Concurs W/Util 880712 Submittal of Detailed Data Re Class 1E Breakers,In Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Submittals of Such Addl Data for Unit 2 Will Not Be Necessary
ML20207J240
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 08/25/1988
From: Reeves E
Office of Nuclear Reactor Regulation
To: Hairston W
ALABAMA POWER CO.
References
IEB-88-001, IEB-88-1, TAC-67665, NUDOCS 8808300323
Download: ML20207J240 (2)


Text

.

August 25, 1988 Docket No. 50-348 DISTRIBUTION

Oschst1Hler.

C Adensam

'NRC POR ~~'

P. Anderson Mr. W. G. Hairston, Ill Local POR OGC Senior Vice President PDII.1 reading E. Jordan (MNBB 3302)

Alabama Power Company S. Varga (14E4)

8. Grimes (9A2)

Post Office Box 2641 G. Lainas ACRS(10)

Birtaingham, Alabama 35291 0400 D. Hood (14D13) l

0. Sellers (

)

Dear Mr. Hairston:

s AmerS

SUBJECT:

NRC BULLETIN 88-01. DEFECTS IN WESTINGHOUSE CIRCU!T BREAKERS (MPA B-100)

JOSEPH M. FARLEY NUCLEAR PLANT, UNIT 1 (TAC NO. 67665)

NRC Bulletin 88 01, dated February 5,1988, requested holders of operating licenses or construction permits to provide letters of confirmation to the NRC of the completion of specified inspections on Westinghouse series 05 circuit breakers.

Addressees not having series 05 circuit breakers in Class 1E service were requested to provide a letter to the NRC stating this fact.

By [[letter::05000364/LER-1988-004-01, :on 880315,fire Watch Patrol Not Established as Required.Shift Foreman Failed to Recognize Penetration Released to Be Breached as Fire Barrier Penetration.Caused by Personnel Error.Shift Foreman Counseled|letter dated April 14, 1988]], you advised that the short and long-term inspections of such reactor trips and bypass breakers were completed on March 8,1988 for Units 1 and 2.

Also, by letter dated June 9,1988, you advised that inspections were completed of all other Class IE breakers in Unit 1.

Sixty.seven breakers (nine 05-416 and 58 05-206) were inspected. Sixty-six breakers had pole shaf ts which failed the Bulletin 88-01 criteria. Due to the extensive repairs being made, the NRC staff requested that you provide detailed data for evaluation. Your letter dated July 12, 1988 provided the requested data.

Submittals of such additional data for Unit 2 will not be necessary.

On the basis of your actions to resolve Bulletin 88-01 (MPA B-100), as described herein, we consider the Unit 1 issue to be completed. We understand that the action for the remaining series OS circuit breakers on Unit 2 will be completed during the next refueling outage scheduled to start March 24, 1989, i

i Sincerely.

Edward A. Reeves, Senior Project Manager Project Directorate 11-1 Division of Reactor Projects 1/11 cc:

See next page M.

OFC :LA 1

lPR:PM:PD 1 FR:D-DRPR :

. g., -

NAME :P.

oY :

E.

ee es:

q:. Adensam DATE :8/.t,Y/88

8/1h88
8/6/88 OFFICIAL RECORD COPY a

A Ih 8808300323 880825 I

PDR ADOCK 05000348

\\D l

0 PDC

1

"/

kr.W.G.Hairston,!!!

Alabama Power Company Joseph M. Farley Nuclear Plant CC' Mr. R. P. - Mcdonald Resident inspector Executive Vice President U.S. Nuclear Regulatory Commission Alabama Power Company Post Office Box 24 - Route 2 Post Office Fox 2641 Columbia, Alabama 36319 Birmingham, Alebama 35291-0400 Mr. Bill M. Guthrie D. Biard MacGuineas.-Esquire Executive Vice President Volpe, Boskey and Lyons Alabama Power Company 918 16th Street, N.W.

Post Office Box 2641 Washington. 0.C.-

20006 Birmingham, Alabama 35291-0400 Mr. Louis B. Long, General Manager Charles R. Lowman Southern Company Services, Inc.

Alabama Electric Corporation Post Office Box 2625 Post Office Box 550 Birmingham, Alabama 35202 Andalusia, Alabama 35420 Chairman Regional Administrator, Region II Hcuston County Commission U.S. Nuclear Regulatory Commission Dothan, Alabama 36301 101 Marietta Street, Suite 2900 Atlanta, Georgia 30323 Ernest L. Blake, Jr., Esquire Shaw, Pittman, Potts and Trowbridge Claude Earl Fox, M.D.

2300 N Street, N.W.

State Health Officer Washington, DC 20037 State Department of Public Health 6

State Office Building Montgomery, Alabama 36130 Robert A. Buettner, Esquire Balch, Bingham. Baker, Hawthorne, Mr. D. N. Morey Williams and Ward General Manager - Farley Nuclear Plant Post Office Box 306 Post Office Box 470 Birmingham, Alabama 35201 Ashford, Alabama 36312 P

A

(

9 l

-