W c'
TABLE 1 SUSQUEHANNA SES SEWAGE TREATMENT PLANT TOTAL SUSPENDED SOLIDS DATA Sample Collection Influent Effluent Percent (
Dates (mg/1)
(mg/1)
Reduction 9/23-24/86 920 20 98 9/25-26/86 1,260 35 97 9/30 & 10/1/86 270 19 93 10/2-3/86 740 14 98 10/7-8/86 330 23.5 93 10/9-10/86 500 19 96 10/14-15/86 232 24 90 10/16-17/86 350 22 94 Effluent limits 30 mg/l - monthly average, 60 mg/l - max Percent reduction limit at least 85%
8610270298 861021 ADOCK0500g7 PDR R