Amend 101 to License DPR-3,changing Tech Specs to Increase Time Period That Valve CS-MOV-532 May Be Open from 30 Minutes/Wk to 120 Minutes/Wk
ML20207N416
Person / Time
Site: Yankee Rowe
(DPR-03-A-101, DPR-3-A-101)
Issue date: 01/06/1987
From: Mckenna E
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20207N402 List:
References
NUDOCS 8701140201
Download: ML20207N416 (4)


Text

~

p ( trg'o UNITED STATES 4

g 8"

NUCLEAR REGULATORY COMMISSION n

h WASHINGTON, D. C. 20555

%...../

YANKEE ATOMIC ELECTRIC COMPANY

~

YANKEE NUCLEAR POWER STATION DOCKET NO.50-029 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.101 License No. DPR-3 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The applicatic, for amendment by Yankee Atomic Electric Company (the licensee) dated October 22, 1986 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I;

~

B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasor:able assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

j 2.

Accordingly, the license is amended by changes to the Technical l

Specifications as indicated in the attachment to this license amendment and Paragraph 2.C.(2) of Facility Operating License No. DPR-3 is hereby amended to read as follows:

l PDk 1

. (2)

Technical Specifications The Technical Specifications contained in Appendix A as revised through Amendment No.101, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION N MC M4vw A

Eileen M. McKenna, Project Manager Project Directorate #1 Division of PWR Licensing-A

Attachment:

Changes to the Technical Specifications

'Date of Issuance: January 6, 1987 9

ATTACHMENT TO LICENSE AMENDMENT NO.101 FACILITY OPERATING LICENSE NO. DPR-3 DOCKET NO.50-029 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by i

the captioned amendment number and contain marginal lines indicating the area of change.

REMOVE INSERT 3/4 5-6 3/4 5-6 9

i f

f l

DfERGENCY CORE COOLING SYSTD4S SURVEILLANCE REQUIREMENTS (Continued) 3 VerifyingthatthefollowingvalvesareintheirnormalIyclosed position with power to the valve operator removed by disconnecting the power cables as they leave the motor starter:

Valve Number Valve Function b.

CS-MCV-534 LPSI Pump Header Isolation Valve Bypass 4.

Verifying that the following valves are in their normal position with power to the valve operator motors separated by dual contactors from the motor control center:

Normal Valve Number Valve Function Position

a. CS-MOV-532 LPSI Recirculation Line Closed
b. CS-MOV-533 LPSI Pump Header Isolation Open
c. CS-MOV-535 LPSI Pump Header Isolation Open
d. SI-MOV-518 HPSI and LPSI Pump Header Suction Isolation Open
e. SI-MOV-48 HPSI and LPSI Minimum Recirculation Line Open
f. SI-MOV-49 HPSI and LPSI Minimum Recirculation Line Open
g. SI-MOV-515 Hot Leg Injection Isolation Closed
h. SI-MOV-514 Hot Leg-Injection Isolation Closed
1. SI-MOV-516 V.C. Sump Isolation closed
j. SI-MOV-517 V.C. Sump Isolation Closed
k. SI-MOV-46 HPSI Flow Control Open

. 1. SI-MOV-4 LPSI Pump Crossover to HPSI Pump Open

m. CS-MOV-536 SI Header Isolation to Cold Leg Open
n. CS-MOV-537 SI Header Isolation to Cold Leg Open
o. CS-MOV-538 SI Header Isolation to Cold Leg Open
p. CS-MOV-539 SI Header Isolation to Cold Leg Open
q. MC-MOV-301 MCS Loop Isolation Open l
r. MC-MOV-302*

MCS Loop Isolation Open l

s. MC-MOV-309 MCS Loop Isolation Open
t. MC-MOV-310*

MCS Loop Isolation Open

u. MC-MOV-318*

MCS Loop Isolation Open l

v. MC-MOV-319 MCS Loop Isolation Open
w. MC-MOV-325 MCS Loop Isolation Open t
x. MC-MOV-326*

MCS Loop Isolation Open l

l Note: CS-MOV-532uaybeopenedfor$$120minutesperweekfor l

safety injection tank mixing or low pressure safety injection pump testing.

  • In Modes 2, 3*, 4*,

5*, MCS loop isolation valves are required to be closed for main coolant pump (s) starting. After the pump (s) has been started, the valve (s) shall be reopened.

l YANKEE ROWE 3/4 5-6 AmendmentNo,pp,

, 101

-