ML20204F028

From kanterella
Jump to navigation Jump to search
Forwards Response to 860314 Request for Clarification of Three Open Items Re SEP Topic III-1.Radiographic Acceptability of Fuel Oil Transfer Pump Equivalent to ASTM-E99-55T
ML20204F028
Person / Time
Site: Yankee Rowe
Issue date: 07/28/1986
From: Papanic G
YANKEE ATOMIC ELECTRIC CO.
To: Mckenna E
Office of Nuclear Reactor Regulation
References
TASK-03-01, TASK-3-1, TASK-RR DCC-86-105, FYR-86-070, FYR-86-70, NUDOCS 8608040058
Download: ML20204F028 (3)


Text

%

Telephone (617) 872-8100 TWX 710380 7619 YANKEE ATOMIC ELECTRIC COMPANY MLb 1671 Worcester Road, Framingham, Massachusetts 01701 DCC 66-105

.h July 28, 1986 FYR 86-070 United States Nuclear Regulatory Commission Washington, DC 20555 Attention:

Ms. Eileen M. McKenna Project Manager, Project Directorate No.1 Division of PWR Licensing - A

References:

(a) License No. DPR-3 (Docket No. 50-29)

(b) Letter, YAEC to USNRC, dated September 26, 1984 (c) Letter, USNRC to YAEC, dated March 14, 1985 (d) Franklin Research Center, Technical Evaluation Report No. C5257-436, " Quality Group classification of Components and Systems," dated June 1, 1982

Subject:

SEP Topic III-1

Dear Ms. McKenna:

Yankee provided a response in Reference (b) to open items identified by the staff regarding SEP Topic III-1.

Through Reference (c), you requested clarification of three items in order for the staff to complete their review of this topic.

In response to these open items, the attached information is provided.

We believe we have now responded to all open items pertinent to SEP Topic III-1.

It is our understanding that a supplement to NUREG-0825 will be issued which will address the resolution of this topic. We trust that the information provided herein is satisfactory and look forward to receiving your final assossment.

Very truly yours, YANKEE ATOMIC ELECTRIC COMPANY l

0 L

x George panic, Jr.

Senior roject Eng neer - Licensing GP/hja Attachment 8608040058 860728 Of PDR ADOCK 05000029

'(

P PDR t

a ENCLOSURE 1 Response to Questions Contained in Enclosure 1 of NRC Letter (NYR 86-55), dated March 14 1986 Question 1:

In Attachment B for Item 18, the evaluation code is B1-2.

This l

would appear to be a typographical error; the correct code is requested.

Response

The Evaluation Code B1-2 for Item 18 of Attachment B is indeed a typographical error. The correct code is B1-1.

Ouestion 2:

For Item 49, Attachment B, no data is provided. It was not clear whether this item should have been deleted based on Item 17 of Attachment A or if information is missing.

Response

Item 49, Attachment B, " Fuel Oil Piping System (EDGS)," was not removed from the scope of SEP Topic III-1 based on Item 17 of Attachment A.

Item 17 of Attachment A deletes only the fuel oil transfer pumps. Item 49 of Attachment B has no data provided because:

a.

Reference (d), Table 5-1, " Review of Fracture Toughness

]

Requirements, YNPS," indicates "No" impact test required and material as "not applicable." No problem area is identified, b.

Reference (d), Table 4-1, " Classification of Structures, Systems, and Components, YNPS," and Table 4-2(c), " Quality Croup C Components," also do not indicate any " missing" l

information or unacceptable situations.

Therefore, since no information was missing and no unacceptable situations identified, a data line entry for Item 49 is not required.

l Question 3:

In the index of resolutions for Attachment B, radiography testing is noted as being specified per W65-NPP, YS-4652, and the Stone and Webster ECCS Backfit Specification. A brief description of the references is requested.

Response

W65-NPP, " Welding Procedure Specification for Nuclear Power i

Piping for Austenitic Stainless Steel Piping - Typo 304, Part II, Shop Fabrication Welding" with addendum adding Type 316, dated August 12, 1957. This document specifies that l

radiographic inspection be performed on all butt welds in the Main Coolant Piping System and other 2,000 pound or higher pressures lines, four-inch diameter, and larger. Radiographic acceptability is based on ASTM-E99-55T.

l

e ENCLOSURE 1 Response to Questions Contained in Enclosure 1 of NRC Letter (NYR 86-55). dated March 14 1986 (Continued)

YS-4652, " Specification for Shop and Field Fabrication Nuclear Piping for Revised Arrangement of Safety Injection and Shield Tank Cavity Water Piping," dated July 28, 1970. This document specifies that radiographic inspection be performed on all butt welds of all piping installed per this specification.

Radiographic acceptability based on Appendix bl USAS B31.7-1969.

Stone and Webster ECCS Backfit Specification This document contains a series of construction specifications and purchase orders which include YS-3, " Specification for Stainless Steel Valves for the Safety Injection System." This requires that radiographic inspection be performed on all ECCS valves. Radiographic acceptability is equivalent to ANSI B16.34-1973.