1
(~ x g Duk3 Energy Corporation fg$0 n
od York. SC 29745 Gary R. Peterson (803) 8314251 om gyy (803) 831-3426 Mx February 9, 1999 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.
20555
Subject:
Catawba Nuclear Station, Unit 2 Docket No. 50-414 Special Report - Steam Generator Tube Inspection Please find attached the results of the rt'am generator tube e
inspection conducted in the Fall of 1998 during the Unit 2 End of Cycle 9 refueling outage.
This information is submitted in accordance with Catawba Nuclear Station Technical Specification 5.6.8 b.
The following number of tubes were inspected:
Tubes Inspected Tubes Inspected Steam Generator Full Length Part Length A
2501 133 B
2317 178 C
2273 182 D
2485 179 Attachments 1, 2,
3, and 4 identify the tubes with imperfections in steam generators A, B,
C, and D, respectively.
The location and size of the imperfections is also provided.
A ental of nine tubes were removed from service by plucciag.
Attachments 5, 6,
7, and 8 identify the specific tubes plugged in steam 7 werators A,
B, C,
and D, respectively.
If there are any questions on this information, please contact G.A. Copp at (803) 831-3622.
[
'[
m Gary R.
Pete son Attachments d
j 0f 9902160167 990209 '~
DR p
ADOCK 05000414 PDR;_
l
7..
- t /-
p;--
i U.S. Nuclor.r Regulatory Commission f
i Febru2ry 9, 1999-l Page 2 l
i i
xc:. Mr. P.S. Tam, NRC Project Manager l
Office of Nuclear Reactor Regulation
?
l Mr. L.A..Reyes, Regional Administrator U.S. Nuclear Regulatory Commission,-Region II l
I l
Mr. D.J. Roberts, Senior Resident Inspector l
Catawba Nuclear Station l
I l
E I
l 5
i l
l I
i l
l l
)
t l
l 1
i I
l I
l l
l l '
I l
t t
i 4
4 Y
} '
i 1
4 5
L j
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Speci'al Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 1 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 1
1 09/98 Bobbin HNC 11 3.03 07H
+14.34 1
3 09/98 Bobbin HNI 1.05 02H
+18.00 1 17 09/98 Bobbin HNC 14 0.84 11C
+7.87 1 25 09/98 Bobbin HNC 13 0.57 19C
+1.63 1 29 09/98 Bobbin ODI 14 0.69 04H
+18.27 1 33 09/98 Bobbin ODI 8
0.84 11C
+14.22 1 41 09/99 Bobbin ODI 14 0.45 16C
+29.05 1 48 09/98 Bobbin HNC 4
0.73 16C
+13.51 1 49 09/98 Bobbin HNC 14 0.62 11C
+33.04 09/98 Bobbin HNC 17 0.59 06H
+33.42 1 64 09/98 Bobbin HNI 0.59 02H
+11.00 1 66 09/98 Bobbin ODI 1
0.713 13C
+1.74 1 67 09/98 Bobbin ADI 0.59 12C
+29.09 09/98 Bobbin HNI 1.L5 14C
+16.41 1 82 09/98 Bobbin ODI 12 0.60 TSC
+0.67 1 88 09/98 Bobbin NQI 0.56 16C
+21.92 1 92 09/98 Bobbin HNI 3.25 16C
+28.90 1 93 09/98 Bobbin HNI 1.37 04H
+6.26 09/98 Bobbin HNI 1.55 04H
+7.66 1 105 09/98 Bobbin ADI 1.55 11C
+34.62 09/98 Bobbin HNC 10 1.37 11C
+36.35 1 108 09/98 Bobbin HNI 1.10 07H
+11.73 1
09/98 Bobbin HNI 1.52 03H
+17.61 1 113 09/98 Bobbin HNI 1.79 16C
+4.79 2
2 09/98 Bobbin HNI 0.69 12C
+2.65 to
+9.64 2
3 09/98 Bobbin NOI 0.42 12C
+2.70 to
+8.46 2
8 09/98 Bobbin ODI 12 1.26 16C
+8.73 09/98 C/L Special Interest VOL 1.02 16C
+0.74 2 14 09/98 Bobbin HNC 6
1.08 11C
+7.22 2 18 09/98 Bobbin HNI 1.37 16C
+31.72 09/98 C/L Special Interest VOL 1.14 16C
+31.45 2 25 09/98 Bobbin HNI 0.36 TSC
+3.76 2 37 09/98 Bobbin HNI 0.69 12C
+0.66 to
+7.13 2 42 09/98 Bobbin HNI 3.11 04H
+14.86 2 43 09/98 Bobbin HNC 9
0.57 03H
+18.91 2 50 09/98 Bobbin ADI 1.44 01H
+24.99 2 61 09/98 Bobbin ODI 6
0.42 11C
+37.71 09/98 Bobbin ODI 7
0.41 11C
+37.74 2 66 09/98 Bobbin HNI 1.17 18C
+27.38 2 73 09/98 Bobbin HNI 2.91 O1H
+15.43 2 75 09/98 Bobbin ODI 19 0.35 16C
+30.66 09/98 C/L Special Interest VOL 0.52 16C
+30.66 2 77 09/98 Bobbin ODI 19 0.34 13C
+30.00 2 Gd 09/98 Bobbin ODI 5
0.24 18C
+7.11 2 89 09/98 Bobbin HNI 1.92 13C
+17.45 2 101 09/98 Bobbin HNI 0.61 10C
+11.00 09/98 Bobbin HNI 1.66 10C
+7.55 2 109 09/98 Bobbin HNI 1.83 02H
+20.20 2 114 09/98 Bobbin HNI 0.58 07H
+12.14 3 14 09/98 Bobbin HNC 6
1.76 03H
+30.50 3 31 09/98 Bobbin HNI 0.35 04H
+15.58 3 33 09/98 Bobbin ADI 2.70 12C
+4.36 i
09/98 C/L Special Interest VOL 0.40 12C
+4.64 i
3 67 09/98 Bobbin HNI 0.29 13C
+31.38 09/98 Bobbin ODI 3
0.95 17C
+5.59
)
3 74 09/98 Bobbin HNI 1.13 17C
+5.05 3 78 L9/38 Bobbin ODI 23 0.48 18C
+2.82 3 83 09/98 Bobbin HNI 2.50 10C
+39.45 09/98 C/L Special Interest VOL 1.27 09C
-7.02 3 103 09/98 Bobbin HNI 0.33 10C
+17.39 09/98 Bobbin HNI 0.72 13C
+40.41 3 108 09/98 Bobbin HNI 0.44 12C
+7.24 4 10 09/98 Bobbin ODI 20 0.42 05H
+28.35 4 32 09/98 Bobbin HNC 15 0.67 02H
+13.22 4 51 09/98 Bobbin ADI 2.58 05H
+15.92
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 2 ATTACHMENT #1 INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 4 53 09/98 Bobbin HNC 24 0.32 O1H
+15.13 4 55 09/98 Bobbin HNC 16 1.31 02H
+26.24 4 72 09/98 Bobbin HNI 1.11 12C
+32.84 4 78 09/98 Bobbin HNI 0.95 02H
+10.74 4 82 09/98 Bobbin HNI 1,46 18C
+8.81 09/98 Bobbin HNI 1.59 13C
+6.51 4 85 09/98 Bobbin HNI 0.52 07H
+1.33 09/98 Bobbin HNI 2.11 07H
+15.77 09/98 H/L Special Interest VOL 2.48 07H
+15.77 4 106 09/98 Bobbin HNI 3.85 12C
+7.73 i
09/98 Bobbin HNI 3.88 13C
+31.86 i
09/98 C/L Special Interest VOL 1.08 12C
+7.79 4 111 09/98 Bobbin HNC 8
1.29 O1H
+23.46 1
09/98 H/L Special Interest VOL 0.71 02H
-4.51 5 34 09/98 Bobbin HNC 11 0.78 13C
+7.38 9
09/98 Bobbin HNC 20 0.63 TSC
+4.08 09/98 C/L Special Interest VOL 0.79 13C
+7.42 09/98 C/L Special Interest VOL 0.80 TSC
+3.82 5 37 09/98 Bobbin HNC 28 4.37 12C
+11.99 5 58 09/98 Bobbin UNI 0.32 O1H
+8.17 09/98 Bobbin ODI 12 2.23 12C
+1.85 1
09/98 C/L Special Interest VOL 2.43 12C
+1.58 5 60 09/98 Bobbin HNI 0.45 03H
+4.97 5 62 09/98 Bobbin HNI 1.31 13C
+35.30 l
5 63 09/98 Bobbin HNI 3.02 TSH
+1.94 09/98 H/L Tubesheet VOL 1.36 TSH
+1.55 5 84 09/98 Bobbin HNI 1.01 04H
+5.13 5 86 09/98 Bobbin HNI 0.62 02H
+31.19 5 94 09/98 Bobbin HNI 0.81 10C
+21.95 5 99 09/98 Bobbin HNI 1.31 10C
+27.80 5 108 09/98 Bobbin HNI 0.74 07H
+34.99 6
2 09/98 Bobbin HNC 9
1.56 16C
+8.78 09/98 Bobbin ODI 14 0.95 19C
+5.17 09/98 C/L Special Interest VOL 1.42 16C
+8.81 l
6 3 09/98 Bobbin HNI 2.05 10C
+15.47 I
09/98 Bobbin HNI 4.22 O1H
+24.19 09/98 Bobbin HNC 16 1.69 18C
+2.64 09/98 C/L Special Interest VOL 1.18 18C
+2.17 6
4 09/98 Bobbin HNC 22 0.91 14C
+7.33 6
5 09/9B Bobbin HNC 14 1.65 15C
+4.26 09/98 C/L Special Interest VOL 0.96 15C
+4.24 6 13 09/98 Bobbin NQI 0.29 02H
-1.00 6 24 09/98 Bobbin ODI 15 0.39 02H
+31.13 6 35 09/98 Bobbin HNC 14 1.23 06H
+7.94 09/98 Bobbin HNC 14 1.29 05H
+38.40 09/98 Bobbin HNC 15 0.96 06H
+10.34 09/98 Bobbin HNC 19 1.33 06H
+28.93 09/98 Bobbin ODI.
