ML20206E445

From kanterella
Jump to navigation Jump to search
Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Insp Rept 50-458/87-02
ML20206E445
Person / Time
Site: River Bend Entergy icon.png
Issue date: 04/06/1987
From: Gagliardo J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Deddens J
GULF STATES UTILITIES CO.
References
NUDOCS 8704130613
Download: ML20206E445 (1)


See also: IR 05000458/1987002

Text

,

_

. /a '

.-

APR 6

1987

In Reply Refer To:

Docket: 50-458/87-02

L

Gulf States Utilities

ATTN: Mr. James C. Deddens

SeniorVicePresident,(RBNG)

Nuclear Licensing

P. O. Box 220

St. Francisville, Louisiana

70775

Ger.tlemen:

Thank you for your letter of March 26, 1987, in response to our letter and

Notice of Violation dated February 24, 1987. We have reviewed your reply and

find it responsive to the concerns raised in our Notice of Violation. We will

review the implementation of- your corrective actions during a future inspection

to detemine that full compliance has been achieved and will be maintained.

Sincerely,

Original Signed By

J. E. Gagliardo

J. E. Gagliardo, Chief

Reactor Projects Branch

cc:

Gulf States Utilities

ATTN:

J. E. Booker, Manager-

River Bend Oversight

P. O. Box 2951

Beaumont, Texas

77704

l

Louisiana State University,

Government Documents Department

Louisiana Rao1ation Control Program Director

l

bectoDMB(IE01)

s704130613 e70406

I

PDR

ADOCK 05000458

PDR

l

bec distrib. by RIV:

o

l

RPB

DRSP

Resident Inspector

R. D. Martin, RA

SectionChief(RPB/A)

D. Weiss, RM/ALF

MIS System

RSB

()g

RSTS Operator

Project Inspector

R. Hall

R&SPB

I

g\\

RIV File

7

f b.

/

A

r

P1 t

C: RPB A

C:RPB

r

"\\{/WR

3ennett:cs

4/b/p7

4/5/,

JP0au on

JEGagl

rdo

t

l

4/d /87

5 -O

e

,

a

c'2E"WI

~

,s

n

GULF STATES

UTILITIES COMPANY

POSToFFICEBox22oe ST FRANCISVILLE.LoulS8ANA70776

AREACoDE 504 635-3237

387 4257

March 26, 1987

RBG- 25561

File Nos. G9.5, G15.4.1

m

MC{D]

pW

.- A 4

Nuclear Regulatory Commission

"

'

A {d

i{p

Document Control Desk

I

b

WAR 311987 f til!)

Washington, D.C. 20555

-

Gentlemen.

g

q

River Bend Stat. ion - Unit 1

..

Refer to: Region IV

Docket No. 50-458/ Report 87-02

This letter responds to the Notice of Violation contained in NRC

Inspection Report No. 50-458/87-02. The inspection was performed by

Messrs.

D.D.

Chamberlain and

W.B.

Jones during the period January 1

through February 15, 1987 of activities authorized by NRC Operating

License NPF-47 for River Bend Station.

Gulf States Utilities Company's (GSU) response to Notice of Violation

8702-01, " Inadequate Procedures for Control of Radioactivity",

is

provided in the enclosed attachment pursuant to 10CFR2.201. This

completes GSU's response to the Notice of Violation.

Sincerely,

-

.. : -

J. C. Deddens

Senior Vice President

River Bend Nuclear Group

,

JCD/

/

ja

fY

Attachment

cc: Mr. Robert D. Martin, Regional Administrator

U.S. Nuclear Regulatory Commission

Region IV

611 Ryan Plaza Drive, Suite 1000

Arlington, TX 76011

,

m1

(

Senior Resident Inspector

h

U.S. Nuclear Regulatory Commission

P. O. Box 1051

i

St. Francisville, LA 70775

I

nu wy

_

_

_

-

..

- - -

- - .

--

. .

.

.

. __

  • um

.

.

.

,

IMPED SDm!lS & AM!RICA

larrTFAR REGOTJL'ITRY CDGESSICE

SDL1E & IOUISIANA

PARISH & WEST FELICIANK

In the Matter of

Dodet Nos. 50-458

GUTE SDGES 17fILITIES (IMPANY

(River Bend Station,

Unit 1)

.

