Advises That Terms of Commitment for Surveillance Consistent W/Terms Agreed to & Acceptable.Terms Fulfill Commitment Made in for Surveillance Program for ASEA-ATOM Control Rod
ML20206B121
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
Issue date: 04/01/1987
From: Grotenhuis M
Office of Nuclear Reactor Regulation
To: Taylor J
DAIRYLAND POWER COOPERATIVE
References
TAC-61067, NUDOCS 8704080341
Download: ML20206B121 (3)


Text

_ _ _ - _ - _ - _ - _ _ _

30dicf

(

umTEo STATE:

8

.(

NUCLEAR REGULATORY COMMISSION

{

S wasmwarow, o. c. nossa

,y April 1, 1987 Docket No. 50-409 Mr. James W. Taylor General Manager Dalryland Power Cooperative 2615 East Avenue South La Crosse, Wisconsin 54601

Dear Mr. Taylor:

SUBJECT:

SURVEILLANCEOFASEA-ATOMCONTROLRODS(TAC 61067)

Re:

LaCrosseBoilingWaterReactor(LACBWR) in discussions between the NRC staff and ASEA-ATOM (AA), makers of the AA control rods, it was agreed that surveillance should be performed to monitor the AA control rods in the first two U.S. reactors to use these rods.

Accordingly,DairylandPowerCooperative(DPC),byletterdatedMarch 17, 1986, committed to proposing Technical Specification surveillance requirements for AA rods to be instaIIed in LACRWR reactor during the 1987 refueling outage.

Subsequently, when it was seen that LACBWR would not be one of the first two U.S. reactors to use the AA control rod, discussions were held between NRC staff and DPC regarding a suitable program of surveillance of its AA control rods. As a result of those discussions, by your letter of February 5,1987, you connitted to a surveillance program and conditions which we had previously mutually agreed upon in telephone discussions. These are as follows:

(a) Tne two leading LACBWR AA control rods will be visually inspected, using i

underwater television or other appropriate methods, during the first refueling outage after they reach 65% of nuclear design life.

(b) During subsequent refueling outages, one of these control rods or another LAC 8WR AA control rod with equal or greater exposure will be visually inspected.

l (c) All AA control rods which are discharged from the LACBWR will be visually inspected, j

(d) Inspection results of safety significance will be reported to the NRC and NRC approval of any plans for continued operation with defective AA control rods will be obtained.

(e) This inspection program for LACBWR AA control rods is contingent on the results of inspections of similarly designed AA control rods in other reactors which lead to LACBWR rods in exposure history.

9704090341 870401 PDR ADOCK 05000409 P

PDR

N'r. James W. Taylor April 1, 1987 Since the terms of commitment for surveillance are consistent with those agreed upon in our telephone discussion, they are acceptable, and are taken as fulfilling the comitment made in your March 17, 1986 letter for a surveillance program for the LACBWR AA control rod.

Sincerely.

Original signed by Marshall Grotenhuis, Acting Director BWR Project Directorate #1 Division of BWR Licensing cc: See next page DISTRIBUTION:

~

Docket File '

OGC-BETil (Info)

NRC PDR EJordan Local PDR RGrimes BWDf1 Reading JPartlow RBernero NThompson CJamerson Glainas RBevan GHolohan J7wolinski ACRS(10)

La Crosso filo

/

DBL:BWDfl}'([> DBL:BWDf1 DBL:BWDil CJamersonO RBevan/pn MGrotenhuis

.3 / 31/ 87 sf///87 j/ f /87

v._

. o-

=

=-- - - -- - - - --- - - -

'M'r. James W. Taylor Dairyland Power Cooperative La Crosse Boiling Water Reactor cc:

Fritz Schubert. Esquire Mr. Lanning Smith Chief Engineer Staff Attorney Wisconsin Public Service Consiission Dairyland Power Cooperative Post Office Box 7854 2615 East Avenue South Madison, Wisconsin 53707 La Crosse. Wisconsin 54601 Mr. Kevin P. Gallen Newman 8 Holtzinger P.C.

1615 L Street NW Washington, D.C.

20036 Mr. John Parkyn. Plant Manager la Crosse Boiling Water Reactor Dairyland Power Cooperative P. 0. Box 275 Genoa. Wisconsin 54632 U.S. Nuclear Regulatory Commission Resident Inspectors Office Rural Route #1, Box 276 Genoa Wisconsin 54632 Town Chairman Town of Genoa Route 1 Genoa. Wisconsin 54632 Chairman, Public Service Cosmission of Wisconsin Hill Farms State Office Building Madison, Wisconsin 53702 Regional Administrator. Region !!!

U.S. Nuclear Regulatory Conmission 799 Roosevelt Road Glen Ellyn. Illinois 60137

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.