Proposed Tech Spec Changes Bringing Ranges of Drywell Temp Indicators & Recorders Into Conformity W/Requirements of Reg Guide 1.97
ML20207P531
Person / Time
Site: Peach Bottom  
Issue date: 10/17/1986
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20207P442 List:
References
RTR-REGGD-01.097, RTR-REGGD-1.097 NUDOCS 8701160221
Download: ML20207P531 (4)


Text

.. - - - _ _.. - - _.

TABLE 3.2.F SURVEILLANCE INSTOUMENTATION

U D(D Mtnimum No.

t3 %4 of Operable Type 30 C)

Instrument Indication Item Channels Parameter Instrument and Ran9e Action

  • ma 35 0-t30 hkh$.

1 2

Reactor Water Level LR-2(3)-6-96 Recorder 0-60" (1) (2)(3) yt >

(narrow ran9e)

LI-2(3)-6-94A. B. C Indicator 0-60" 0 03 2

2 Reactor Water Level LR-2(3)-2-3-110A. 8 Recorder -165" to +50" (10) (11)

$ 0' (wide range)

(Green Pen) glhp 3

2 Reactor Water Level LR-2(3)-2-3-110A, B Recorder -325" to 0*

(10) (11)

C3 k3 4 (fuel zone)

(Red Pen)

04

'4 4

2 Reactor Pressure PR-2(3)-6-96 Recorder 0-1500 psto (1) (2) (3)

+

PR-2(3)-2-3-404A. 8 Indicator 0-1203 psig q

PI-2(3)-6-90A.

B.

C 5

2 Drywe11 Pressure PR-4(5)S05 (Pen 2)

Recorder 0-70 psig (1) (2) (3)

PR-2(3)S08 (Pen 2) 1 6

2 Drywell Pressure PR-8(9)102A, 8 Recorder 0-225 psig (8) (9)

(wide range)

(Red Pen) 7 2

Drywell Pressure PR-8(9)102A, 8 Recorder 5-25 psia (8) (9)

[j (substmospheric range)

(Green Pen) i 8

2 Drywell Temperature TR-4(5)S05 (Pen 1)

Recorder 40-440 degrees F (1) (2) (3)

TI-2(3)501 Indicator 40-440 degrees F (1) (2) (3) (12) 9 2

Suppression Chamber Water TR-8(9)123A. 8 Recorder 30-230 degrees F (1) (2) (3) (6)

Temperature TIS-2(3)-2-71A. 8 Indicator 30-230 degrees F 10 2

Suppression Chamber Water LR-8(9)D27 Recorder 13.7-15.7 ft.

(1) (2) (3)

Level (narrow range)

LI-8(9)D27 Indicator 13.7-15.7 ft.

4 h

1 x >

. wm n

IDV J

TABLE 3.2:F (Cont'd) - SURVEILLANCE INSTRUMENTATION Minimum No.

of Operable Type Instrument Indication Item Channels Parameter Instrument and Range Action

  • l l

l 11 2

Suppression Chamber LR-8(9)123A. B Recorder 1-21 ft.

(10) (11)

Water Level (wide range) 12 1

Control Rod Position N/A 28 Volt Indicating

)

Lights

)

(1) (2) (3) (4)

)

13 1

Neutron Monitoring N/A SRM. IRM. LPRMe

)

0-10D%

)

14 1

Safety-Reitef Valve POAM-2(3)-2-71A-L Acoustic or (5)

Posttten Indication TE-2(3)-2-113A-L Thermocouple 15 2

Drywell High RR-8(9)103A. B Recorder (7) 8 Range Radiation 1-1E(+B) R/hr Monttors l

16 1

Main Stack High Range RR-7127 (Green Pen)

Recorder l

Radiation Monitor 1.4E(-2) to 1.4E(+4)uct/cc (7) l 17 1

Reactor Building Roof RR-7127 (Red Pen U/2)

Recorder i

Vent High Range Radiation RR-7127 (Blue Pen U/3) 1.4E(-2) to 1.4E(+4)uct/cc (7)

[j Monitor m

.I 18 2

Drywell Hydrogen 2(3)BS215, 2(3)CS215 Analyzer and Recorder (1) (2) (3)

Concentration Analyzer H2R-4(5)9658, C 0-20% volume l

and Monitor

  • Notes for Table 3.2.F appear on pages 78 and 78a.

s e

CM m

e.

w

'* ~

PBAPS NOTES'FOR TABLE 3.2.F (Cont'd) 9)

If no channels are operable, continued operation is permissible during the succeeding 7 days, provided both

. Drywell Pressure : instruments (0-70 psig) are operable; otherwise, restore the inoperable channel (s) to operable g

statue within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least Hot Chutdown within i

the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

e 10)

With the number of operable channels less than the minimum number of instrumentation channels shown'in Table 3.2.F, l

continued operation is permissible during the succeeding 30 days, provided both narrow range instruments monitoring the i

same variable are operable; othc.rwise, restore the inoperable channel to operable status within 7 days or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, 11)

If no channels are operable, continued operation is permissible during the succeeding seven days, provided both narrow range instruments monitoring the same variable are s

operable; otherwise, restore the inoperable channel (s) to operable status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least Hot 4

Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

12)

The instrument range may be greater than the range listed in Table 3.2.F provided that (1) the range includes the upper and lower-range limits specified in Table 3.2.F, and (2) the range does not exceed three times the range specified in Table 3.2.F.

q l

-78a-

~

l' s

CERTIFICATE OF SERVICE I certify that service of the foregoing Application was made upon the Commonwealth of Pennsylvania, by mailing a copy thereof, via first-class mail, to Thomas R. Gerusky, Director, Bureau of Radiological Protection, P. O. Box 2063, Harrisburg, PA 17120; all this 24th day of October,1986.