1 0.88 06H
+16.75 09/98 H/L Special Interest VOL 1,76 06H
+18.04 09/98 H/L Special Interest VOL 2.48 06H
+8.36 6 36 09/98 Bobbin HNC 15 0.51 15C
+13.05 6 37 09/98 Bobbin HNC 26 0.88 O1H
+4.16 I
6 40 09/98 Bobbin HNC 12 1.36 10C
+38.91 09/98 Bobbin ODI 9
2.27 10C
+16.65 09/98 C/L Special Interest VOL 0.95 10C
+38.65 09/98 C/L Special Interest VOL 1.38 10C
+16.69 6 53 09/98 Bobbin HNC 4
0.91 02H
+33.77 09/98 Bobbin ODI 13 1.14 19C
+1.36 i
6 54 09/98 Bobbin HNI 0.35 12C
+13.12 09/98 Bobbin HNC 10 2.24 05H
+3.57 6 62 09/98 Bobbin HNI 1.41 04H
+21.59 09/98 Bobbin ODI 12 0.75 03H
+1.88 6 75 09/98 Bobbin HNI 2.52 11C
+10.04 09/98 Bobbin HNC 6
1.24 19C
+6.77 09/98 C/L Special Interest VOL 1.07 19C
+6.73
r '-
]
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12
)
Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubenheet,MRPC ATTACHM2NT #1 INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA I
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 6 77 09/98 Bobbin HNI 0.37 11C
+32.47 6 81 09/98 Bobbin HNI 3.42 11C
+18.65 6 91 09/98 Bobbin HNC 5
1.42 04H
+14.15 09/98 Bobbin HNC 15 0.51 10C
+19.B0 6 99 09/98 Bobbin ADI 1.94 12C
+20.49 i
09/98 Bobbin HNI 0.57 16C
-1.33 6 104 09/98 Bobbin HNI 1.57 07H
+14.66 6 114 09/98 Bobbin HNI 1.53 10C
+36.96 7 14 09/98 Bobbin HNC 12 0.62 TSC
+5.74 7 15 09/98 Bobbin HNC 10 1.33 TSC
+4.92 7 26 09/98 Bobbin HNC 13 1.63 03H
+9.80 09/98 Bobbin ODI B
1.12 TSC
+3.72 1
09/98 H/L Special Interest VOL 2.90 03H
+9.80 7 31 09/98 Bobbin HNC 19 0.80 04H
+9.20 09/98 Bobbin ODI 15 0.75 10C
+38.13 1
I 09/98 H/L Special Interest VOL 0.82 04H
+9.27 7 40 09/98 Bobbin HNI 0.40 18C
+12.95 09/98 Bobbin NOI 0.30 19C
+4.21 l
09/98 Bobbin HNC 34 0.65 17C
+13.22 09/98 C/L Special Interest VOL 0.45 18C
+12.76
)
7 43 09/98 Bobbin
.HNC 11 1.29 12C
+15.06 i
09/98 C/L Special Interest VOL 0.80 12C
+15.29 7 51 09/98 Bobbin ODI 14 0.61 19C
+2.48 7 56 09/98 Bobbin HNI 1.72 05H
+5.04 7 61 09/98 Bobbin HNC 13 0.71 06H
+20.27
[
09/98 Bobbin HNC 13 0.74 06H
+15.78 7 65 09/98 Bobbin HNC 4
0.83 19C
+1.90 7 67 09/98 Bobbin ODI 12 0.46 18C
+10.24 7 69 09/98 Bobbin HNC 20 0.71 TSH
+6.05 l
09/98 Bobbin HNC 21 1.47 03H
+4.39 7 70 09/98 Bobbin HNC 11 0.85 16C
+12.02 t
09/98 Bobbin HNC 14 0.83 17C
+6.65 7 90 09/98 Bobbin HNC 22 0.54 10C
+31.80 09/98 Bobbin HNC 33 0.97 07H
+33.29 l
7 93 09/98 Bobbin HNC 14 1.08 01H
+6.76 i
09/98 H/L Special Interest VOL 0.90 O1H
+6.76 7 94 09/98 Bobbin HNC 6
0.70 O1H
+20.41 7 97 09/98 Bobbin HNI 0.43 11C
+9.33 09/98 Bobbin ODI 17 0.53 09C
+7.92 7 104 09/98 Bobbin HNC 20 0.46 O1H
+10.40 7 106 09/98 Bobbin HNI 1.79 06H
+12.26 7 108 09/98 Bobbin HNI 0.28 12C
+35.24 7 113 09/98 Bobbin HNC 9
0.98 TSC
+3.93 8
3 09/98 Bobbin HNC 4
0.70 07H
+11.61 8 12 09/98 Bobbin ODI 4
0.71 10C
+29.73 8 16 09/98 Bobbin HNC 14 1.36 O1H
+19.34 09/98 Bobbin HNC 21 0.38 10C
+28.53 09/98 Bobbin ODI 3
0.74 10C
+23.96 i
09/98 Bobbin ODI 18 0.33 10C
+23.04 09/98 Bobbin ODI 24 0.30 07H
+27.26 09/98 H/L Special Interest VOL 3.72 02H
-9.73 8 19 09/98 Bobbin HNC 5
2.09 04H
+30.99 8 24 09/98 Bobbin HNC 10 1.45 07H 425.88 8 35 09/98 Bobbin HNC 21 0.42 19C
+8.22 09/98 Bobbin HNC 27 0.32 19C
+7.28 8 38 09/98 Bobbin HNI 0.50 02H
+14.98 8 39 09/98 Bobbin HNI 1.89 13C
+1.72 8 44 09/98 Bobbin HNC 10 0.43 14C
+4.65 09/98 Bobbin HNC 15 0.82 02H
+25.91 09/98 Bobbin HNC 16 0.28 15C
+8.94 09/98 Bobbin ODI 25 0.28 15C
+4.12 09/98 C/L Special Interest VOL 0.12 15C
+8.60 C2/98 C/L Special Interest VOL 0.13 15C
+3.85 8 45 09/98 Bobbin HNI 1.18 15C
+14.93 09/98 Bobbin HNI 2.35 05H
+34.70
i FTZ TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 4 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin HNC 8
0.44 15C
+2.36 09/98 Bobbin HNC 10 0.50 16C
+11.23 8 46 09/98 Bobbin HNC 7
1.27 05H
+37.03 09/98 Bobbin HNC 12 1.42 18C
+4.19 I
09/98 C/L Special Interest VOL 1.40 18C
+4.10 8 47 09/98 Bobbin HNC 10 1.56 06H
+2.99 8 52 09/98 Bobbin HNI 0.43 03H
+4.22 8 63 09/98 Bobbin HNC 15 1.31 11C
+33.18 8 79 09/98 Bobbin HNC 14 1.19 15C
+15.63 8 87 09/98 Bobbin HNC 17 1.24 12C
+26.59 09/98 C/L Special Interest VOL 1.29 12C
+26.59 8 91 09/98 Bobbin HNI 1.99 16C
+10.80 8 96 09/98 Bobbin NQI 0.20 15C
+10.56 8 102 09/98 Bobbin HNI 1.65 O1H
+7.51 8 108 09/98 Bobbin HNC 11 1.43 11C
+9.14 09/98 Bobbin HNC 12 0.94 11C
+17.12 09/98 Bobbin HNC 12 1.34 11C
+14.65 8 109 09/98 Bobbin HNI 7.34 09C
+7.11 09/98 Bobbin NQI 0.27 10C
+30.52 8 111 09/98 Bobbin NQI 0.21 10C
+36.53 09/98 Bobbin ODI 16 0.17 10C
+34.74 8 112 09/98 Bobbin ODI 7
0.82 11C
