Forwards Response to IE Bulletin 85-003, Motor-Operated Valve Common Mode Failures During Plant Transients Due to Improper Switch Settings
ML20205Q174
Person / Time
Site: San Onofre  
Issue date: 05/19/1986
From: Rainsberry J
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
IEB-85-003, IEB-85-3, NUDOCS 8605280199
Download: ML20205Q174 (21)


Text

.

f55 Southern California Edison Company P O. 00X 000 2244 WALNUT GROVE AVENUE ROSE MEAD, C ALIFORNIA 91770 May 19, 1986 U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 Attention: Mr. John B. Martin, Regional Administrator

Dear Sir:

Subject:

Docket Nos. 50-206, 50-361 and 50.-362 San Onofre Nuclear Generating Station Units 1, 2 and 3 In IE Bulletin 85-03, " Motor-Operated Yalve Common Mode Failures During Plant Transients Due to Improper Switch Settings" Southern California Edison (SCE) was requested to develop and implement a program to ensure that switch settings on certain safety-related motor-operated valves are selected, set and maintained correctly to accommodate the maximum differential pressures expected on these valves during both normal and abnormal events within the design basis. The safety-related motor-operated valves included in this program are in the high pressure safety injection and auxiliary feedwater (emergency feedwater) systems that are required to be tested for operational readiness in accordance with 10 CFR 50.55a(g).

As requested in item e of IE Bulletin 85-03, SCE hereby submits a report (Enclosure 1) which includes (1) the results of Action a, the design 8605280199 860519 PDR ADOCK 05000206 G

PDR 1

(1 f ll

Mr. J. B. Martin basis differential pressure for each applicable valve, and (2) the program to accomplish Actions b through d of this bulletin including a completion schedule which complies with the requirements of Action e.l.

If you would like additional information concerning this matter, please let me know.

Subscribed on this

/b day of

,1986.

U Respectfully submitted, SOUTHERN CALIFORNIA EDISON CONPANY s

By:

.'L.'Rahsberry Supervising Engineer San Onofre Unit 1 Li e ing Subscribed and sworn to before me this

/ft day of Vh j _ F/ %

,%kh LY E Notary Public id and for the County of t$*N$!sYub"N I

Los Angeles, State of California My Comm. Em, Apr. 20,1990 My Commission Expires:

do,/f90 Enclosure cc:

U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 H. Rood, NRC Senior Project Manager, San Onofre Units 2 and 3 R. Dudley, NRC Project Manager, San Onofre Unit 1 F. Huey, NRC Senior Resident Inspector, Units 1, 2 and 3

RESPONSE TO IE BULLETIN 85-03 MOTOR OPERATED VALVE COMMON MODE FAILURE DURING PLANT TRANSIENTS DUE TO IMPROPER SWITCH SETTINGS SAN ONOFRE NUCLEAR GENERATING STATION UNITS 1, 2,

AND 3 IE Bulletin 85-03 requested Southern California Edison to review the design basis of mid to develop and implement a

program to ensure that switch settings on high pressure safety injection and auxiliary feedwater system safety related motor operated valves are

selected, set, and maintained correctly to accommodate the maximum differential pressure expected on these valves during both normal and abnormal events within the design basis.

Valves selected are those that are required to be tested for operational readiness in accordance with 10CFR50.55a (g).

Provided below is the response for San Onofre Nuclear Generating Station.

Action "a"

" Review and document the design basis for the operation of each valve.

This documentation should include the maximum differential pressure expected during both opening and closing the valve for both normal and abnormal events to the extent that these valve operations and events are included in the existing, approved design

basis, (i.e.,

the design basis documented in pertinent licensee submittals such as FSAR analyses and fully-approved operating and emergency procedures, etc.).

When determining the maximum differential

pressure, those single equipment failures and inadvertent equipment operations (such as inadvertent valve closures or openings) that are within the plant design basis should be assumed."

Response "a" SONGS Units 1,

2, and 3 design and operating conditions have been evaluated for the required valves as requested.

