Special Rept:On 860606,Fire Door 137 Breached to Perform Mod to Door.On 860612,fire Detection Sys DA4116W Removed from Svc to Support Welding Activities in Area.Door & Sys Returned to Svc on 860624 & 26,respectively
ML20205B317
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 07/18/1986
From: Lempges T
NIAGARA MOHAWK POWER CORP.
To: Murley T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NMP-19625, NUDOCS 8608110566
Download: ML20205B317 (1)


Text

=

NMP-19625 NIAGARA MOH AWK POWER CORPORATION NIAGARA MOHAWK 300 E' R I E BOULEVARO WEST SYR ACU S E. N. Y.13 2 02 THOMAS E LEMPGES WE PAESOENT-88uCLE AA GENEAAf08 July 18, 1986 Dr. Thomas E. Murley Regional Administrator United States Nuclear Regulatory Commission Region 1 631 Park Avenue King Of Prussia, PA 19406 RE:

Docket No. 50-220 SPECIAL REPORT Gentlemen:

In accordance with the Nine Mile Point Unit I Technical Specifications a Special Report is required for each fire barrier and detection system that is out-of-service for more than 14 days.

During the recent refueling outage, two of these incidents occun 3d.

Each is described below. A separate Special Report will not be submitted for each incident since this letter satisfies the reporting requirements.

On June 6, 1986 fire door 137 (Turbine Building 261', MSIV Room) was breached to perform a modification to the fire door. The fire door was declared non-functional in accordance with Technical Specification 3.6.10.1 (Fire Barrier Penetrations).

In accordance with Technical Specification 3.6.10.1.b a continuous fire watch was established. The fire door was returned to service on June 24, 1986 and the continuous fire watch was removed.

On June 12, 1986 fire detection system DA4116W (Reactor Building 261') was removed from service to support welding activities in the area. The system was declared inoperabic in accordance with Technical Specification 3.6.6 (Fire Detection).

Since an inoperabic fire door existed in the detection area, a continuous fire watch was established in accordance with Technical Specification 3.6.10.1.b.

On June 26, 1986 the detection system was returned to service and the continuous fire watch was removed.

Sincerely, 10 r600110566Bh0220 Thomas E. Lempges ADOCW O PDR Vice President

'y PDR B

Nuclear Generation

((q s

l TEL/ tb cc: Document Control Desk

.