+35.74 8 113 09/98 Bobbin NQI 0.30 07H
+34.83 09/98 Bobbin NOI 0.57 07H
+39.59 09/98 Bobbin NOI 0.77 07H
+24.23 09/98 Bobbin HNC 14 1.15 10C
+24.12 09/98 Bobbin HNC 25 0.83 07H
+26.57 9
6 09/98 Bobbin HNC 4
0.66 O1H
+19.63 9 11 09/98 Bobbin HNC 19 0.79 13C
+4.92 9 15 09/98 Bobbin HNC 3
2.03 17C
+11.42 9 21 09/98 Bobbin HNI 0.64 13C
+23.13 09/98 Bobbin NQI 0.83 13C
+19.41 09/98 C/L Special Interest VOL 0.69 13C
+19.46 9 46 09/98 Bobbin HNI 0.82 16C
+4.24 9 70 09/98 Bobbin HNI 2.02 04H
+6.05 9 81 09/98 Bobbin HNC 14 1.29 18C
+11.20 9 89 09/98 Bobbin HNI 0.66 13C
+19.71 9 93 09/98 Bobbin HNI 1.02 14C
+13.74 9 96 09/98 Bobbin HNC 5
0.75 04H
+38.26 9 99 09/98 Bobbin HNC 14 1.88 08H
+5.29 9 106 09/98 Bobbin HNC 21 2.09 11C
+15.72 09/98 C/L Special Interest VOL 2.49 11C
+15.73 10 12 09/98 Bobbin HNC 23 1.04 07H
+7.65 i
10 14 09/98 Bobbin HNC 8
3.25 02H
+27.60 1
09/98 Bobbin HNI 4.43 03H
+5.76 to
+9.58 10 17 09/98 Bobbin HNC 16 1.44 11C
+21.97 09/98 C/L Special Interest VOL 1.18 11C
+22.28 10 34 09/98 Bobbin ODI 10 1.49 07H
+31.47 10 50 09/98 Bobbin HNI 0.34 04H
+38.04 09/98 Bobbin HNI 2.19 07H
+21.58 10 59 09/98 Bobbin HNC 12 2.38 13C
+32.36 09/98 Bobbin HNC 14 1.37 16C
+3.03 10 61 09/98 Bobbin HNC 25 0.67 01H
+11.71 10 70 09/98 Bobbin HNC 8
0.93 03H
+12.42 09/98 Bobbin HNC 11 0.72 03H
+9.14 10 77 09/98 Bobbin HNC 22 0.75 07H
+33.58 09/98 H/L Special Interest VOL 1.30 08H
-12.42 10 79 09/98 Bobbin HNC 19 0.98 05H
+38.49 10 82 09/98 Bobbin HNC 14 1.80 15C
+15.14 09/98 Bobbin HNC 20 0.57 13C
+11.45 09/98 C/L Special Interest VOL 1.33 ISC
+15.18 10 88 09/98 Bobbin HNC 24 0.37 11C
+7.41 10 89 09/98 Bobbin HNC 9
0.41 13C
+22.96 10 91 09/98 Bobbin HNC 13 0.52 10C
+41.97 09/98 Bobbin HNC 23 0.61 13C
+17.04
m
~.... _
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:13 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 5 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 10 95 09/98 Bobbin HNC 30 0.49 07H
+29.48 10 97 09/98 Bobbin HNI 0.40 13C
+32.23 09/98 Bobbin ODI 32 0.62 15C
+13.36 10 108 09/98 Bobbin ADI 0.73 07H
+39.47 09/98 Bobbin ODI 31 0.27 10C
+40.62 10 110 09/98 Bobbin ADI 2.39 06H
+30.20 10 111 09/98 Bobbin HNI 0.56 10C
+34.24 09/98 Bobbin ODI 3
0.37 07H
+33.93 09/98 Bobbin ODI 18 0.23 10C
+34.66 09/98 H/L Special Interest VOL 1.51 08H
-11.85 10 112 09/98 Bobbin ODI 1
1.19 07H
+34.22 10 113 09/98 Bobbin HNI 0.67 10C
+43.66 11 2 09/98 Bobbin ODI 5
0.54 05H
+36.75 11 4 09/98 Bobbin HNC 25 0.46 15C
+4.55 11 5 09/98 Bobbin HNI 0.40 07H
+15.83 09/98 Bobbin HNC 19 0.60 10C
+19.29 11 8 09/98 Bobbin ODI 9
0.42 O1H
+22.29 11 9 09/98 Bobbin HNC 10 1.47 17C
+15.11 11 12 09/98 Bobbin ODI 6
1.36 10C
+15.73 09/98 C/L Special Interest VOL 0.57 10C
+15.19 11 16 09/98 Bobbin HNI 0.23 10C
+30.08 09/98 Bobbin HNC 7
0.67 07H
+27.98 09/98 Bobbin HNC 11 0.48 10C
+31.29 11 28 09/98 Bobbin HNI 2.36 TSC
+5.61 11 30 09/98 Bobbin HNC 6
1.85 14C
+15.76 09/98 Bobbin HNC 19 1.37 14C
+13.54 09/98 C/L Special Interest VOL 0.51 14C
+15.75 09/98 C/L Special Interest VOL 1.30 14C
+13.79 11 35 09/98 Bobbin ODI 2
0.46 05H
+34.99 11 51 09/98 Bobbin HNI 3.41 02H
+25.31 11 54 09/98 Bobbin HNC 7
0.81 15C
+3.21 11 57 09/98 Bobbin NQI 0.27 15C
+14.73 11 65 09/98 Bobbin HNC 13 0.64 13C
+14.69 09/98 Bobbin HNC 14 0.69 03H
+5.98 11 80 09/98 Bobbin NQI 4.42 08H
+2.25 11 87 09/98 Bobbin HNC 15 0.37 02H
+10.13 09/98 Bobbin HNC 15 0.63 17C
+3.54 11 88 09/98 Bobbin HNI 0.23 13C
+22.20 11 107 09/98 Bobbin HNI 0.20 10C
+13.11 09/98 Bobbin HNC 23 0.31 07H
+36.11 09/98 Bobbin ODI 29 0.47 07H
+38.68 11 110 09/98 Bobbin NQI 0.12 07H
+33.51 09/98 Bobbin HNC 19 0.33 10C
+30.56 11 111 09/98 Bobbin HNC 9
0.83 10C
+39.51 11 112 09/98 Bobbin ODI 22 1.35 07H
+44.25 11 113 09/98 Bobbin HNC 7
0.64 10C
+42.48 12 10 09/98 Bobbin HNC 14 1.69 O1H
+24.78 12 13 09/98 Bobbin HNI 5.42 TSC
+4.65 09/98 Ch; Special Interest VOL 1.59 TSC
+4.32 12 19 09/40 eobbin HNC 18 0.97 10C
+24.98 09/98 Bobbin HNC 19 0.50 07H
+23.50 le 23 09/98 Bobbin NOI 0.59 07H
+44.11 09/98 Bobbin HNC 16 1.10 10C
+22.96 09/98 Bobbin HNC 20 0.43 07H
+26.32 l
09/98 Bobbin HNC 21 0.39 07H
+25.60 09/98 Bobbin HNC 24 0.40 07H
+23.78 09/98 Bobbin HNC 27 0.76 10C
+26.94 09/98 Bobbin ODI 14 0.41 07H
+24.93 09/98 Bobbin ODI 14 0.80 07H
+39.85 i
12 24 09/98 Bobbin HNI 1.78 02H
+19.00 l
12 45 09/98 Bobbin ODI 16 0.35 06H
+39.11 12 52 09/98 Bobbin HNC 3
0.78 10C
+31.26 09/98 Bobbin HNC 8
1.11 10C
+23.24 12 55 09/98 Bobbin HNC 6
0.57 11C
+15.67 09/98 C/L Special Interest VOL 0.39 11C
+15.67
--..- ~ -
- ~..
