Part 21 & Deficiency Rept Re Tdi Diesel Generator Lube Oil Pump Section Foot Valve.Other Plants Not Susceptible to Failures Experienced at Shearon Harris.Item Not Reportable Per Part 21 or 10CFR50.55(e)
ML20205A828
Person / Time
Site: Vogtle  
Issue date: 07/25/1986
From: Foster D
GEORGIA POWER CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21-86 GN-1017, NUDOCS 8608110455
Download: ML20205A828 (1)


Text

V

,(

Georg:a Power Company Post Of fice Box 282 4

Waynesboro, Georgia 30830 Telephone 404 554-9961. Ext. 3360 404 724-8114. Ext. 3360 GeorgiaPower

0. 0. Foster mo <w n thync sgier p

July 25,1986 N

United States Nuclear Regulatory Commission

,E Region II File: X7BG03-i1115 Suite 2900 Log:

GN.1017 101 tiarietta Street, Northwest ca Atlanta, Georgia 30323 VogtleElectricGeneratingPlant-Units 1and2;50-4245$0-425;

Reference:

Diesel Generator Lube Oil Pump Section Foot Valve; Letters GN-918 dated 5/23/86 and GN-1002 dated 7/15/86 Attention: Mr. J. Nelson Grace Georgia Power Company has completed its evaluation of the referenced concern which was initially reported to the USNRC pursuant to 10 CFR 21 by Transamerica Delaval.

Additional information provided by Transamerica Delaval indicates that Vogtle is not affected by the reported concern.

Georgia Power Company conducted an engineering evaluation of the Vogtle diesel generator lube oil system design and confirmed that our equipment is not susceptible to the failures experienced at the Shearon Harris plant.

Therefore, this concern is not reportable pursuant to 10 CFR 50.55(e) or 10 CFR 21 for the Vogtle Electric Generating Plant.

Copies of the correspondence from Transamerica Delaval are attached for your convenience.

This response contains no proprietary information and may be placed in the NRC Public Document Room.

Yours truly,

$[kNN Ih S

D. O. Foster F REF/D0F/tdm Attachment xc:

U. S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.

20555 J. H. iiiller R. A. Thomas L. T. Gucwa J. P. O'Reilly D. R. Altman C. W. Hayes G. F. Head P. R. Bemis G. A. ficCarley R. E. Conway J. A. Bailey D. S. Read igd}

J. T. Beckham

0. Batum Sr. Resident (NRC)

R. H. Pinson G. Bockhold C. S. McCall (OPC) 4 P. D. Rice C. E. Belflower J. E. Joiner (T" B. M. Guthrie J. F. D'Amico D. C. Teper U.S. NRC REGION U D. E. Dutton E. D. Groover NORilS OFFICIAL COPY

v.

Transamenca

~"- aaa"=

En^crprise Engine Dmsion i

hg(gygl Enterpnse Way & 95m Annue a lg cjj l[,

a i-P.O. Box 2161 e

8 t=

Oektene. Cahforne 94621 g

(415) 577 7400 3, g, it March 10, 1986 Report #135 i

Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission

. Washington, D.C.

20555 1

Dear Sir:

In accordance with the requirements of Title 10, Chapter 10, Code of Federal Regulations, Part 21, Transamerica Delaval Inc. hereby notifies the Commission of a potential defect in a component of a DSRV Standby Diesel Generator.

There could exist a potential problem with the Lube Oil Sump Tank Foot Valve.

Transamerica Delaval Inc. has supplied this component with the potential problem to the following nuclear sites-:

UTILITY SITE SERIAL f MODEL Mississippi Power & Light Grand Gulf 74033/36 DSRV-16-4 Gulf States Utilities River Ber.d 74039/40 DSR-48 Carolina Power & Light Shearon Harris 74046/49 DSRV-16-4 Duke Power Catawba 75017/20 DSRV-16-4 S. Cal. Edison San Onofre 75041/42 DSRV-16-4 Cleveland Electric Perry 75051/54 DSRV-16-4 Tennessee Valley Authority Bellefonte 75080/83 DSRV-16-4 W.P.P.S.S.

WNP 1 75084/85 DSRV-16-4 Texas Utilities Comanche Peak 76001/4 DSRV-16-4 Georgia Power Vogtle 76021/24 DSRV-16-4 Consumer Power Midland 77001/4 DSRV-12-4 Tennessee Valley Authority Hartsville/Phipps 77024/35 DSRV-16-4 S.M.U.D.

Rancho Seco 81015/16 DSR-48 1565i?D994

,.t

.Transamenoa Delaval

~

BE i,

s U.S. Nuclear Regulatory Commission March 10, 1986 Page 2 At Carolina Power and Light, Shearon Harris Plant, the elastomer liner in the foot valve mounted in the Lube Oil Sump Tank was found in pieces.

This condition was found during maintenance of the lube oil system performed by Carolina Power personnel.

The foot valve is manufactured by the Clearflow Company 1ocated in Berkeley, California.

The disintergration of the liner could cause a restriction in the valve preventing flow of oil to the on-engine lube oil pump, or the liner pieces could flow upstream lodging in and damaging the on-engine lube oil pump.

Either failure will cause a loss of lube oil to the engine, effecting engine availability.

Transamerica Delaval Inc. is waiting for Carolina Power to return the damaged liner so that we can determine the cause of the failure, and corrective action measures.

Transamerica Delaval Inc. recommends that the Utilities inspect the condition of the foot valve liners and notify the TDI Customer Service Department of the findings.

TDI will make all Utilities fully aware of our failure analysis of the Carolina Power & Light foot valve liner and will report the findings to the other Utilities as they become known to us.

A copy of this letter will be sent to all of the sites referenced in Paragraph 2 of this letter as indicated by the carbon copy list.

Our evaluation of this matter was concluded on March 10, 1986.

Ve truly your,

ance Block Q.A. Engineer LRB:ddm r-

r~

, ~v.'*

TF8DS8158FIOS O

Enterpnee Engine Dmeen e[

h i

t gl Enterpnee Way & 45m Avenue e)

P.O. som 2161

  • \\

\\ ]y a

Oakland. Cahfornia 94621 s

(415) 577 7400 g

w May 8, 1986 Report #135 Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555

Dear Sir:

On March 10, 1986, Transamerica Delaval notified the Nuclear Regulatory Commission that a potential defect existed with the lube oil sump tank foot valves a component of DSR or DSRV

/

Standby Diesel Generator.

The purpose of this letter is to modify the list of affected sites as a result of our further investigation.

At the time of our March 10 notification, preliminary information was that the valve liner material was deteriorating.

Our final investigation, however, reveals that the valve was being overpressurized causing extrusion of the liner material.

Not:all of the sites identified in our March 10 letter are affected by this failure mode.

We have reviewed piping schematics and find the following sites are affected:

UTILITY SITE SERIAL f MJDEL CP & L Shearon Harris 74046-49 DSRV-16-4 TVA Bellefonte 75080-84 DSRV-16-4 WPPSS WPPSS 1 75085-86 DSRV-16-4 Texas Utilities Commanche Peak 76001-04 DSRV-16-4 Consumers Power Midland 77001-04 DSRV-16-4 We are continuing to develop a course for corrective action and will keep all parties appraised of our recommendations.

A copy of this letter will be forwarded to all of the-sites affected by our original notification.

S cm ly,

+.

B.C.

trum Manh

, Quality Assurance BCG:ddm TYdWW

.