The resulting data are presented in Attachments 1, 2,

and 3, "Valv e Datt Symmary", for SONGS Units 1, 2,

and 3 respectively.

Action "b"

"Using the results from item "a"

above, establish the correct switch settings.

This shall include a program to review and

revise, as necessary, the methods for selecting and setting all switches (i.e.,

torque bypass, position limit, overload) for each valve operation (opening and closing).

! L

d If the licensee determines that a valve is inoperable,-the licensee shall also make an appropriate justification for continued' operation in accordance with the applicable technical

, specification."

Response

"b" The plan to accomplish Action "b"

is as follows:

1)

Review the bases provided in item "a".

2)

Calculate torque and thrust requirements for each valve listed in Valve Data Summary.

3)

Revise Limitorque control circuit and wiring such that the torque switch bypass limit switch and open/close limit indicating switches are on separate rotors, where applicable.

4)

Review measured values from the maximum differential pressure test and calculations for torque and thrust and' then establish correct switch settings.

-5)

For valves which are determined to be inoperable, the justification for continued operation will be established.

Action "c" c

" Individual valve settings shall be changed, as appropriate, to those established in item "b",

above.

Whether the valve setting is changed or not, the valve will be demonstrated to be operable

.by.

testing the valve at the maximum differential pressure determined in item "a" above with the exception that testing motor-operated valves under conditions simulating a break in the line containing the valve is not required.

Otherwise, justification should be provided for any cases where testing with the maximum differential pressure cannot practicably be performed.

This justification should

-include the alternative to maximum differential pressure testing which will be used to verify the correct settings.

Note:

This bulletin is not intended to establish a requirement for valve testing' for the condition simulating a break in the line containing the valve.

However, to the extent that such valve 3 -

operation is relied upon in the design basis, a break in the line containing the valve should be considered in the analyses

. prescribed in items "a" and "b"

above.

The resulting switch settings for pipe break conditions should be

verified, to the extent practical, by the same methods that would be used to verify other settings (if any) that are not tested at the maximum differential pressure.

Each valve shall be stroke tested, to the extent practical, to verify that the settings defined in item "b"

above have been properly implemented even if testing with differential pressure can not be performed." -.

f 7" Response "c"

-The plan to accomplish Action "c" is as follows:

1)

Perform valve analysis utilizing Motor Operated Valve Analysis and Test System (MOVATS) on each valve specified in Valve Data Summary to set switches.

Maintenance orders will be used to accomplish all switch settings and data recording.

2)

Determine if a test at maximum differential pressure is possible-and if it can be safely performed with fuel in

-the reactor.

3)'

If a test can not be performed at a maximum differential pressure condition an alternate test and justification for the alternate test will be provided.

Action "d"

" Prepare ~ or-revise procedures to ensure that correct switch settings are determined and maintained throughout the life of the plant.

Ensure that applicable industry recommendations are

. considered in the preparation of these procedures.

This item is intended to be completely consistent with action item 3.2,

" Post-Maintenance Testing (All Other Safety-Related

. Components),"

of Generic Letter 83-28,

" Required Actions Based on Generic Implications of Salem ATWS Events."

-These procedures should include provisions to monitor valve performance to ensure the switch settings are correct.

This is particularly important if the torque or. torque bypass switch setting has been significantly raised above that required."

Response

"d" The plan to accomplish Action "d"

involves documenting all final 4

settings on appropriate drawings and revising the following procedures to include details for inspection, adjusting and documenting the limit, torque and bypass settings for Limitorque MOVs:

S0123-I-6.8

" Actuators - Limitorque Model SMB-O through SMB-4 and SB-0 through SB-4 Disassembly, Inspection, Repair and Assembly" S0123-I-6.7 "Limitorque Model SMB-000, SMB-00 and SB-00 Disassembly, Inspection,

Repair, Assembly and Adjustment" S0123-I-8.313 " Actuators

- Motor Operated Valve Testing Utilizing MOVATS" e

Action "e" "Within 180 days of the date of this bulletin, submit a

written report to-the NRC that: (1) reports the results of item "a" and (2) contains.

the program to accomplish items "b" through "d"

above

- including a schedule for completion of these items.