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 6 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 12 89 09/98 Bobbin HNC 21 1.23 07H
+14.48 12 90 09/98 Bobbin HNI 2.90 06H
+8.64 09/98 Bobbin HNI 3.59 07H
+41.52 12 108 09/98 Bobbin HNI 0.94 05H
+28.28 13 4 09/98 Bobbin HNI 1.54 02H
+20.32 13 7 09/98 Bobbin HNC 6
0.38 12C
+2.29 13 11 09/98 Bobbin HNC 16 1.16 18C
+4.93 13 14 09/98 Bobbin HNC 14 0.61 13C
+38.63 13 21 09/98 Bobbin HNC 9
1.59 07H
+36.11 13 29 09/98 Bobbin HNC 14 0.56 07H
+11.24 09/98 Bcitin h iC 33 0.50 07H
+10.21 13 33 09/98 B icin HNI 2.75 07H
+18.99 13 34 09/98 Bobbin HNC 3
1.99 19C
+4.43 09/98 Bobbin HNC 22 1.26 12C
+18.98 09/98 Bobbin HNC 25 0.62 13C
+5.16 09/98 C/L Special Interest VOL 0.31 19C
+4.43 13 43 09/98 Bobbin HNI 1.34 05H
+33.84 13 47 09/98 Bobbin HNC 17 1.15 19C
+5.01 13 76 09/98 Bobbin HNC 7
0.98 07H
+8.34 09/98 Bobbin HNC 11 1.06 11C
+35.59 09/98 Bobbin HNC 13 0.70 07H
+10.27 13 87 09/98 Bobbin HNI 0.46 06H
+25.89 09/98 Bobbin HNI 0.94 06H
+27.51 09/98 Bobbin HNC 12 0.92 07H
+7.37 09/98 Bobbin HNC 21 1.07 07H
+21.87 09/98 H/L Special Interest VOL 1.19 07H
+7.37 09/98 H/L Special Interest VOL 1.61 07H
+21.86 13 93 09/98 Bobbin ODI 12 0.43 04H
-0.02 13 103 09/98 Bobbin ADI 0.66 07H
+40.47 G9/98 Bobbin HNI 1.73 06H
+35.03 09/98 Bobbin HNC 24 0.81 06H
+33.87 09/98 H/L Special Interest VOL 0.53 08H
-6.79 13 107 09/98 Bobbin HNI 0.32 10C
+21.61 14 16 09/98 Bobbin ODI 3
1.14 10C
+39.72 09/98 Bobbin HNI 0.23 07H
+37.41 to
+41.11 14 17 09/98 Bobbin HNI 0.21 07H
+32.76 09/98 Bobbin HNI 2.11 03H
+23.97 09/98 Bobbin ODI 10 0.39 11C
+19.99 14 25 09/98 Bobbin HNC 13 1.05 15C
+J. 57 09/98 Bobbin HNC 19 2.07 17C
<1.06 09/98 Bobbin HNC 26 1.07 16C
+1.39 09/98 Bobbin HNC 28 1.09 13C
+11.76 09/98 Bobbin ODI 6
0.92 12C
+5.98 09/98 C/L Special Interest VOL 0.57 15C
+1.57 09/98 C/L Special Interest VOL 0.82 16C
+1.39 09/98 C/L Special Interest VOL 0.84 17C
+1.06 14 28 09/98 Bobbin HNI 1.17 15C
+15.02 09/98 Bobbin HNC 6
0.78 10C
+17.76 14 29 09/98 Bobbin HNC 6
1.76 06H
+21.80 09/98 H/L Special Interest VOL 0.66 06H
+21.02 14 33 09/98 Bobbin HNC 23 0.40 10C
+40.98 14 44 09/98 Bobbin OD1 20 0.28 06H
+35.07 14 49 09/98 Bobbin HNI 0.25 10C
+32.50 09/98 Bobbin ODI 14 1.02 TSC
+3.01 14 83 09/98 Bobbin HNC 10 1.27 03H
+13.80 14 97 09/98 Bobbin HNC 9
1.50 12C
+31.39 09/98 Bobbin HNC 17 1.03 12C
+37.57 14 100 09/98 Bobbin HNI 5.13 AV4
+6.38 14 103 09/98 Bobbin HNI 2.84 12C
+15.43 09/98 C/L Special Interest VOL 0.99 12C
+13.42 14 105 09/98 Bobbin HNI 2.38 06H
+38.44 14 107 09/98 Bobbin HNC 10 0.52 07H
+37.82 14 108 09/98 Bobbin HNC 14 0.93 06H
+6.25 14 110 09/98 Bobbin ODI 17 0.30 07H
+40.44 14 111 09/98 Bobbin HNI 0.44 07H
+38.04
. ~ _ -. - -
. =. - -
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 7 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin HNC 14 0.36 07H
+38.47 09/98 Bobbin ODI 2
0.68 10C
+34.84 09/98 Bobbin ODI 19 0.19 10C
+22.58 14 112 09/98 Bobbin ODI 10 0.68 06H
+23.90 15 3 09/98 Bobbin HNI 0.33 07H
+15.19 09/98 Bobbin ODI 4
0.43 07H
+16.27 15 7 09/98 Bobbin HNC 13 0.47 06H
+22.69 15 17 09/98 Bobbin HNC 1
0.87 10C
+27.86 09/98 Bobbin HNC 10 0.38 10C
+26.73 15 18 09/98 Bobbin HNC 12 0.71 07H
+31.76 09/98 Bobbin HNC 14 0.38 10C
+35.39 15 22 09/98 Bobbin HNC 13 0.44 11C
+19.76 15 23 09/98 Bobbin HNC 20 0.64 10C
+23.85 09/98 Bobbin ODI 14 0.24 10C
+38.74 15 24 09/98 Bobbin HNI 0.20 07H
+27.70 09/98 Bobbin HNI 0.38 TSC
+5.29 09/98 Bobbin HNI 0.52 10C
+42.97 09/98 Bobbin NOI 0.21 10C
+40.39 09/98 Bobbin HNC 8
0.82 10C
+5.32 i
09/98 Bobbin HNC 9
1.17 07H
+23.07 09/98 Bobbin HNC 14 0.33 07H
+26.67 09/98 Bobbin ODI 8
0.76 07H
+22.52 15 25 09/98 Bobbin ODI 17 0.90 17C
+16.54 15 27 09/98 Bobbin HNI 1.75 TSC
+3.27 15 30 09/98 Bobbin HNI 0.43 10C
+41.02
'r 09/98 Bobbin HNC 11 0.39 07H
+39.13 15 31 09/98 Bobbin HNC 5
1.35 06H
+36.73 15 38 09/98 Bobbin HNC 14 0.68 10C
+43.74 15 49 09/98 Bobbin HNC 2
0.72 02H
+17.65 1
15 51 09/98 Bobbin HNC 29 0.28 07H
+30.61 15 53 09/98 Bobbin HNC 13 0.47 06H
+40.66 15 55 09/98 Bobbin HNC 14 1.44 17C
+8.99 15 56 09/98 Bobbin HNI 0.30 06H
+4.23 09/98 H/L Special Interest VOL 0.65 06H
+5.05 15 57 09/98 Bobbin HNC 5
0.66 18C
+9.72 09/98 C/L Special Interest VOL 0.87 18C
+9.73 15 65 09/98 Bobbin HNI 0.60 10C
+14.60 09/98 Bobbin HNC 7
0.57 10C
+15.40 09/98 Bobbin HNC 10 0.54 10C
+16.70 15 72 09/98 Bobbin ODI 18 1.18 03H
+22.02 15 74 09/98 Bobbin HNC 1
1.00 16C
+10.65 15 75 09/98 Bobbin HNC 10 1.00 16C
+13.97 15 85 09/98 Bobbin HNC 11 0.66 11C
+27.97 09/98 C/L Special Interest VOL 0.61 11C
+27.86 15 87 09/98 Bobbin HNC 22 0.71 13C
+27.13 15 97 09/98 Bobbin HNI 0.30 07H
+39.22 09/98 Bobbin HNI 0.31 12C
+29.91 09/98 Bobbin HNC 4
1.07 07H
+40.05 09/98 Bobbin ODI 2
0.41 03H
+24.46 09/98 H/L Special Interest VOL 0.47 04H
-11.54 15 107 09/98 Bobbin HNI 0.30 11C
+35.77 09/98 Bobbin NOI O.50 08H
+1.10 09/98 Bobbin HNC 23 0.25 06.I
+32.11 15 108 09/98 Bobbin HNC 7
1.07 07H
+37.98 15 109 09/98 Bobbin HNC 12 0.67 11C
+27.86 09/98 Bobbin HNC 14 1.58 14C
+10.52 09/98 Bobbin ODI 10 0.51 OBH
+1.12 09/98 Bobbin ODI 14 0.92 07H
+18.98 15 110 09/98 Bobbin HNI 2.28 OBH
+11.13 16 4 09/98 Bobbin HNI 1.96 07H
+28.87 09/98 Bobbin HNC 12 0.61 11C
+29.35 16 6 09/98 Bobbin ODI 3
0.60 10C
+43.66 16 16 09/98 Bobbin ODI 11 0.50 07H
+41.94 16 17 09/98 Bobbin HNC 15 0.41 10C
+24.80 09/98 Bobbin ODI 10 0.42 10C
+30.12
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 L
Catawba Nuclear Station - Unit Two i
S/G A t
09/98 RFO l
