Notice of Violation from Insp on 880912-16.Violations Noted:Undersized Motor Contactor Installed in Motor Control Ctr Cubicle B1735 Not in Conformance to Technical Requirements Specified by Drawing E10,Rev 12
ML20204D696
Person / Time
Site: Pilgrim
Issue date: 10/14/1988
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20204D688 List:
References
50-293-88-32, NUDOCS 8810210200
Download: ML20204D696 (1)


Text

_ _ _ _ _.

r 8

i APPENDIX A NOTICE OF VIOLATION Boston Edison Company Docket No.53-203 i

Pilgrim Nuclear Power Station License No. DPR-35 i

As a result of the inspection conducted on September 12-16, !W8, and in accordance with the "General Statement of Policy and Procedure for NRC Enforce-l ment Actions," 10 CFR Part 2 Appendix C (Enforcement Policy) (1988), the following violations were identified:

1.

10 CFR 50 Appendix B Criterion VII requires that measures shall be established to assure that purchased equipment conform to procurement documents. These measures shall include provisions for examination of l

products upon delivery.

The Pilgrim Nuclear Power Station Quality Assurance Manudi Section 7 l

requires that a ret.eipt inspection of purchased equipment be performed dCCording to the approved prDCurement documents to assure equipment 3

conformance to specified technical aad QA requirements, i

Contrary to the above, on February 3,1988, NRC inspectors identified an undersized motor contactor in nalled in MCC cubicle B1735 not in l

conformance to the technical requirements specified by drawing E10, Revision 12.

This is a Severity Level IV vielation (Supplement I).

2.

10 CFR 50.49(f) requires that qualification of each component ba based on i

testing or experience with identical equipment or with similar equipment t

with a supporting analysis to show that the equipment to be qualified is j

acceptable.

l t

Contrary to the above, it was observed that on June 20-30, 1988 two

[

l i

unidentifiable wires were present in MOV MO-202-58 and as a result, j

subsequent licensee walkdowns identified environmentally unqualified wires 1

installed in MOVs 220-1, 1001-63, 1301-16, and 2301-4 located inside the i

dryvell.

This is Severity Level IV (Supplement I).

l BEco is not required to respond to these violations as the violations have been corrected and the corrective actions to prevent reoccurrence are i

complete. These actions were reviewed and found to be satisfactory by the NRC in the subject inspection period.

[

{