The schedule shall ensure that these items are completed as soon as practical and within two years from the date of this bulletin".

Response "e" This report completes action "a".

The schedule for accomplishing the program for Actions "b"

through "d" ebove will be completed prior to start up from the outages listed below:

Unit 1 Maintenance Ending June 1987 Outage Unit 2 Refueling Ending June 1986 Outage Unit 3 Refueling Ending March 1987 Outage Summary of the data will be provided within 60 days after canpletion of the Unit 1 Maintenance Q1tage.

As requested, the time required to complete action item "a" was 25 man days.

1 i

t t:

IEB 85-03

^

ATTACHMENT 1 PAGE 1 OF 3 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 1 SAFETY INJECTION SYSTEM Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM)

A57:ii355----- II II;- ue---~~~~~~~i5i i;-----~~~~~~~----- si/---~~

Anchor / Darling SMB-00-**

Charging Pump 78 psi Gate, 570 WDD 1700 rpm suction 4",150 lb MOV-1100B Limitorque RWST to Charging 75 psi /

Anchor / Darling SMB-00-**

Pump Suction 75 psi Gate, 570 WDD 1700 rpm 4",

150 lb MOV-1100D Limitorque RWST to Charging 75 psi /

Anchor / Darling SMB-00-**

Pump Suction 75 psi Gate, 570 WDD 1700 rpm 4",

150 lb MOV-356 Limitorque Charging Pump 2446 psi /

Rockwell SMB-00-25 Discharge to Loop A 2446 psi.

Globe,3624 JM Cold Leg 2 1/2,1500 lb *****

MOV-357 Limitorque Charging Pump 2446 psi /

Rockwell SMB-00-25 Discharge to Loop B 2446 psi Globe,3624 JM Cold Leg 2 1/2",1500 lb *****

MOV-358 Limitorque Charging Pump 2466 psi /

Rockwell SMB-00-25 Discharge to Loop C 2446 psi Globe,3624 JM Cold Leg 2 1/2,1500 lb *****

To Be Supplied with final report

IEB 85-03 ATTACHMENT 1 PAGE 2 0F 3 YALVE DATA

SUMMARY

SAN ONOFRE UNIT 1 SAFETY INJECTION SYSTEM Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motcr RPM Size, Rating Output Speed (RPM)

MOV-850A Limitorque Safety Injection 1750 psi /

Crane SMB-1-40 to RCS Loop A 1750 psi Gate, 6x4x6 1700 rpm 6",

1500 lb MOV-850B Limitorque Safety Injection 1750 psi /

Crane SMB-1-40 to RCS Loop B 1750 psi Gate, 6x4x6 1700 rpm 6",

1500 lb MOV-850C Limitorque Safety Injection 1750 psi /

Crane SMB-1-40 to RCS Loop C 1750 psi Gate, 6x4x6 1700 rpm 6",

1500 lb MOV-883 Limitorque Refueling 16 psi /

W-K-M_

SMB-00-10 Water Storage 16 psi Gate, Pow-R 850 rpm Tank Outlet Seal L

8",

300 lb MOV-866A Limitorque East Recirc 131 psi /

Anchor /D9rling SMB-00-5 Pump Discharge 131 psi

qate,

', 3Ce 8668 Limitorque West Recirc 131 psi / -

Anchor / Darling SMB-00-5 pump discharge 131 psi Gate, 570 WDD 4",

300 lb To Bt. Supplied with final report

~_

4 IEB 85-03 ATTACHMENT 1 PAGE 3 0F 3 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 1 AUXILIARY FEED SYSTEM Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM)

MOV-1202-Limitorque Aux Feedwater 1221 psi /

Westinghouse SB-00-25 Pump Discharge 1221 psi Gate,3-GM 88FN *****

3",

1500 lb MOV-18 Limitorque Seal Filter 2446 psi /

Westinghouse SMB-00-7 1/2 Manifold Bypass 2446 psi Gate, *****

4",

MOV-19 Limitorque Seal Filter 2446 psi /

Westinghouse SMB-00-7 1/2 Manifold Bypass 2446 psi Gate, *****

4",

To Be Supplied with final report

IEB 85-03 ATTACHMENT 2 PAGE 1 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 2 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM

- Size, Rating Output Speed (RPM) 55V 5555---~~~~iimiiorqEe-----~~~- High-~ Pressure 55feiy~~~~5555 psi /~~~

Z

~

Target Rock SMB-00-10-1800 Injection Header No.2 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1A 2",^1500 lb 2HV-9324 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.1 1508 psi Globe,-

1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1A 2",

1500 lb 2HV-9326 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.2 1508 psi.

