Responds to NRC Re Violations Noted in Insp Repts 50-445/88-58 & 50-446/88-54.Corrective Actions:Qc Personnel Responsible for Watertight Door Insps Instructed to Ensure Required Insps of Watertight Door Commodities Performed
ML20205A085
Person / Time
Site: Comanche Peak  
Issue date: 10/21/1988
From: Counsil W, Woodlan D
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
TXX-88735, NUDOCS 8810250384
Download: ML20205A085 (4)


Text

e.

-~

Log # TXX-88735

~

File # 10130 E

E IR 88-58 IR 88-54 nlELECTRIC gef, o goc 7pg,20g wn yg October 21, 1988 U. S. Nuclear Degulatory Commission Attn: Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS 50-445 AND 50-446 RESPONSE TO NRC INSPECTION REPORT N05.

50-445/88-58 AND 50-446/88-54 Gentlemen TV Electric has reviewed your letter dated September 21, 1988 concerning the inspection conducted by Mr. M. Runyan and an NRC consultant during the period August 3 through September 8,1988.

This inspection covered activities authorized by NRC Construction Permits CPPR-126 and CPPR-127 for CPSES Units 1 and 2.

Attached to your letter was a Notice of Violation.

We hereby respond to the Notice of Violation in the attachment to this letter.

Very truly yours, u ). c,. % n. L S W. G. Counsil By t, D.R. Woodlan Docket Licensing Manager RDD/mlh Attachment c - Mr. R. D. Martin, Region IV Resident inspectors, CPSFS (3) 8M02503g4 g83o23 g

ADOCK 05000445 PNU l

@ North Obw Street LB 8I Dellas, Tem 73.W

Attachment to TXX-88735 October 21, 1988 Page 1 of 2 NOTICE OF VIOLATION

- (44578858 V;02)-

1 Criterion V of A)pendix B to 10 CFR Part 50, as implemented by Section 5.0, Revision 0, of t1e TV Electric Quality Assurance Manual dated February 1, 1988, requires that activities affecting quality shall be prescribed by and accomplished in accordance with documented instructions, procedures, or drawings.

Paragraph 7.1 of Field Verification Method (FVM) CPE-SWEC-FVM-EE/ME/IC/CS-090, Revision 5, states:

"Those coninodities and associated attributes identified on Attachments 1-4 of this FVM shall be reinspected by Quality Control in accordance with the referenced specification criteria identified on Attachments 1-4 of the FVM." to this FVM shows that location, orlentation, and welding are to be inspected for structural steel.

Contrary to the above, Post Construction Hardware Validation Program (PCHVP) package CS-090-SG1-773-54al, for a safety-related watertight door, contains inspection Report 1-Olf with attributes for location, orientation, and l

welding incorrectly mv4 N/A" (not applicable).

Construction traveler CE-82-201-8903, the orig.

'struction document, specifies, in part that:

(1) the door assembly 1.

ation and location be verified and (2) welding be used between the dor

'd the associated embeds.

The welds provide structural attachment o. we 6.

N te the building walls and/or provide a watertight seal.

The att -

tes for location, orientation, and welding are i

applicable to this PCHVF r koge (445/8858-V-02).

l e

L RESPONSE TO NOTICE OF V10LM10N (445/8858-V-02)

TV Electric agrees with the alleged violation and the requested information follows:

1.

Reason for Violation f

I This violation was the result of incorrect interpretation and i

implementation of NQI-3.09-M-005, "Field Verification of Structural and Miscellaneous Steel". Specifically, the embedded frame for the watertight I

door should have been inspected as a "structural steel" item which includes attributes for inspection of location, orientation and site-performed welding. However, the watertight door inspection documented in package CS-090-SG1-773-54-51 was for a "structural embed" inspection.

The applicable inspection attribute for structural embeds is for base metal damage / defects. Since watertight door frames are unique configurations in that they are considered "embedded structural steel" items, the applicable attributes for PCHVP ir,spections were not consistently implemenied, as exemplified by the incomplete in,pn tion noted in this violation.

4 Attachment to TXX-88735 r

October 21, 1988 Page 2 of 2 NOTICE OF VIOLATION (445/8BT8-V-02) ~

2.

Corrective Steps Taken and Results Achieved Of the twelve watertight doors subject to Post Construction Hardware Validation Program (PCHVP) inspection, seven doors have been inspected including door number S-6 as documented in package CS-090-SG1-773-54-51.

The seven completed packages have been reviewed by QC supervision to determine if additional deficiencies existed.

As a result of this review, OR C-88-04499 was initiated to document the failure to inspect the location, orientation and site-performed welds on door 5-6 as noted in the violatiot, as well as failure to inspect for base metal damage of embeds for doors S-4 and S-26, packages CS-090-SG1-773-53-51 and CS-090-0G-1-810-85-508, respectively.

The disposition of DR C-88-04499 will correct these deficiencies.

3.

Corrective S_teps Which Will be Taken to Avoid further Violations In addition to the review of completed watertight door packages described above, QC supervision performed reviews of other miscellaneous steel commodities inspected per P')l-3.09-M-005.

Pipe whip restraints, i

i platforms, monorails and electrical equipment packages were reviewed to determine if similar deficiencies existed.

This review did not identify inspection deficiencies similar to those involving embedded watertight 1

door commodities.

Based on this review we consider this violation to be i

limited to the inspection of embedded watertight doors.

QC personnel responsible for watertight door inspections have been I

instructed in the requirements of NQI-3.09-H-005 to assure that the required inspections of embedded watertight door comodities are correctly j

performed.

This instruction of QC personnel is considered sufficient to avoid further violations.

t 4.

Date When Full Compliance Will be Achieved The review and reinstruction described above was achieved on October 18, j

1988.

The corrective actions associated with DR C-88-04499 will be i

completed by November 30, 1988.

I i

]

I f

l

)

1 1

I i

i 1

1 Outgaing Corrospondence bec (6):

M. D. Spence J. J. Kelley M. R. Steelran A

W. G. Counsil L. Kennedy W. L. Stendebach I

J. W. Beck J. E. Krechting P. B. Stevens i

R. W. Ackley O. W. Lowe J. F. Streeter J. J. Allen D. M. McAfee/

TXX File D. L. Anderson P. E. Halstead C. L. Terry t

ARMS R. E. McCaskill T. G. Tyler R. P. Baker J. P. McGaughy

0. Vandeputte J. L. Barker G. McGrath J. L. Vota R. Bentley J. W. Muffett E. L. Wagoner Bethesda Licensing L. D. Nace R. D. Walker /

W. R. Burchette D. E. Noss J. S. Marshall J. H. Butts PIMS K. C. Warapius R. D. Calder S. S. Palmer H. M. Warren (2)

F. A. Camp L. E. Powell R. A. Werner R. L. Cloud R. L. Ramsey N. H. Williams G. Dawe C. J. Rawley D.R.Woodlan!

R. D. Delano J. O. Redding R. A. Wooldridge D. E. Deviney D. M. Reynerson 1

J. Ellis N. S. Reynolds W. D. Fenoglio M. J. Riggs

[

s R. M. Fillmore M. A. Robinson J. Garibaldi H. C. Schmidt l

T. A. Hope A. B. Scott A. Husain C. E. Scott i

R. T. Jenkins M. G. Schwarz S. D. Karpyak J. Smith August 25, 1988

  • - First Class Mail I

-.