Northern States Power Company Prairie Island Nuclear Generating Plant 1717 Wakonade Dr. East Welan. Minnesota 55089 i
December 9,1998 Technical Specifications 6.7.A.3 US Nuclear Regulatory Commission Attn Document Control Desk Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket Nos. 50-282 License Nos. DPR-42 50-306 DPR-60 Monthly Operating Report November 1998 Attached is the Monthly Operating Report for November 1998 for the Prairie Island Nuclear Generating Plant.
t Joel P. Sorensen
\\
l
. Plant Manager Prairie Island Nuclear Generating Plant
< l'\\\\'
c:
Regional Administrator-Ill, NRC NRR Project Manager, NRC
/$
NRC Resident inspector
/
1 State of Minnesota - Kris Sanda Attachment
~
9a12160077 9ei130 PDR ADOCK 05000282 R
PM k.
NRC MONTHLY REPORT PRINTED 12/?/199 Page1 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO 1 DATE 12/2/1998 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 NARRATIVE
SUMMARY
OF OPERATING EXPERIENCE MONTH: NOVEMBER 1998 For the beginning of November, Unit 1 continued in the forced outage that started on the 29th of October. The cause of the outage was a shorted Control Rod Drive cable. All of the Unit's Control Rod Drive cables were replaced. The Reactor was taken critical on the 18th at 0009. The Generator was placed on-line on the 18th at 2347. The Unit reached full power operation on the 19th at 1638.
The Unit was base loaded.
The trip r.nded a continuous operating run of approximately 133 days.
l l
l l
)
CURRENT CONTINUOUS OPERATING RUN OF 12 DAYS
NRC MONTHLY REPORT PRINTED 12/2/199 Page 2 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO.1 DATE 12/2/1998 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 OPERATING DATA REPORT OPERATING STATUS
- 1. UNIT NAME:
PRAIRIEISLAND NO.1
- 2. REPORTING PERIOD:
NOVEMBER 1998
- 3. LICENSED THERMAL POWER (MWT): 1650 1
~4. NAMEPLATE RATING (GROSS MWE): 593
- 5. DESIGN ELECTRICAL RATING (NET MWE): 543
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):
558
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):
526
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASON:
)
NONE
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NONE
- 10. REASONS FOR RESTRICTIONS,IF ANY:
NONE THIS MONTH Y_R-TO-DATE C_UM.ULATIVE
- 11. HOURS IN REPORTING PERIOD 720 8016 218784
- 12. NUMBER OF HOURS REACTOR CRITICAL 311.8 7266.5 188043.5 i
- 13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.00 5571.1
- 14. HOURS GENERATOR ON-LINE 288.2 7206.2 186194.7
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.00 0.00
- 16. GROSS THERMAL ENERGY GENERATED (MWH) 457650 11732112 296009955
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 159870 4024950 97843660
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 147507 3803389 92037710
- 19. UNIT SERVICE FACTOR 40.0 89.9 85.1
- 20. UNIT AVAILABILITY FACTOR 40.0 89.9 85.1
- 21. UNIT CAPACITY FACTOR ( MDC NET) 38.9 94.6 83.2
- 22. UNIT CAPACITY FACTOR ( DER NET) 38.7 91.6 79.2
- 23. UNIT FORCED OUTAGE RATE 60.0 9.8 4.8
- 24. FORCED OUTAGE HOURS 431.8 786.5 9327.2
NRC MONTHLY REPORT PRINTED 12/2/199 Page 3 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO.1 DATE 12/2/1998 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 A
UNIT SHUTDOWNS AND POWER REDUCTIONS 1
i MONTH: NOVEMBER 1998 DATE UNIT TYPE HOURS REASON METHOD LER NUMBER SYSTEM COMPONENT 11/1/1998 1
F 431.8 A
4 1-98-16 N/A N/A i
NOTES:
Reactor trip of 10/29/98 caused by control rod cable short.