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1B 2".

1500 lb 2HV-9327 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header,No.1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1B 2",

1500 lb L

~

~

l IEB 85-03 ATTACHMENT'2 PAGE 2 0F 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 2 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) isv:5555------ IisIio qLe--~~~~--- High PresiEre~5Afeiy-~~~~I555~~sI/~~~

~

Target Rock SMB-00-10-1800 Injection Header No.2 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2A 2",

1500 lb 2HV-9330 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2A 2",

1500 lb 2HV-9332 Limitorque High Pressure Safety 1509 psi /

Target Rock SMB-00-10-1800 Injection Header No.2 1509 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2B 2",

1500 lb 2HV-9333 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2B 2",

1500 lb

-w s

c IEB 85-03 ATTACHMENT 2 PAGE 3 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 2 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve-Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) 2HV-9302 Limitorque Containment Emergency 71 psi /

Fisher SMB-00-10-1700 Sump Outlet 71 psi Butterfly 1700 rpm 9220 34.69 rpm 24",

150 lb 2HV-9303 Limitorque Containment Emergency 71 psi /

Fisher SMB-00-10-1700 Sump Outlet 71 psi Butterfly 1700 rpm 9220 34.69 rpm 24",

150 lb 2HV-9420 Limitorque High Pressure Safety 1509 psi /

Target Rock SMB-00-10-1800 Injection to Reactor 1509 psi Globe 1800 rpm Coolant Loop 2A Hot 74R-003 50 rpm Leg 3",

1500 lb 2HV-9434 Limitorque High Pressure Safety 1509 psi /

Target Rock SMB-00-10-1800 Injection to Reactor 1509 psi Globe 1800 rpm Coolant Loop 1A 74R-003 50 rpm Hot Leg 3",

1500 lb

IEB 85-03 ATTACHMENT 2 PAGE 4 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 2 HIGH PRESSURE SAFETY INJECTION V'alve Design Valve Valve Operator Function Basis d/p Compone.

ID Manufacturer, Open/Close Manufactarer Model Type, Model Motor RPM Size, Rating Output Speed (RPM)

Eiv:5355--~~~~~ii;Itor se-----~~~~ iifeguard Pumps ~~~~~~~~~~1557 psi /~~~

WKM SMB-00-5-1800 Mini-Flow 1517 psi

Gate, 1800 rpm M-Pow-R-Seal 30.46 rpm 4",

000 lb 2HV-9307 Limitorque Safeguard Pumps 1518 psi /

WKM SMB-00-5-1800 Mini-Flow 1518 psi

Gate, 1800 rpm M-Pow-R-Seal 30.46 rpm 4",

900 lb 2HV-9347 Limitorque Safeguard Pumps 1517 psi /

i WKM SB-00-5-1800 Mini-Flow 1517 psi

Gate, 1800 rpm M1-Pow-R-Seal 28.61 rpm 4

900 lb 2HV-9348 Limitorque Safeguard Pumps 1518 psi /

WKM SMB-00-5-1800 Mini-Flow 1518 psi

Gate, 1800 rpm M-Pow-R-Seal 28.61 rpm 4",

900-lb t

IEB 85-03 ATTACHMENT 2 PAGE 5 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 2 AUXILIARY FEEDWATER Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer,-

Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) 2HV-4706 Limitorque Auxiliary Feedwater 1386 psi /

