Amends 230 & 206 to Licenses DPR-53 & DPR-69,respectively, Revising TS 3.7.6 to Allow Operation of Units 1 & 2 with One SRW Plate & Frame Heat Exchanger in Subsystem Secured
ML20205P776
Person / Time
Site: Calvert Cliffs  
Issue date: 04/14/1999
From: Bajwa S
NRC (Affiliation Not Assigned)
To:
Shared Package
ML20205P780 List:
References
NUDOCS 9904200358
Download: ML20205P776 (8)


Text

i 4@MGy y

t UNITED STATES g."

g NUCLEAR REGULATORY COMMISSION WASHINGToW, D.C. 20555-0001

/

  • se**

BALTIMORE GAS AND ELECTRIC COMPANY DOCKET NO. 50-317 CALVERT CLIFFS NUCLEAR POWER PLANT UNIT NO.1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. N License No. DPR-53 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Baltimore Gas and Electric Company (the licensee) dated November 19,1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and l

security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the j

Commission's regulations and all applicable requirements have been satisfied.

1 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.2. of Facility Operating License No. DPR-53 is hereby amended to read as follows:

l 9904200358 990414 PDR A00CK 0S000317 P

POR i.

2.

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 230, are hereby incorporated in the license. The licensee shall j

operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 30 days.

FOR THE NUCLEAR REGULATORY COMMISSION fM S. Singh Bajwa, Chief, Section 1 j

Project Directorate I Division of Licensing Project Manags.nent Office of Nuclear Reactor Regulation j

1

Attachment:

Changes to the Technical Specifications l

Date of issuance:

April 14,19%

j i

I l

l l'

{-

L

ps ato y'-

/t UNITED STATES E

NUCLEAR REGULATORY COMMISSION E

i!

WASHINGTON, D.C. 205554001

...../

bat.TIMORE GAS AND ELECTRIC COMPANY DOCKET NO. 50-318

~

CALVERT CLIFFS NUCLEAR POWER PLANT UNIT NO. 2 AMENENENT TO FACILITY OPERATING LICENSE Amendment No. M i

License No. DPR-69 l

-1.

The Nuclear Regulatory Commission (the Commission) has found that:

i A.

The application for amendment by Baltimore Gas and Electric Company (the l

licensee) dated November 19,1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, l

l and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment 1

can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations;-

l L

D.

The issuance of this amendment will r.ot be inimical to the common defense and security or to the health and sait,ty ? the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the j

Commission's regulations and all applicable requirements have been satisfied.

j i

i l

2.'

Accordingly, the license is amended by changes to the Technical Specifications as l

indicated in the attachment to this license amendment, and paragraph 2.C.2. of Facility i

l Operating License No. DPR-69 is hereby amended to read as follows:

i l

i I

i o

2-t 2.

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through l

Amendment No. 206, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 30 days.

FOR THE NUCLEAR REGULATORY COMMISSION l

f/

S. Singh Bajwa, Chief, Section 1 Project Directorate i Division of Licensing Project Management Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical L

Specifications l

Date of issuance: April 14, 1999 l

4 6

A

.i

9 l

ATTACHMENT TO LICENSE AMENDMENTS AMENDMENT NO. 2%

FACILITY OPERATING LICENSE NO. DPR-53 AMENDMENT NO. 206 FACILITY OPERATING LICENSE NO. DPR-69 DOCKET NOS. 50-317 AND 50-318 Revise Appendix A as follows:

Remove Paoe Insert Paae l

3.7.6-1 3.7.6-1 3.7.6-2 3.7.6-2 3.7.6-3 l

e

g SRW l-3.7.6 L

3.7 PLANT SYSTEMS l

3.7.6 Service Water (SRW) System I

l LC0 3.7.6 Two SRW subsystems shall be OPERABLE.

{

l i

l

. APPLICABILITY:

MODES 1, 2, 3, and 4.

I l

ACTI0t3 CONDITION REQUIRED ACTION COMPLETION TIME l

'A.

One SRW heat A.1 Isolate flow to one 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> exchanger inoperable.

of the associated containment cooling units.


NOTE -------

l Enter applicable Conditions and Required Actions of LC0 3.6.6,

" Containment Spray and Cooling Systems,"

l for one containment

{

cooling train made

{

inoperable by the heat exchanger.

j AND A.2 Restore heat 7 days exchanger to operable l

status.

I CALVERT CLIFFS - UNIT 1 3.7.6-1 Amendnant No. 230 CALVERT CLIFFS - UNIT 2 Amendment No. 206 L_.

SRW 3.7.6 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME i

B.

One SRW subsystem B.1


NOTE l

inoperable.

Enter applicable Conditions and Required Actions of LC0 3.8.1, "AC Sources--Operating,"

for diesel generator made inoperable by SRW.

i I

Restore SRW subsystem 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to OPERABLE status.

l C.

Required Action and C.1 Be in MODE 3, 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> l

I associated Completion Time of Condi. ion A AND or B not met.

C.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> i

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.6.1


NOTE-------------------

Isolation of SRW flow to individual components does not rerder SRW inoperable.

Verify each SRW manual,. power-operated, and 31 days automatic valve in the flow path servicing safety-related equipment, that is not locked, sealed, or otherwise secured in position, is in the correct position.

CALVERT CLIFFS'- UNIT 1 3.7.6-2 Amendment No. 230

.CALVERT CLIFFS - UNIT 2 Amendment No. 206

r j

SRW j

3.7.6 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.7.6.2 Verify each SRW automatic valve in the flow 24 months path that is not locked, sealed, or l

otherwise secured in position, actuates to the correct position on an actual or simulated actuation signal.

1 SR 3.7.6.3 Verify each SRW pump starts automatically on 24 months an actual or simo ated actuation signal.

i l

i 1

l CALVERT CLIFFS - UNIT 1 3.7.6-3 Amendment No. 230 CALVERT CLIFFS - UNIT 2 Amendment No. 206 L