AFFIDAVIT

J. C. Deddens, being duly sworn, states that he is a Senior Vice

President of Gulf States Utilities Campany; that he is authorized on the

part of said Chnpany to sign and file with the Nuclear Regulatory

Ommission the h=nts attached hereto; and that all such h_=nts

are true and correct to the best of his knowledge, information and

belief.

/

J.[Ak' Deddens

Subscribed and sworn to before me, a Notary Public in and for the

StateandandParishabovenamed,thisS

day of bf((fdh ,19

-

J-rtts .

4se

W

/Joan W. Middlebrooks

  • '

Notary Public in and for

West Feliciana Parish,

Ia11siana

My Ccomissian is for Life.

.-

.

...

. . .

. - - _

. _ - _ _ _ _

- - _

.

_ _ - _ _ _ _ - - _ - _ - _ _ _ _ _ . _ __

- -.

r wh

.-

.

,

o

ATTACHMENT

' '

Response To Notice of Violation 50-458/8702-01

LEVEL IV

REFERENCE

Notice of Violation - J. E. Gagliardo letter to

J.

C.

Deddens, dated

February 24, 1987.

INADEQUATE PROCEDURES FOR CONTROL OF RADIOACTIVITY

Technical Specification, paragraph

6.8.1.a.

requires that procedures

shall he established, implemented, and maintained for

activities

recommended in Appendix A of Regulatory Guide 1.33, Revision 2, February

1978. Paragraph 7 of Appendix A to Regulatory Guide 1.33 delineates

procedures for the control of radioactivity.

Contrary to the above, it was found on February 9, 1987, that there were

no procedures in effect directing personnel exiting through portal

radiation monitors as to what should be done if a portal monitor

alarmed.

.

This is a Severity Level IV violation.

REASON FOR VIOLATION

The subject violation was reviewed for determination of the cause.

The

results of the review identified that proper action for portal monitor

alarm was addressed in General Employee Training, but not specifically

addressed

in

the

Radiological Program and Security procedures.

Therefore, the cause was determined to be insufficient information

regarding the portal monitor alarm in the Radiological Program and

Security procedures.

CORRECTIVE STEPS WHICH HAVE BEEN TAKEN AND THE RESULTS ACHIEVED

Radiation Protection has revised RPP-0043, " Personnel Frisking",

to

include the following statement.

!

"When passing thru a Portal Monitor, if the alarm sounds, reset the

monitor and pass thru again.

If second alarm sounds, notify

Radiation Protection.

Personnel alarming Portal Monitors after

resetting must be released by Radiation Protection."

Security has revised SPI-4 " Security Position Instruction" as follows:

1.

If an Officer is on duty in the exit area and the portal

monitor alarms when an individual exits, the individual will be

stopped, instructed to reset the portal monitor and pass

,

j

through again.

If the monitor alarms a second time, Radiation

Protection will be contacted to perform a contamination survey

i

l

!

l

.. --

-- .

-

- -

- - - - . -

-

- -

- . -

- .

-

c__

1% 2

,

,

2.

If an Officer is not on duty in the exit area and the portal

monitor alarms, the Access Control Officer will lock the

  • -

turnstile and the same procedure in paragraph one will be

followed.

A handout was given to personnel exiting the plant and also

personnel at the Main Administration Building personnel exit and

Gate 9.

This memo was also included in the Safety Bulletin.

A printout of personnel exiting at the same time as the Condition

Report (CR)

initiator was obtained and a comparison of Radiation

Work Permit (RWP) entries was accomplished. It was determined that

personnel entering and exiting at approximately the same time as the

CR initiator had not worked in areas of significant radiological

hazards.

An additional alarm has been attached to the portal monitors which

is much louder than the alarms furnished with the instrument. This

should ensure personnel hear the alarm during rush periods.

Implementation and enforcement of

revised

procedures

has

been

accomplished.

CORRECTIVE STEPS WHICH WILL BE TAKEN TO AVOID FURTHER VIOLATIONS

RBNP-024, " Radiation Protection Plan",

will be revised by 5/29/87 to

include the same statement as RPP-0043.

DATE WHEN FULL COMPLIANCE WILL BE ACHIEVED

Full compliance will be achieved as of 5/29/87.

t

,