l l
TYPE REASON METHOD SYSTEM CODE F-FORCED A-EQUIPMENT FAILURE 1-MANUAL DRAFT IEEE STD S-SCHEDULED B-MAINTENANCE OR TEST 2-MANUAL TRIP C-REFUELING 3-AUTO TRIP D-REGULATORY RESTRICTION 4-CONTINUED 4
i E-OPERATOR TRAINING AND 5-REDUCED LOAD COMPONENT CODE LICENSE EXAMINATION 9-OTHER IEEE STD 803A-1983 j
F-ADMINISTRATIVE G-OPERATIONAL ERROR H-OTHER
NRC MONTHLY REPORT PRINTED 12/2/199 Page 4 1
DOCKET NO. 50-306 UNIT PRAIRIE ISLAND NO. 2 i
DATE 12/2/1998 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 NARRATIVE
SUMMARY
OF OPERATING EXPERIENCE MONTH: NOVEMBER 1998 4
For the beginning of November, Unit 2 was base loaded operating at full power. On the 8th at 2330., operations began a controlled shutdown of the Unit to start cycle 19 refueling outage. On the 9th at 0048, the Unit was at approximately 22% power when a turbine trip was generated and automatically shut down the Unit.
The cause of the trip is still under investigation, j'
Some of the outage activities are:
Refueling Generator low pressure rotor upgrade Reactur coolant pump work Steam generator eddy current testing and repair Diesel generator D6 five year inspection Reactor vessel inspection CRDM cable rep lacement 4
Routine maintenance of many other components 4
The outage ended a continuous operating run of approximately 250 days 1
J t
CURRENT CONTINUOUS OPERATING RUN OF 0 DAYS
NRC MONTHLY REPORT PRINTE012/2/199 P:ge5 DOCKET NO. 50-306 UNIT PRAIRIE ISLAND NO. 2 DATE 12/2/1998 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 OPERATING DATA REPORT OPERATING STATUS
- 1. UNIT NAME:
PRAIRIEISLAND NO.2
- 2. REPORTING PERIOD:
NOVEMBER 1998
- 3. LICENSEL THERMAL POWER (MWT): 1650
- 4. NAMEPLATE RATING (GROSS MWE):
593
- 5. DESIGN ELECTRICAL RATING (NET MWE): 530
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):
544
' 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):
512
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASON:
NONE
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NONE
- 10. REASONS FOR RESTRICTIONS, IF ANY:
NONE THIS MONTH YR TO-DATE CUMULATIVE
- 11. HOURS IN REPORTING PERIOD 720 8016 209902
- 12. NUMBER OF HOURS REACTOR CRITICAL 192.8 6565.9 185292.1
- 13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 1516.1
- 14. HOURS GENERATOR ON-LINE 192.8 6557.1 183784.2
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
- 16. GROSS THERMAL ENERGY GENERATED (MWH) 317833 10686494 293151081
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 1069A0 3538520 96035930
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 10C176 3339377 90790547
- 19. UNIT SERVICE FACTOR 26.8 81.8 87.6
- 20. UNIT AVAILABILITY FACTOR 26.8 81.8 87.6
- 21. UNIT CAPACITY FACTOR ( MDC NET) 27.4 81.4 86.1
- 22. UNIT CAPACITY FACTOR ( DER NET) 26.5
- i8.6 81.6
- 23. UNIT FORCED OUTAGE RATE 0.0 12.4 3.0
- 24. FORCED OUTAGE HOURS 0.0 931.7 5662.8
I' i.
NRC MONTHLY REPORT PRINTED 12/2/199 Page 6 DOCKET NO. 50-306 UNIT PRAIRIE ISLAND NO. 2 4
DATE 12/2/1998 COMPLETED BY DALE DUGSTAD PHONE 651-388-11214376 2
4-UNIT SHUTDOWNS AND POWER REDUCTIONS 1
MONTH: NOVEMBER 1998 Y
DATE UNIT TYPE HOURS REASON METHOD LER NUMBER SYSTEM COMPONENT 11/9/1998 2
S 527.2 C
3 2-98-005 N/A N/A NOTES: Refueling outage, cycle 19, Turbine trip at - 22% power.
J l
i i-4 TYPE REASON METHOD SYSTEM CODE F-FORCED A-EQUIPMENT FAILURE 1-MANUAL DRAFT lEEE STD S-SCHEDULED B-MAINTENANCE OR TEST 2-MANUAL TRIP C-REFUELING 3-AUTO TRIP D-REGULATORY RESTRICTION 4-CONTINUED E-OPERATOR TRAINING AND 5-REDUCED ' OAD COMPONENT CODE LICENSE EXAMINATION j
9-OTHER IEEE STD 803A-1983 i
F-ADMINISTRATIVE G-OPERATIONAL ERROR H-OTHER