WKM SMB-000-2-1900 Pump, P-140, Discharge 138G psi

Globe, 1900 rpm to Steam Generator 70-28-2MO 25.33 rpm E-089 4",

900 lb 2HV-4713' Limitorque Auxiliary Feedwater 1386 psi /

WKM SMB-000-2-1800 Pump, P-141, Discharge 1386 psi

Globe, 1800 rpm to Steam Generator 70-28-2MO 25.0 rpm E-089 4",

900 lb 2HV-4715 Limitorque Auxiliary Feedwater 1388 psi /

WKM SB-00-15-1900 to Steam Generator 1388 psi

Globe, 1900 rpm E-089, isolation 70-28-2MO 59.56 rpm valve 6",

900 lb 2HV-4705 Limitorque Auxiliary Feedwater 1380 psi /

WKM SMB-000-2-1900 Pump, P-140, Discharge 1380 psi

Globe, 1900 rpm to Steam Generator 70-28-2MO 25.33 rpm E-088 4",

900 lb

IEB 85-03 ATTACHMENT 2 PAGE 6 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 2 AUXILIARY FEEDWATER Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) ihV 4715------ Eisiior ue-----~~-- luxiiisry FeedwAier~~~~~~1555 psi /~~~

-WKM SMB-000-2-1800 Pump P-504, Discharge 1380 psi

Globe, 1800 rpm to Steam Generator 70-28-2MO 25.0 rpm E-088 4",

000 lb 2HV-4730 Limitorque Auxiliary Feedwater 1388 psi /

WKM SB-00-15-1900 to Steam Generator 1388 psi

Globe, 1900 rpm E-088 Isolation 70-28-2MO 59.56 rpm Valve 6",

900 lb 2HV-4716 Limitorque Auxiliary Feedwater 1210 psi /

Gimpel, Inc.

SMB-000-35-1800 Pump, P-140, Turbine 1210 psi

Globe, 1800 rpm Stop Valve 74-12235-1 4",

900 lb

  • To Be Supplied with final report

IEB 85-03 ATTACHMENT 3 PAGE 1 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 3 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) 3Hv:5555-~~~~~~IImIIErqGe--------- High Pre $s5re 55feiy~~~~~I555 psi /~~~

~

Target Rock SMB-00-10-1800 Injection Header No. 2 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1A 2",

1500 lb 3HV-9324 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1A 2",

1500 lb 3HV-9326 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.2 1508 psi

Globe, 1800. rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1B 2",

1500 lb 3HV-9327 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No 1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 1B 2",

1500 lb A

v IEB 85-03 ATTACHMENT 3 PAGE 2 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 3 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve Operator.

Function Pasis d/p

. Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size,' Rating Output Speed (RPM) 35V5335-~~~~- IIsitor se-~~~~~~~~~5Igh Press $re~5a fei~~~~~~5555~ psi /~~~

Target Rock SMB-00-10-1800 Injection Header No.2 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2A 2",

1500 lb i

3HV-9330 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2A 2",

1500 lb 3HV-9332 Limitorque High Pressure Safety 1509 psi /

Target Rock SMB-00-10-1800 Injection Header No.2 1509 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2B 2",

1500 lb 3HV-9333 Limitorque High Pressure Safety 1508 psi /

Target Rock SMB-00-10-1800 Injection Header No.1 1508 psi

Globe, 1800 rpm to Reactor Coolant 74R-002 36.3 rpm Loop 2B 2",

1500 lb L

.f.

t IEB 85-03 ATTACHMENT 3 PAGE 3 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 3 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM

= Size, Rating Output Speed (RPM) 3HV-9302 Limitorque Containment Emergency 71 psi /

Fisher SMB-00-10-1700 Sump outlet 71 psi Butterfly 1700 rpm 9220 34.69 rpm 24"_,

150 lb 3HV-9303 Limitorque Containment Emergency 71 psi /

Fisher SMB-0 0 170 0 Sump Outlet 71 psi Butterfly 1700 rpm 9220 34.69 rpm 24",

150 lb 3HV-9420 Limitorque High Pressure Safety 1509 psi /

Target Rock SMB-00-10-1800 Injection to Reactor 1509 psi 74R-003 1800 rpm Coolant Loop 2A Hot Leg 3",

