse the

-existing isolation valves, NI-267A and NI-264B, redesignated as WL-1302A and WL-1301B, respectively. This arrangement, with these valves receiving a Phase "A" Containment Isolation Signal (as indicated in the May 14, 1986 submittal) satis-fies GDC 56, (part 4) as the penetration will have one automatic isolation valve inside containment and one automatic valve outside containment. Additionally, an error has been identified in the original submittal for the insert to page 3/4 6-29 (proposed B 3/4 6-4L).

In the original submittal, valves WL-1301B and WL-1302A were both designated as " PALS DISCHARGE OUTSIDE CONTAINMENT ISOLATION",

as is correct for valve WL-1301B; Valve WL-1302A should be designated " PALS DISCHARGE INSIDE CONTAINMENT ISOLATION"; a revised insert page is attached. We regret any problems this may have caused.

If any additional information is needed, please contact us through normal licen-cing channels.

Very truly yours, h l' lhY Hal B. Tucker JBD/180/jgm

\\

O go 8703180413 870312 PDR ADOCK 05000369 PDR

I:%

Document Control Desk March 12, 1987

~Page 2 xc:

Dr. J. Nelson Grace Regional Administrator, Region II U.S. Nuclear Regulatory Commission 101 Marietta St. NW, Suite 2900 Atlanta, Georgia 30323 Mr. Darl Hood U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Washington, D.C.

20555-Mr. W.T. Orders NRC Resident Inspector McGuire Nuclear Station

L, A trachrnent 6'C.VTAIAMEN T 3

FLact (fCa rf sump NIS36 CV - RB - A B e

A e

el V-m M

J m2G7A NI2G4 8 M-las CV -RB - AB i

m2r.5

  1. I2"^

hoer rot io n v

CV -RB - AB r7 e

m

)

LJ f+,

cv -n3 WLl?O'#

WLI302A q

y

-,B WL /307 Pro po sed penexration

! re

. g.

WL1301Bff PALS DISCHARGE OUTSIDE CONTAINMENT ISOLATION f 15 WL1302Aff PALS DISCHARGE INSIDE CONTAINMENT ISOLATION