Bobbin,C/L'Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION f
i 09/98 Bobbin-ODI 21 0.27 10C
+27.01
~
16 23 09/98 Bobbin HNC 18 1.05 13C
+14.98 16 26 09/98 Bobbin HNC 8
0.93 17C
+16.51 09/98 Bobbin-ODI 11 0.68 16C
+1.86 16 46 09/98 Bobbin NQI 0.33 10C
+42.68 16 54 09/98 Bobbin ODI 28 0.59 04H
+25.79 16 60 09/98 Bobbin HNI 1.02 13C
+20.10 i
09/98 Bobbin HNC 15 0.85 13C
+16.41 09/98 Bobbin ODI 10 0.58 13C
+13.65 j
16 61 09/98 Bobbin HNC 13 1.78 17C
+4.49 16 62 09/98 Bobbin HNI 1.45 O1H
+4.20 l
16 64 09/98 Bobbin HNC 4
1.59 18C
+14.40 09/98 Bobbin ODI 17 0.44 10C
+28.41 09/98 C/L Special Interest VOL 1.13 18C
+14.50 16 77 09/98 Bobbin HNC 4
0.75 16C
+11.25 i
16 82 09/98 Bobbin ODI 1
1.15 O1H
+12.88 16 102 09/98 Bobbin ADI 1.31 13C
+9.31 i
09/98 Bobbin HNI 4.56 'OC
+4.68 16 105 09/98 Bobbin HNC 1
1.53 0*H
+10.97 16 106 09/98 Bobbin HNI 2.23 10C
+20.47 l
-09/98 Bobbin HNC 19 0.72 17C
+7.44 09/98 Bobbin ODI 5
1.14 03H
+31.10 i
16 111 09/98 Bobbin HNC 24 0.48 07H
+27.60 09/98 Bobbin ODI 1
0.95 07H
+30.01 l
17 7 09/98 Bobbin NQI 0.26 14C
+11.69 i
09/98 Bobbin HNC 12 1.33 06H
+24.56 17 8 09/98 Bobbin HNC 5
1.60 10C
+5.61 17 9 09/98 ' Bobbin HNC 10 0.34 05H
+10.68 09/98 Bobbin ODI 15 0.33 17C
+5.12 09/98 Bobbin ODI 25 0.24 07H
+9.25 09/98 Bobbin ODI 37 0.40 14C
+11.08 17 11 09/98 Bobbin HNC 11 2.38 13C
+22.06 17 18 09/98 Bobbin ODI 12 0.51 10C
+31.94 17 19 09/98 Bobbin ODI 16 0.59 O1H
+3.90 t
17 24 09/98 Bobbin HNI 1.04 11C
+25.65 17 28 09/98 Bobbin HNI 2.06 18C
+9.15 17 31 09 98 Bobbin HNI 0.31 07H
+36.73 09 98 Bobbin ODI 1
0.94 13C
+25.95 09/98 Bobbin ODI 4
1.60 08H
+4.90 17 35 09/98 Bobbin HNC 11 1.16 07H
+22.56 17 39 09/98 Bobbin HNI 0.67 07H
+44.80 17 43 09/98 Bobbin ODI 7
0.52 10C
+37.95 i
09/98 Bobbin ODI 25 0.30 07H
+27.26 17 45 09/98 Bobbin HNC 29 0.52 10C
+17.27 17 52 09/98 Bobbin NQI 0.21 10C
+10.61 09/98 Bobbin HNC 17 0.94 07H
+30.16 1
09/98 Bobbin ODI 10 0.30 07H
+12.92 09/98 Bobbin ODI 19 0.26 10C
+32.81 09/98 Bobbin ODI 22 0.33 10C
+32.06 17 59 09/98 Bobbin ODI 14 1.26 15C
+8.68 09/98 C/L Special Interest VOL 0.48 15C
+9.03 17 61 09/98 Bobbin HNC 16 1.84 14C
+11.48 09/98 C/L Special Interest VOL 0.97 14C
+11.93 17 63 09/98. Bobbin HNC 14 1.43 03H
+11.13 17 65 09/98 Bobbin HNC 10 2.26 17C
+1.19 09/98 Bobbin ODI 10 1.20 18C
+14.50 17 80 09/98 Bobbin HNC 28 1.04 13C
+14.83 09/98 C/L Special Interest VOL 1.14 13C
+15.89 17 85 09/98 Bobbin NOI 0.45 04H
+18.85 17 86 09/98 Bobbin HNI 0.74 07H
+8.51 09/98 H/L Special Interest VOL 1.52 07H
+8.51 17 88 09/98 Bobbin HNC 17 0.25 11C
+20.91 17 108 09/98 Bobbin NQI 0.48 OBH
+0.22 09/98 ' Bobbin HNC 10 0.96 06H
+2.93 17 110 09/98 Bobbin HNI 0.58 05H
+24.62
- m. _ _ _. _
i FTI TUBAN TI (Version 3.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 9 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 18 4 09/98 Bobbin ODI 32 0.75 07H
+41.02 18 10 09/98 Bobbin ODI 2
1.02 10C
+43.15 18 15 09/98 Bobbin HNI 0.46 11C
+12.54 09/98 Bobbin HNC 15 0.34 13C
+6.88 18 17 09/98 Bobbin HNI 0.38 10C
+24.40 18 26 09/98 Bobbin ODI 25 0.49 13C
+23.89 18 36 09/98 Bobbin HNC 6
1.58 13C
+30.60 09/98 Bobbin HNC 14 2.02 13C
+28.42 09/98 Bobbin ODI 9
0.59 16C
+5.20 18 38 09/98 Bobbin HNC 10 1.01 10C
+41.83 18 41 09/98 Bobbin HNC 7
1.13 12C
+21.72 18 64 09/98 Bobbin HNC 15 0.78 O1H
+20.01 09/98 Bobbin ODI 9
0.45 11C
+6.23 09/98 Bobbin ODI 19 0.33 02H
+11.08 09/98 H/L Special Interest VOL 0.66 02H
+11.46 09/98 H/L Special Interest VOL 1.06 O1H
+19.70 18 65 09/98 Bobbin HNC 16 0.99 05H
+24.36 18 66 09/98 Bobbin HNC 2
0.87 13C
+17,75 09/98 Bobbin HNC 9
0.79 18C
+4.13 18 67 09/98 Bobbin HNC 10 1.84 10C
+4.26 09/98 C/L Special Interest VOL 0.51 10C
+3.93 18 90 09/98 Bobbin HNI 0.32 12C
+17.41 18 111 09/98 Bobbin HNI 0.60 13C
+1.15 09/98 Bobbin HNI 0.67 14C
+15.62 09/98 Bobbin HNI 0.89 06H
+26.95 09/98 Bobbin HNC 25 1.18 07H
+16.42 09/98 C/L Special Interest VOL 0.83 13C
-2,38 09/98 C/L Special Interest VOL 0.90 13C
+1.15 09/98 C/L Special Interest VOL 0.96 14C
+15.62 09/98 H/L Special Interest VOL 0.93 07H
-15.04 09/98 H/L Special Interest VOL 1.46 07H
+16.33 19 15 09/98 Bcbbin NOI 0.66 16C
+9.53 19 16 09/98 Bobbin HNI 0.24 04H
+15.55 09/98 Bobbin HNI 0.43 04H
+11.91 09/98 Bobbin ODI 3
0.62 10C
+43.96 09/98 Bobbin ODI 10 0.19 10C
+2.69 09/98 Bobbin ODI 10 0.32 10C
+3.86 09/98 Bobbin ODI 18 0.23 10C
+42.85 09/98 H/L Special Interest VOL 1.53 04H
+12.52 09/98 H/L Special Interest VOL 2.88 04H
+16.58 19 19 09/98 Bobbin HNC 12 0.71 07H
+38.98 09/98 Bobbin ODI 27 0.40 07H
+40.79 19 22 09/98 Bobbin ODI 23 0.35 10C
+41.56 19 43 09/98 Bobbin ODI 16 2.34 13C
+7.13 19 45 09/98 Bobbin NOI 0.34 07H
+44.50 19 46 09/98 Bobbin HNC 20 0.41 10C
+39.15 09/98 Bobbin ODI 3
0.64 10C
+41.88 19 48 09/98 Bobbin ODI 7
1.24 07H
+40.17 19 51 09/98 Bobbin ODI 5
0.53 10C
+40.87 19 52 09/98 Bobbin NQI 0.34 10C
+41.32 19 54 09/98 Bobbin HNI 1.26 10C
+43.90 19 62 09/98 Bobbin HNI 0.51 12C
+30.48 i
19 69 09/98 Bobbin HNI 0.76 06H
+14.10 19 94 03/98 Bobbin HNC 7
1.04 04H
+8.95 09/98 Bobbin HNC 7
1.50 O1H
+14.89 l
09/98 Bobbin HNC 18 0.69 05H
+10.05 j
09/98 Bobbin HNC 18 1.30 05H
+13.71
)
09/98 H/L Special Interest VOL 1.16 05H
+10.45 09/98 H/L Special Interest VOL 1.58 OSH
+13.58 19 96 09/98 Bobbin HNC 6
1.72 11C
+34.97 19 100 09/98 Bobbin ODI 29 0.59 O1H
+20.58 09/98 H/L Special Interest VOL 1.30 02H
-8.28 19 103 09/98 Bobbin HNI 1.44 13C
+24.16 to
+31.27 09/98 Bobbin HNI 2.04 10C
+16.91 to
+24.88 19 105 09/98 Bobbin HNI 0.51 07H
+44.51
~.
.-- __._ ~ -.