1500 lb 50 rpm 3HV-9434 Limitorque High Pressure Safety 1509 psi /

Target Rock SMB-00-10-1800 Injection to Reactor 1509 psi Globe 1800 rpm Coolant Loop 1A Hot Leg 74R-003 50 rpm 3",

1500 lb

]

IEB 85-03 ATTACHMENT 3 PAGE 4 0F 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 3 HIGH PRESSURE SAFETY INJECTION Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) 5HV5555--~~~- IIsiisrqEe-----~~-- 5sfegisrd PE$ps~~~~~~~~~~1557 psi /~~~

~

WKM SMB-00-5-1800 Mini-Flow 1517 psi

Gate, 1800 rpm M-Pow-R-Seal 30.46 rpm 4",

900 lb 3HV-9307 Limitorque Safeguard Pumps 1518 psi /

WKM SMB-00-5-1800 Mini-Flow 1518 psi

Gate, 1800 rpm M-Pow-R-Seal 30.46 rpm 4",

900 lb 3HV-9347 Limitorque Safeguard Pumps 1517 psi /

WKM SB-00-5-1800 Mini-Flow 1517 psi

Gate, 1800 rpm M1-Pow-R-Seal 28.61 rpm 4",

000 lb 3HV-9348 Limitorque Safeguard Pumps 1518 psi /

WKM SMB-00-5-1800 Mini-Flow 1518 psi

Gate, 1800 rpm M-Pow-R-Seal 28.61 rpm 4",

900 lb

-.M

3 IEB 85-03 ATTACHMENT 3 PAGE 5 OF 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 3 AUXILIARY FEEDWATER Valve Design Valve Valve Operator Function Basis d/p Component ID Manufacturer, Open/Close Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM) 3HV-4706 Limitorque Auxiliary Feedwater 1386 psi /

WKM SMB-000-2-1900 Pump, P-140, Discharge 138G psi

Globe, 1900 rpm to Steam Generator 70-28-2MO 25.33 rpm E-089 900 lb 4"_,

3HV-4713 Limitorque Auxiliary Feedwater 1386 psi /

WKM SMB-000-2-1800 Pump, P-141, Discharge 1386 psi

Globe, 1800 rpm to Steam Generator 70-28-2MO 25.0 rpm E-089 4"_, 900 lb 3HV-4715 Limitorque Auxiliary Feedwater 1388 psi /

WKM SB-00-15-1900 to Steam Generator 1388 psi

Globe, 1900 rpm E-089, Isolation 70-28-2MO 59.56 rpm Valve 6",

000 lb 3HV-4705 Limitorque Auxiliary Feedwater 1380 psi /

WKM SMB-000-2-1900 Pump, P-140, Discharge 1380 psi

Globe, 1900 rpm to Steam Generator 70-28-2MO 25.33 rpm E-088 4",

900 lb

4 a.

IER 85-03 ATTACHMENT 3 PAGE 6 0F 6 VALVE DATA

SUMMARY

SAN ONOFRE UNIT 3 AUXILIARY FEMDWATER Valve Design Valve Valve Operator Function Basis d/p

- Component ID Manufacturer, Open/Close

-Manufacturer Model Type, Model Motor RPM Size, Rating Output Speed (RPM)

' 3HV-4712 Limitorque Auxiliary Feedwater 1380 psi /

WKM SMB-000-2-1800 Pump P-G04, Discharge 1380 pai

Globe, 1800 rpm to Steam Generator 70-28-2MO 25.0 rpm E-088 4",

900 lb

.3HV-4730 Limitorgae Auxiliary Feedwater 1388 psi /

WKM SB-00-15-1900 to Steam Generator 1388 psi

Globe, 1900 rpm E-088, Isolation l

70-28-2MO 59.56 rpa valve 6",

900 lb 3HV-4716 Limitorque Auxiliary Feedwater 1210. psi /

Gimpel, Inc.

SMB-000-35-1800 Punp P-140, Turbine 1210 psi

Globe, 1800 rpm Step Valve 74-12235-2 4",

900 lb