Submits Result of Generic Concerns Identified in NRC Info Notice 96-007 Re Slow Scram Insertion Times Caused by Pilot Valve Viton Internals
ML20203H825
Person / Time
Site: Oyster Creek
Issue date: 12/09/1997
From: Roche M
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
6730-97-2237, IEIN-96-007, IEIN-96-7, NUDOCS 9712190055
Download: ML20203H825 (1)


Text

-

y e

e j

GPU Nucteer,inc.

U S Route #9 South g

For ed ve NJ 08731-0388 181 609-971 4000 j

6730-97-2237 December 9, 1997 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington,DC 20555 Gentlemen:

Subject:

Oyster Creek Nuclear Generating Station (OCNGS)

Docket No. 50-219 Facilhy License No. DPR-16 Control Rod Drive Scram Solenoid Pilot Valve Augmented Testing Progra c.

GPU Nuclear letter to the NRC dated April 9,1996 (letter No. 6730-96-2091) described the augmented testing program implemented for scram solenoid pilot valves (SSPV) at OCNGS. This was a result of generic concerns identified in NRC Information Notice 96-07 regarding slow scram insertion times caused by the pilot valve Viton internals.

GPU Nuclear has installed qualified replacement Viton 515 AB diaphragms in the SSPVs at OCNGS.

The replacement diaphragms made from Viton 515 AB have demonstrated satisfactory performance during qualification testing and post-installation augmented surveillance testing, and are expected to correct the problem associated with increased control rod drive scram times caused by sticking diaphragms in the SSPVs. This qualification is described in General Electric Company Report GE NEDC-32365P-Addendum 4. Accordingly, the augmented testing of these valves at OCNGS has been discontinued. Control rod drive operability will continue to be demonstrated in accordance with existing OCNGS Technical SpecificaNon Section 3.2 requirements.

I O If any additional information is required, please contact Mr. David J. Diste!, Regulatory Affairs, at (20l) 316-7955.

Very truly yours,

%L06%

NY MichaelB. Roche Vice President and Director, Oyster Creek MBR/DJD c: : Administrator, US'NRC Region I.

OCNGS NRC Senior Resident Inspector OCNGSNRC SeniorProjectManager j jgg j] gj]lll 9712190055 971209 ~