Text
5 4
h] Pennsylvania Power & Light Company Two North Ninth Street
- Allentown, PA 18101 + 215 / 77G5151 jf October 21, 1986 Mr. Stanley Lehman Water Quality Specialist Supervisor Bureau of Water Quality Management Pennsylvania Department of Environmental Resources 90 East Union Street, Second Floor Wilkes-Barre, PA 18701-3296 SUSQUEHANNA STEAM ELECTRIC STATION SEWAGE TREATMENT PLANT, NPDES PERMIT NO. 0047325 REACTIVATOR / CLARIFIER BLOWDOWN TREATMENT STATUS REPORT #7 CCN 741326 FILE R9-8A PLE-8803
Dear Mr. Lehman:
Attached for the Pennsylvania Department of Environmental Resources (Pa DER) review is a table listing total suspended solids (TSS) concentrations discharged from the Susquehanna SES sewage treatment plant (STP). As you are aware, blowdown from the reactivator / clarifier is treated at the STP.
The monthly average TSS limit of 30 mg/l was not exceeded in September even though there was one effluent analysis of 35 mg/l on September 26, 1986. The high TSS could have been attributed to sludge dewatering activities when the sample was collected. Table 1 lists TSS data collected at the STP during the period of September 23 through October 17, 1986.
The Pennsylvania Power & Light Company (PP&L) continues to review permanent treatment methods for the reactivator blowdown. Once a treatment method is selected, PP&L will contact the Pa DER for concurrence.
In the interim, however, PP&L will continue to direct this discharge to the STP with Pa DER
~
concurrence.
If you have any questions, please contact me at (215) 770-7889.
Respectfully yours, Q,
/^