l i
l FTZ TUDAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two II/G A 05/98 RFO Bobbin,C/L Special Interest, Expansion C t->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
/
Page 10 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA l
ROW COL OUTAGE TEST TYPE IND LTW VOLTS LOCATION i
09/98 Bobbin HMC 12 0.50 07H
+43.58 l
19 107 09/98 Bobbin HNI 0.65 15C
+15.85 09/98 Bobbin HNI 1.01 12C
+2.74 l
19 110 09/98 Bobbin HNC 19 0.39 10C
+41.28 l
20 5 09/98 Bobbin HNC 14 0.37 10C
+44.01 i
20 6 09/98 Bobbin ODI 20 0.41 02H
+6.08 20 9 09/98 Bobbin HNI 0.04 11C
+18.00 20 12 09/98 Bobbin HNC 7
1.02 18C
+8.22 09/98 Bobbin HNC 15 0.50 10C
+16.15 09/98 Bobbin HNC 23 0.29 10C
+15.01 09/98 Bobbin ODI 12 0.51 10C
+32.90 l
20 20 09/98 Bobbin HNI 0.33 06H
+24.67 09/98 Bobbin ODI 19 0.41 07H
+30.60 20 22 09/98 Bobbin NQI 0.59 10C
+41.15 09/98 Bobbin HNC 6
1.38 10C
+43.88 09/98 Bobbin ODI 3
0.95 10C
+36.88 09,'98 Bobbin ODI 32 0.43 10C
+35.75 20 23 09/98 Bobbin HNI 0.49 14C
+10.12 09/98 Bobbin HNC 13 0.51 15C
+B.08 20 45 09/98 Bobbin HNC 8
0.29 10C
+42.27 20 47 09/98 Bobbin ODI 18 0.44 07H
+44.05 20 48 09/98 Bobbin ODI 2
0.43 07H
+43.16 09/98 Bobbin ODI 5
0.30 07H
+2.19 20 50 09/98 Bobbin ODI 11 0.27 07H
+42.66 20 52 09/98 Bobbin HNC 2
0.86 10C
+43.14 20 54 09/98 Bobbin ADI 0.97 07H
+5.80 09/98 Bobbin HNC 6
1.76 15C
+3.99 09/98 Bobbin ODI 9
1.13 18C
+10.25 20 57 09/98 Bobbin HNI 0.36 11C
+7.60 i
09/98 Bobbin HNI 0.62 14C
+14.84 1
09/98 Bobbin NQI 0,15 10C
+21.64 i
09/98 Bobbin HNC 1
1.43 14C
+15.85 09/98 Bobbin HNC 7
0.80 11C
+8.70 09/98 Bobbin ODI 23 0.21 10C
+31.18 09/98 Bcbbin HNI 0.88 06H
+19.57 to
+32.49 09/98 Bobbin NOI 0.78 07H
+4.33 to
+41.87 09/98 Bobbin NQI 1.07 10C
+22.82 to
+30.58 20 63 09/98 Bobbin HNC 28 0.28 15C
+16.37 09/98 Bobbin ODI 2
0.92 04H
+21.99 20 70 09/98 Bobbin HNI 0.64 16C
+5.96 20 77 09/98 Bobbin HNC 21 0.58 04H
+15.14 20 86 09/98 Bobbin HNI 0.39 06H
+8.98 20 88 09/98 Bobbin HNI 0.87 12C
+38.27 20 91 09/98 Bobbin HNI 0.67 05H
+37.61 20 92 09/98 Bobbin HNI 1.14 10C
+3.80 20 109 09/98 Bobbin HNC 20 1.17 O1H
+21.43 21 5 09/98 Bobbin ODI 14 0.22 TSH
+7.14 21 8 09/98 Bobbin ODI 8
0.46 06H
+30.36 21 19 09/98 Bobbin HNC 20 0.61 10C
+32.31 21 46 09/98 Bobbin ODI 8
0.33 04H
+36.31 21 47 09/98 Bobbin ODI 13 0.68 07H
+40.20 21 49 09/98 Bobbin ODI 21 0.51 07H
+35.75 21 51 09/98 Bobbin ODI 9
0.27 TSH
+30.41 21 53 09/98 Bobbin HNI 0.45 02H
+15.92 09/98 Bobbin ODI 12 0.62 10C
+41.97 21 64 09/98 Bobbin HNC 22 0.87 02H
+13.32 21 75 09/98 Bobbin HNC 19 0.32 14C
+6.68 21 80 09/98 Bobbin HNI 0.79 02H
+13.47 09/98 H/L Special Interest VOL 2.58 02H
+13.53 21 88 09/98 Bobbin HNI 0.53 07H
+18.91 09/98 Bobbin NOI 0.34 17C
+16.50 09/98 H/L Special Interest VOL 1.10 07H
+18.91 21 92 09/98 Bobbin HNI 0.47 04H
+2.70 09/98 Bobbin HNI 0.47 07H
+2.00 09/98 H/L Special Interest VOL 0.70 07H
+1.93
s FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A j
09/98 RFO Bobbin,C/L Special Interest,Expannion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 11
)
ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA I
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 H/L Special Interest VOL 0.73 04H
+2.73 21 94 09/98 Bobbin HNI 1.13 10C
+3.87 to
+10.37 21 lot 09/98 Bobbin HNI 1.32 07H
+24.21 J
09/98 Bobbin HNC 17 0.82 07H
+23.02 21 103 09/98 Bobbin HNC 10 0.55 10C
+43.91 09/98 Bobbin HNC 15 0.19 10C
+24.48 i
21 104 09/98 Bobbin NQI 0.32 10C
+33.61 09/98 Bobbin OD1 24 0.30 10C
+27.86 l
21 106 09/98 Bobbin HNI 0.95 10C
+42.77 09/98 Bobbin HNC 12 0.34 07H
+38.63 09/98 Bobbin HNC 23 0.27 07H
+37.04 21 107 09/98 Bobbin HNI 0.37 04H
+20.64 09/98 Bobbin HNI 0.46 05H
+38.02 09/98 Bobbin HNC 9
0.39 10C
+34.67 09/98 H/L Special Interest VOL 1.54 04H
+21.75 22 6 09/98 Bobbin NQI 0.26 10C
+15.28 22 11 09/98 Bobbin NQ1 0.51 OSH
+30.53 09/98 Bobbin ODI 15 1.27 13C
+24.80 09/98 C/L Special Interest VOL 0.95 13C
+24.58 l
22 14 09/98 Bobbin HNC 7
0.87 07H
+44.45 22 20 09/98 Bobbin HNI 0.42 07H
+35.37 09/98 Bobbin HNC 21 1.03 11C
+27.61 09/98 Bobbin ODI 24 0.31 10C
+39.23 i
22 24 09/98 Bobbin HNI 0.62 12C
+41.12 09/98 C/L Special Interest VOL 0.52 12C
+41.11 09/98 C/L Special Interest VOL 0.62 12C
-2.42 09/98 C/L Special Interest VOL 0.65 12C
-1.68 22 41 09/98 Bobbin HNI 0.36 17C
+2.23 09/98 Bobbin HNC 7
1.44 02H
+7.26 09/98 Bobbin HNC 15 1.19 14C
+7.64 09/98 Bobbin ODI 6
0.84 15C
+14.38 l
09/98 Bobbin ODI 8
0.75 19C
+7.19 09/98 C/L Special Interest VOL 0.34 17C
+2.68 l
09/98 C/L Special Interest VOL 0.56 14C
+7.99 22 44 09/98 Bobbin HNC 13 0.68 10C
+42.57 22 76 09/98 Bobbin HNC 1
0.55 13C
+4.39 22 89 09/98 Bobbin HNI 0.18 14C
+11.66 09/98 Bobbin HNC 5
0.38 14C
+9.14 22 96 09/98 Bobbin HNI 0.94 07H
+22.35 09/98 Bobbin HNC 28 0.54 06H
+19.73 22 97 09/98 Bobbin HNC 28 0.44 O1H
+17.44 22 108 09/98 Bobbin HNI 0.22 07H
+41.82 09/98 Bobbin HNI 0.34 10C
+29.96 09/98 Bobbin NQI 0.13 10C
+22.43 09/98 Bobbin ODI 3
1.12 11C
+30.96 l
09/98 Bobbin ODI 13 0.32 10C
+41.63 l
09/98 Bobbin ODI 17 0.21 10C
+23.52 09/98 Bobbin ODI 19 0.75 10C
+15.78 23 16 09/9F Bobbin NOI 0.23 15C
+13.56 09/93 Bobbin HNC 12 0.50 07H
+37.81 23 19 09/38 Bobbin HNI 0.45 10C
+13.95 23 30 09/98 Bobbin HNC 15 1.10 11C
+20.33 23 31 09/98 Bobbin HNC 11 0.62 07H
+10.29 23 72 09/98 Bobbin ODI 23 0.68 08H
+1.33 i
23 77 09/98 Bobbin HNC 9
0.77 15C
+1.95 23 78 09/98 Bobbin HNC 14 0.75 11C
+5.73 23 93 09/98 Bobbin ODI 15 0.55 03H
+18.51 09/98 H/L Special Interest VOL 0.61 03H
+18.87 23 95 09/98 Bobbin HNI 1.21 06H
+21.48 09/98 H/L Special Interest VOL 2.23 06H
+21.44 j
23 106 09/98 Bobbin HNI 0.15 10C
+39.69 09/98 Bobbin HNI 0.27 10C
+40.03 2
09/98 Bobbin HNC 20 0.44 07H
+34.95 23 108 09/98 Bobbin HNI 0.31 10C
+38.29 4
09/9B Bobbin HNC 19 0.62 10C
+33.15 1
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 12 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin NQI 0.46 07H
+26.83 to
+40.8*
23 109 09/98 Bobbin ODI 5
1.12 10C
+38.38 09/98 Bobbin ODI 9
0.55 10C
+37.40 24 15 09/98 Bobbin HNC 10 1.02 18C
+3.15 09/98 Bobbin ODI 19 0.61 19C
+8.87 24 18 09/98 Bobbin HNC 14 0.62 10C
