Amend 86 to License NPF-69,changing Surveillance Frequencies in TS 4.8.4.4a & 4.8.4.5a to Require Testing of Electrical Protection Assemblies Once Every 6 Months with Plant on-line Rather than Shutdown
ML20204G270
Person / Time
Site: Nine Mile Point 
Issue date: 03/18/1999
From: Bajwa S
NRC (Affiliation Not Assigned)
To:
Shared Package
ML17059C596 List:
References
NUDOCS 9903260117
Download: ML20204G270 (5)


Text

~

po af og i

f*

,2%

UNITED STATES

  • ,ipj[(/

y.

Zi,j NUCLEAR REGULATORY COMMISSION g

WASHINGTON. D.C. 2055HX)01 s, u NIAGARA MOHAWK POWER CORPORATION DOCKET NO. 50-410 NINE MILE POINT (FJCLEAR STATION. UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.86 License No. NPF-69

1. The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Niagara Mohawk Power Corporation (the licensee) dated November 19,1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended ll.he Act) and the Commission's rules and regulations set forth in 10 CFR Chapter 1; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The it.suance of this amendment will not be inimical to the common oefense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-69 is hereby amended to read as follows:

9903260117 990318 PDR ADOCK 05000410 P

PDR l

... ~. -.

l j (2)

Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A and the Environmenta!

Protection Plan contained in Appendix B, both of which are attached hereto, as revised through Amendment No.86 are hereby incorporated into this license.

Niagara Mohawk Power Corporation shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance to be implemented within 30 days.

FOR THE NUCLEAR REGULATORY COMMISSION N#

p S. Singh Bajwa, Director Project Directorate I-1 Division of Licensing Project Management i

Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: March 18,1999 l

l i

~..

ATTACHMENT TO LICENSE AMENDMENT NO. 86 TO FACILITY OPERATING LICENSE NO. NPF-69 DOCKET NO. 50-410 Replace the following pages of the Appendix A Technical Specifications with the attached pages. The revised pages are identified by Amendment number and contain verticallines indicating the areas of change.

Remove Insert 3/4 8-32 3/4 8-32 3/4 8-33 3/4 8-33 l

4

j ELECTRICAL POWER SYSTEMS l-ELECTRICAL EQUIPMENT PROTECTIVE DEVICES REACTOR PROTECTION SYSTEM ELECTRICJ'OWER MONITORING (RPS LOGIC) h]gTING CONDITIONS FOR OPERATION 3.8.4.4 Two RPS UPS electrical protection assemblies for each inservice UPS set or alternate source shall be OPERABLE.

APPLICABILITY: At all times.

m,. TlON:

With one RPS electrical pictection assembly for an inservice RPS UPS incperable, a.

restore the inoperable electrical protection assembly to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or remove the associated RPS UPS from service.

b.

With both RPS electrical protection assemblies for en inservice F,FS UPS inoperable, l

restore at least one electrical protection assembly to OPERABLE status within 30 minutes or remove the associated hPS UPS from service.

l SURVEILLANCE REQUIREMENTS 4.8.4.4 The above specified RFS electrical protection assemblies instrumentation shall be determined OPERABLE:

a.

At least once every 6 months by performance of a CHANNEL F UNCTIONAL TEST.

b.

At least once per 18 months by demonstrating the OPERABILITY of overvoltage, undervoltage and underfrequency protective Instrumentation by performance of a CliANNEL CALIBRATJON including simulated automatic actuation of the protective relays, tripping logic and output circuit breakers and verifying the following setpoints.

1.

Overvoltage Bus A:

s 132 volts AC Bus B:

s 132 volts AC 2.

- Undervoltage Bus A-2117.1 volts AC Bu; 2 115.75 volts AC i

2.

Underfrequency a 57 Hz t

NINE MILE POINT - UNIT 2 3/4 8-32 Amendment No. (( M

=

El.ECTRICAL POWER SYSTEMS ELECTRICAL EQUIPMENT PROTECTIVE DEVICES REACTOR PROTECTION SYSTEM ELECTRIC POWER MONITORING 1 SCRAM SOLENOIDS)

LIMITING CONDITIONS FOR OPERATION i

I 3.8.4.5 Two RPS electrical protection assemblies (EPAs) for each inservice PPS MG set or alternate source shall be OPERABLE.

APPLICABILITY: At all times.

ACTION:

a.

With one RPS electrical protection assembly for an inservice RPS MG set or altamate power supply inoperable, restore the inoperable EPA to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or remove the ar.sociated RPS MG set or alternato power supply from service, b.

WP

.a RPS electrical protection assemblies for an inservice RPS MG set or altcmate power supply inoperable, restore at least one EPA to OPERABLE status within 30 minutes or remove. the associated RPS MG set or alternate power supply

~ from service.

SURVEILLANCE FIEQUIREMENTS 4.8.4.5 The above specified RPS electrical protection essemblies shall be determined OPERABLE:

a.

At least once every 6 months by performance of a CHANNEL FUNCTIONAL TEST.

b.

At least once per 18 months by demonstrating the OPERABILITY of overvoltage, undervoltage and underfrequency protective instrumentation by performance of a CHANNEL CAllBRATION including imulated automatic actuation of the protective relays, tripping logic and output circuit breakers and verifying the following setpoints.

1.

Overvoltage Bus A:

s 128.8 volts AC Bus B:

s 130.0 volts AC 2.

Undervoltage Bus A:

2114.5 volts AC Bus B:

2115.1 volts AC 3.

UnderfreqJency a 57 Hz NINE MILE POINT - UNIT 2 3/4 8-33 Amendment No. //fE