ML20206B336

From kanterella
Jump to navigation Jump to search
Requests Amend of Safety & Technical Evaluations to Delete Ref to Gas Turbine & Breakers Contained in Room Constructed of Walls,Floor/Ceiling That Are 3 H Fire Rated
ML20206B336
Person / Time
Site: Point Beach  
Issue date: 11/01/1988
From: Fay C
WISCONSIN ELECTRIC POWER CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CON-NRC-88-104 VPNPD-88-535, NUDOCS 8811150415
Download: ML20206B336 (2)


Text

.__ _ _ -_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. ___ _ _

L.

t

~

Wisconsin Elecinc

,Y POWER COM0AM ni w ucon po.:c.m:3,v% u sm VPNP9-88-335 i

NRC-88-104 November 1, 1980 U. S. NUCLEAR REGULATORY COMMISSION Document Control Desk Mail Station Pl-137 Washington, D.C.

20555 Gentlement DOCKET NOS. 50-266 AND 50-301 4160V SWITCHGEAR ROOM At TERNATE SHUTDOWN CAPABILITY POINT BEACH NUCLEAR PLA*;f, UNIT NOS. 1 AND 2 i

By letter dated April 15, 1987, we submitted our final design fer an alternate shutdown system independent of the 4160V switchgear room l

at Point Beach Nuclear Plant Units 1 and 2.

An alternate shutdown analysis for this area showing conformance to 10 CFR 50 Appendix R Section III.L was submitted on February 29, 1988.

You approved our design in a safety evaluation dated July 27, 1988.

During our review of the safety evaluation we note an area where our submittals may have been misinterpreted.

The technical evaluation attached to the subject safety evaluation states in relation to the gas turbine generator and associated equipment, "The gas turbine and associate output breakers are located in the gas turbine building located away from the 4160V switchgear room.

The turbine and breakers are contained in a room constructed of walls and floor / ceiling assembly that are three-hour fire rated." The gas turbine building is not a three-hour fire rated structure.

It is a separate building of metal panel and steel frame construction wnich is located more than 75 feet west of the main plant baildings.

The 4160V switchgear is located in a three hour firo rated enclosure within the main plant building.

We feel this meets the requirements of 10 CFR 50 Appendix R Section III.L.3 and doc, nr*

nyalidate the conclusions of your July 27, 1988 safety evalua' tun.

We request that the safety evaluation and technical evaluation be amended, as necessary, deleting the reference to the gas turbine and breakers being contained in a room 8911150415 881101 hDR ADOCK 05000266 f (0, i

PDC Ii i

.4 sukkey of Mimnwr Exy Geprma

4..

c.

Document Control Desk November 1, 1988 Page 2 constructed of walls, floor / ceiling that i re three-hour firs rated.

We have discussed this with Mr.

W.

Swenson, our Project Manager, and Mr. D.

Kubicki of your staff.

Mr. Kubicki concurred that the present configuration meets the requirements of Appendix R and does not invalidate the conclusions reached in the safety evaluation.

If you should reqaire any additional information, please contact us.

Very truly yours, s' /

wg 4

,N C.

W.

Fay Vice Presideat Nuclear Power Copy to NRC Regional Administrator, Region III NRC Resident Inspector

.-