+42.37 09/98 Bobbin HNC 26 0.33 10C
+41.20 09/98 Bobbin ODI 3
2.44 07H
+36.12 09/98 Bobbin ODI 28 0.40 07H
+13.94 24 25 09/98 Bobbin HNC 9
1.39 14C
+4.83 09/98 Bobbin ODI 13 0.67 07H
+5.53 09/98 Bobbin ODI 18 0.44 10C
+34.87 24 31 09/98 Bobbin ODI 5
0.85 10C
+40.16 09/98 Bobbin ODI 6
1.05 13C
+37.26 09/98 Bobbin ODI 7
1.14 31C
+35.57 09/98 Bobbin ODI 8
0.92 12C
+40.45 09/98 Bobbin ODI 9
0.66 10C
+37.69 09/98 Bobbin ODI 10 0.56 10C
+33.28 09/98 Bobbin ODI 11 1.04 18C
+8.79 09/98 Bobbin ODI 28 0.29 10C
+32.10 24 33 09/98 Bobbin ODI 5
1.08 19C
+6.85 24 37 09/98 Bobbin ODI 6
1.72 12C
+4.48 i
24 41 09/98 Bobbin ODI 22 0.44 IOC
+40.18 24 44 09/98 Bobbin ODI 10 0.35 12C
+13.73 24 46 09/98 Bobbin ODI 3
0.54 13C
+12.43 24 49 09/98 Bobbin HNI 0.28 10C
+41.21 1
24 51 09/98 Bobbin NQI 0.19 07H
+20.75 i
09/98 Bobbin ODI 3
0.23 07H
+21.89 09/98 Bobbin ODI 5
0.35 07H
+34.07 24 52 09/98 Bobbin ODI 22 0.13 07H
+19.32 09/98 Bobbin ODI 24 0.13 07H
+12.99 24 53 09/98 Bobbin ODI B
0.45 07H
+23.52 09/98 Bobbin ODI 11 0.43 10C
+41.72 09/98 Bobbin ODI 17 0.25 07H
+22.37 1
24 55 09/98 Bobbin ODI 17 0.29 10C
+27.96 24 63 09/98 Bobbin HNC 17 0.36 11C
+4.73 1
09/98 Bobbin ODI 10 0.60 07H
+40.44 24 64 09/98 Bobbin HNC 10 0.78 13C
+15.05 09/98 Bobbin ODI 4
1.61 10C
+24.02 09/98 Bobbin ODI 13 0.72 04H
+23.40 24 77 09/98 Bobbin HNI 0.29 10C
+12.13 24 79 09/98 Bobbin HNI 0.20 10C
+44.19 24 84 09/98 Bobbin NQI 0.36 OBH
+0.12 09/98 Bobbin HNC 10 0.33 07H
+33.79 09/98 Bobbin HNC 20 1.42 05H
+31.41 09/98 H/L Special Interest VOL 2.69 06H
-11.52 4
24 90 09/98 Bobbin HNC 14 0.80 11C
+31.67 09/98 Bobbin HNC 27 1.04 16C
+7.47 24 94 09/98 Bobbin HNC 11 1.33 12C
+38.91 24 98 09/98 Bobbin NOI 0.73 07H
+2.52 24 99 09/98 Bobbin HNI 0.30 10C
+41.70 09/98 Bobbin HNC 2
0.99 07H
+34.68 09/98 Bobbin HNC 15 1.23 07H
+37.14 24 100 09/98 Bobbin ODI 17 0.45 10C
+28.26 i
09/98 Bobbin ODI 22 0.40 07H
+44.52 24 107 09/98 Bobbin ODI 32 0.20 10C
+44.16 25 B 09/98 Bobbin HNC 5
1.17 16C
+13.15 09/98 C/L Special Interest VOL 0.73 16C
+12.94 25 13 09/98 Bobbin HNI 0.50 16C
+11.91 25 15 09/98 Bobbin NOI 0.26 10C
+33.67 25 23 09/98 Bobbin HNI 0.30 07H
+26.25 25 25 09/98 Bobbin ODI 34 0.25 10C
+29.80 25 27 09/98 Bobbin HNI 0.38 07H
+11.66 09/98 Bobbin HNC 15 0.28 19C
+3.48 09/98 Bobbin ODI 4
0.65 07H
+12.82
FTI TUBAM II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 13 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 7
1.18 13C
+38.93 09/98 Bobbin ODI 8
0.22 07H
+44.73 i
09/98. Bobbin ODI 8
0.36 07H
+39.00 25 29 09/98 Bobbin HNI 2.69 AV1
+18.48 25 30 09/98 Bobbin NQI 0.21 07H
+41.45 09/98 Bobbin HNC 9
1.75 13C
+9.41 09/98 Bobbin HNC 11 2.03 14C
+9.47 09/98 Bobbin ODI 11 1.08 14C
+12.46 25 32 09/98 Bobbin HNC 13 0.61 12C
+22.29 09/98 Bobbin HNC 16 1.67 06H
+18.22 09/98 H/L Special Intcreet VOL 1.59 06H
+18.38 25 36 09/98 Bobbin HNC 12 0.60 12C
+18.53 25 37 09/98 Bobbin HNI 4.01 AV4
+18.93 25 39 09/98 Bobbin ODI 13 0.69 06H
+15.56 25 41 09/98 Bobbin ODI 11 3.60 O1H
+23.96 25 52 09/98 Bobbin NOI 0.25 02H
+31.13 25 55 09/98 Bobbin HNI 1.05 12C
+6.85 09/98 C/L Special Interest VOL 1 31 12C
+6.99 25 59 09/98 Bobbin HNC 10 0,81 12C
+9.83 l
09/98 C/L Special Interest VOL 0.41 12C
+9.57 25 69 09/98 Bobbin HNC 12 1.07 06H
+30.05 25 71 09/98 Bobbin HNI 0.38 07H
+40.09 25 80 09/98 Bobbin HNC 23 0.73 19C
+3.78 25 98 09/98 Bobbin ODI 30 0.36 07H
+36.82 25 101 09/98 Bobbin HNC 12 0.35 06H
+34.37 i
25 103 09/98 Bobbin HNI 0.23 10C
+42.35 09/98 Bobbin HNC 13 0.50 10C
+33.82 09/98 Bobbin HNC 21 0.22 10C
+37.09 25 104 09/98 Bobbin HNC 19 0.40 07H
+32.86 09/98 Bobbin HNC 20 0.63 13C
+35.19 09/98 Bobbin ODI 9
0.35 10C
+22.05 25 106 09/98 Bobbin HNC 8
0.95 10C
+41.04 09/98 Bobbin ODI 21 0.34 10C
+27.21 09/98 Bobbin ODI 24 0.59 AV4
+3.31 25 107 09/98 Bobbin HNC 4
1.02 05H
+14.35 09/98 Bobbin ODI 4
1.08 10C
+39.27 25 108 09/98 Bobbin HNC 25 0.58 07H
+34.05 26 8 09/98 Bobbin HNC 4
0.52 10C
+33.79 09/98 Bobbin ODI 19 0.31 07H
+40.05 26 11 09/98 Bobbin HNC 7
0.77 02H
+20.80 26 20 09/98 Bobbin HNI 0.29 07H
+26.24 26 24 09/98 Bobbin HNI 0.78 12C
+6.29 26 28 09/98 Bobbin ODI 11 1.45 11C
+40.63 09/98 C/L Special Interest VOL 0.95 11C
+40.49 26 30 09/98 Bobbin HNI 0.23 10C
+39.96 26 32 09/98 Bobbin HNI 1,67 09C
+18.69 26 36 09/98 Bobbin HNC 16 0.40 10C
+34.13 26 64 09/98 Bobbin HNC 13 0.93 14C
+5.23 26 69 09/98 Bobbin ODI 7
1.72 07H
+15.28 26 70 09/98 Bobbin NOI 0.30 10C
+40.93 09/98 Bobbin ODI 15 0.40 11C
+30.30 26 71 09/98 Bobbin HNI 0.34 10C
+43.36 26 74 09/98 Bobbin HNI 0.36 10C
+23.31 09/98 Bobbin HNI 0.60 10C
+20.59 09/98 Bobbin NOI 0.16 19C
+3.61 09/98 Bobbin HNC 1
0.98 05H
+30.48 09/98 Bobbin HNC 16 1.75 10C
+2.00 09/98 Bobbin ODI 9
1.22 12C
+40.66 09/98 Bobbin ODI 10 1.67 12C
+23.48 09/98 C/L Special Interest VOL 0.69 10C
+2.02 26 77 09/98 Bobbin HNC 21 0.73 13C
-0.28 l
26 86 09/98 Bobbin HNC 19 1.32 14C
+13.58 26 88 09/98 Bobbin HNI 0.19 10C
+44.92 09/98 Bobbin HNC 22 0.62 11C
+17.88 a
09/98 C/L Special Interest VOL 0.53 11C
+18.31 l
l J
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 14 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 26 89 09/98 Bobbin ADI 1.59 18C
+13.14 09/98 Bobbin ADI 1.65 16C
+13.02 09/98 Bobbin ADI 1.76 19C
+4.94 09/98 C/L Special Interest VOL 0.46 16C
+13.24 26 90 09/98 Bobbin HNI 4.11 14C
+7.11 09/98 Bobbin ODI 14 1.74 11C
+19.85 09/98 C/L Special Interest VOL 0.98 14C
+7.08 26 92 09/98 Bobbin NQI C.58 13C
+39.39 26 95 09/98 Bobbin HNC 20 0.46 10C
+30.10 27 13 29/98 Bobbin HNI 0.54 10C
+28.88 09/98 Bobbin HNI 0.62 17C
+2.11 27 18 09/98 Bobbin HNI 0.97 06H
+10.15 27 19 09/98 Bobbin HNI 0,41 11C
+0.29 27 24 09/98 Bobbin HNI 1.04 16C
+14.52 09/98 C/L Special Interest VOL 0.66 16C
+14.41 27 32 09/98 Bobbin HNC 9
0.76 11C
+23.59 27 34 09/98 Bobbin NOI 0.24 07H
+39.13 09/98 Bobbin HNC 24 0.94 10C
+31.19 09/98 Bobbin ODI 7
0.71 15C
+3.50 09/98 Bobbin ODI 8
2.22 10C
+27.89 1
09/98 C/L Special Interest VOL 0.99 10C
+31.19 09/98 C/L Special Interest VOL 1.04 10C
+31.19 i
09/98 C/L Special Interest VOL 1.25 10C
