Amend 6 to License NPF-62,revising Tech Spec Section 4.11.2.7.2 Re Radioactivity Rate of Noble Gases from Offgas Recombiner Effluent
ML20207D674
Person / Time
Site: Clinton Constellation icon.png
Issue date: 08/08/1988
From: Muller D
Office of Nuclear Reactor Regulation
To:
Illinois Power Co
Shared Package
ML20207D679 List:
References
NPF-62-A-006 NUDOCS 8808150420
Download: ML20207D674 (4)


Text

..

puta uq'of,

d UNITED STATES 8

NUCLEAR REGULATORY COMMISSION o

(

WASHINGTON. D, C. 20555

%...../

ILLIN0IS POWER COMPANY, ET AL DOCKET NO. 50-461 CLINTON POWER STATION, UNIT N0. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 6 License No. NPF-62 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendmeat by the Illinois Power Company * (IP),

Soyland Power Cooperative, Inc. and Western Illinois Power Cooperative, Inc. (the licensees) dated October 30, 1987 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in confonnity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endargering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-62 is hereby amended to read as follows:

(2) Technical p ecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised

  • Illinois Power Company is authorized to act as agent for Soyland Power Cooperative, Inc. and Western Illinois Power Cooperative, Inc. and has exclusive responsibility and control over the physical construction, operation and maintenance of the facility.

8808150420 880800 PDR ADOCK 05000461 P

PNu

2 through Amendment No. 6, are hereby incorporated into this license.

IP shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION lk.

k'Or Daniel R. Muller, Director

' Project Directorate III-2 Division of Reactor Projects - III, IV, V and Special Projects Atta chir. ant:

Changes to the Technical Specifications Date of Issuance: August 8, 1988 l

l 1

l l

l

ATTACHMENT TO LICrNSE AMENDMENT N0. 6 FACILITY OPERATING LICENSE N0. NPF-62 DOCKET NO. 50-461 Replace the following page of the Appendix "A" Technical Specifications with the attached page. The revised page is identifed by amendnent number and contains vertical lines indicating the area of change.

Remove Insert 3/4 11-17 3/4 11-17

RADI0 ACTIVE EFFLUENTS MAIN CONDENSER LIMIIING CONDITION FOR OPERATION 3.11.2.7 The radioactivity rate of noble gases measured at the offgas recom-biner effluent shall be limited to less than or equal to 289 millicuries /sec after 30 minutes' decay.

APPLICABILITY:

During operation of the main condenser air ejector.

ACTION With the radioactivity rate of noble gases at the offgas recombiner effluent exceeding 289 millicuries per second after 30 minutes deca,', restore the gross radioactivity rate to within its limit within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or se in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.11.2.7.1 The radioactivity rate of noble gases at the offgas recombiner effluent shall be continuously monitored.

4.11.2.7.2 The radioactivity rate of noble gases from the offgas recombiner effluent shall be determined to be within the limits of Specification 3.11.2.7 at the following frequencies

  • by performing an isotopic analysis of a represen-l tative sample of gasas taken at the discharge (prior to dilution and/or dis-charge) of the offgas recombiner:

a.

At least once per 31 days.

b.

Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> following an increase, as indicated by the Pretreatment Off-Gas ?rocess radiation monitor listed in Table 3.3.7.1-1, of greater than 50%, after factoring out increases due to changes in THERMAL POWER level, in the nominal steady state fission gas release from the primary l

conlant.

l l

1 1

  • The provisions of Specification 4.0.4 are not applicable.

l CLINTON - UNIT 1 3/4 11-17 Amendment No. 6

--.