+27.89 27 39 09/98 Bobbin HNI 0.25 10C
+41.68 09/98 Bobbin HNC 19 0.53 10C
+33.46 27 42 09/98 Bobbin ODI 10 0.27 16C
+15.18 09/98 Bobbin ODI 11 0.34 16C
+15.87 09/98 Bobbin ODI 14 1.42 12C
+21.76 09/98 Bobbin ODI 15 0.27 10C
+40.52 27 43 09/98 Bobbin HNC 20 0.77 07H
+9.32 27 49 09/98 Bobbin HNC 17 0.97 07H
+7.96 27 51 09/98 Bobbin HNI 0.49 10C
+39.60 27 53 09/98 Bobbin NQI 0.29 07H
+44.50 09/98 Bobbin NQI 0.48 07H
+41.90 09/98 Bobbin HNC 8
0.72 10C
+27.71 27 56 09/98 Bobbin HNC 13 0.45 10C
+43.63 27 69 09/98 Bobbin ODI 8
0.59 15C
+3.37 09/98 Bobbin ODI 8
0.97 15C
+5.25 09/98 Bobbin ODI 12 0.80 16C
+15.23 09/98 Bobbin ODI 15 0.49 16C
+16.04 09/98 C/L Special Interest VOL 0.39 16C
+16.04 j
09/98 C/L Special Interest VOL 0.47 16C
+15.23 27 77 09/98 Bobbin ADI 1.94 13C
+41.91 i
09/98 Bobbin ODI 13 0.52 13C
+5.90 27 78 09/98 Bobbin ODI 10 0.91 15C
+4.03 27 83 09/98 Bobbin HNC 5
1.36 09C
-0.63
~
27 85 09/98 Bobbin HNC 22 0.k, 16C
+13.05 27 87 09/98 Bobbin HNC 31 0.60 05H
+25.87 27 92 09/98 Bobbin NQI 0.53 10C
+8.42 27 93 09/98 Bobbin HNI 0.17 10C
+38.85 1
27 94-09/98 Bobbin HNI 0.30 07H
+44.01 27 96 09/98 Bobbin HNI 0.19 10C
+35.12 09/98 Bobbin NQI 0.22 10C
+36.22 27 98 09/98 Bobbin HNC 7
1.02 10C
+38.46 09/98 Bobbin HNC 8
0.48 07H
+43.78 09/98 Bobbin OD7 27 0.32 07H
+42.13 09/98 H/L Special Interest VOL 0.55 08H
-3.79 09/98 H/L Special Interest VOL 0.84 08H
-1.84 27 99 09/98 Bobbin HNC 3
0.75 10C
+37.76 09/98 Bobbin HNC 10 0.35 10C
+36.57 27 101 09/98 Bobbin HNC 23 0.28 07H
+31.98 27 102 09/98 Bobbin HNI 1.62 07H
+30.16 09/98 Bobbin HNC 17 0.26 10C
+41.11 09/98 Bobbin HNC 34 0.33 07H
+24.24 09/98 H/L Special Interest VOL 2.57 08H
-15.84
1 l
l l
FTI TUBAN II (Version 3.3) 01/21/1999 11:23:12 l
Catawba Nuclear Station - Unit Two i
S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&18,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA i
ROW COL OUTAGE TEST TYPE IND LTW VOLTS LOCATION 27 103 09/98 Bobbin HNC 5
0.52 10C
+39.83 09/98 Bobbin HNC 20 0.77 04H
+24.35 27 104 09/98 Bobbin HNC 19 0.36 12C
+23.85 09/98 Bobbin HNC 25 0.76 13C
+16.26 i
09/98 C/L Special Interest VOL 1.08 13C
+16.26 27 105 09/98 Bobbin ODI 4
2.98 07H
+43.84 27 106 09/98 Bobbin HNI 0.68 10C
+41.02 09/98 Bobbin HNC 19 0.49 07H
+44.45 09/98 Bobbin ODI 25 0.48 O1H
+24.38 27 107 09/98 Bobbin HNC 3
0.62 07H
+45.17 1
28 9 09/98 Bobbin HNI 0.71 14C
+5.68 09/98 Bobbin HNC 14 1.76 15C
+8.19 09/98 Bobbin ODI 5
1.43 05H
+39.21 09/98 C/L Special Interest VOL 1.78 15C
+8.25 1
09/98 H/L Special Interest VOL 2,14 06H
-3.72 l
28 12 09/98 Bobbin HNC 4
0.53 07H
+27.88 j
28 15 09/98 Bobbin HNI 1.32 06H
+33.42 09/98 Bobbin HNI 1.56 06H
+30.55 09/98 H/L Special Interest VOL 2.48 07H
-9.45 09/98 H/L Special Interest VOL 3.15 07H
-12.38 28 19 09/98 Bobbin HNI 0.54 18C
+7.96 28 21 09/98 Bobbin NQI 0.60 09C
+0.46 28 27 09/98 Bobbin NOI 0.34 19C
+6.10 09/98 Bobbin HNC 10 0.54 03H
+27.95 28 37 09/98 Bobbin HNI 0.29 10C
+39.19 28 42 09/98 Bobbin HNC 17 0.79 10C
+38.36 28 45 09/98 Bobbin HNI 0.48 13C
+35.03 09/98 Bobbin HNI 0.81 14C
+2.53 09/98 Bobbin HNI 1.18 05H
+25.00 09/98 Bobbin HNI 1.44 05H
+8.15 09/98 Bobbin ODI 4
0.80 14C 99.18 09/98 C/L Special Interest VOL 0.45 12C
-7.75 09/98 H/L Special Interest VOL 1.63 05H
+B.61 28 46 09/98 Bobbin HNI 1.01 13C
+35.57 09/98 Bobbin HNI 1.04 17C
+15.19 09/98 Bobbin HNI 1.05 12C
+38.75 09/98 Bobbin HNI 1.09 13C
+36.47 09/98 Bobbin HNI 1.31 05H
+6.67 09/98 Bobbin NOI 0.61 14C
+16.58 09/98 Bobbin HNC 12 0.62 07H
+13.44 09/98 C/L Special Interest VOL 0.80 12C
-7.37 09/98 C/L Special Interest VOL 0.83 12C
-6.41 09/98 C/L Special Interest VOL 0.98 11C
-4.17 28 52 09/98 Bobbin HNI 0.69 12C
+18.11 28 53 09/98 Bobbin HNC 12 0.42 18C
+3.68 09/98 Bobbin HNC 15 0.61 18C
+2.55 28 60 09/98 Bobbin HNC 4
0.39 11C
+23.70 28 63 09/98 Bobbin ODI 14 0.59 O1H
+9.56 09/98 Bobbin ODI 20 0.65 TSH
+6.87 28 69 09/98 Bobbin ODI 5
1.23 16C
+2.17 28 72 09/98 Bobbin HNI 0.39 17C
+4.43 09/98 Bobbin HNI 0.52 06H
+9.09 05/98 Bobbin HNC 24 1.03 06H
+6.43 09/98 C/L Special Interest VOL 0.42 17C
+4.61 28 74 09/98 Bobbin HNI 0.84 10C
+7.33 09/98 Bobbin HNC 12 0.78 10C
+16.52 09/98 C/L Special Interest VOL 0.71 10C
+17.20 09/98 C/L Special Interest VOL 0.92 10C
+7.36 28 77 09/98 Bobbin ODI 14 0.26 19C
+2.25 28 78 09/98 Bobbin HNC 10 1.22 13C
+28.64 1
09/98 Bobbin HNC 10 1.45 13C
+24.64 1
09/98 C/L Special Interest VOL 0.56 13C
+28.73 l
09/98 C/L Special Interest VOL 0.79 13C
+24.79 28 68 09/98 Bobbin NOI 0.62 04H
+19.41 09/98 Bobbin HNC 2
2.19 13C
+26.25
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC I
Page 16 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 7
1.12 13C
+23.49 09/98 C/L Special Interest VOL 1.05 13C
+25.48 09/98 C/L Special Interest VOL 1.42 13C
+28.48 09/98 H/L Special Interest VOL 0.93 04H
+19.41 28 94 09/98 Bobbin HNI 0.27 10C
+41.91 28 95 09/98 Bobbin HNC 3
0.91 05H
+25.28 28 96 09/98 Bobbin HNC 15 0.90 16C
+9.72 28 99 09/98 Bobbin HNC 16 0.45 07H
+40.97 09/98 Bobbin HNC 24 0.88 10C
+33.48 28 100 09/98 Bobbin HNI 0.33 07H
+38.88 09/98 Bobbin HNC 11 0.56 07H
+42.68 28 103 09/98 Bobbin HNI 0.28 07H
+32.20 28 105 09/98 Bobbin HNI 0.18 10C
+32.44 09/98 Bobbin HNI 0.39 06H
+36.85 l
29 11 09/98 Bobbin ODI 12 0.30 10C
+35.18 29 18 09/98 Bobbin HNI 0.43 10C
+34.78 29 20 09/98 Bobbin NQI 0.27 10C
+36.69 29 22 09/98 Bobbin HNI 0.93 03H
+15.42 29 28 09/98 Bobbin HNC 8
0.59 10C
+32.59 09/98 Bobbin HNC 30 0.33 10C
+43.58 29 31 09/98 Bobbin HNI 0.44 09C
+1.11 09/98 Bobbin HNC 24 0.22 10C
+36.30 09/98 Bobbin HNC 29 0.38 10C
+28.02 09/98 Bobbin ODI 6
0.78 09C
-0.66 29 32 09/98 Bobbin HNC 4
0.65 07H
+40.30 09/98 Bobbin HNC 10 0.32 10C
+35.17 29 39 09/98 Bobbin HNI 0.24 07H
+28.67 09/98 Bobbin HNC 18 0.21 10C
+36.03 i
09/98 H/L Special Interest VOL 0.97 07H
+29.58 i
29 40 09/98 Bobbin HNI 0.34 10C
+40.53 09/98 Bobbin HNI 0.43 10C
+38.08 29 50 09/98 Bobbin HNI 0.41 13C
+9.49 29 51 09/98 Bobbin HNI 0.34 10C
+39.96 29 54 09/98 Bobbin HNC 18 0.55 IOC
+43.72 29 61 09/98 Bobbin HNC 3
0.62 10C
+44.04 09/98 Bobbin HNC 17 1.08 14C
+1.06 29 69 09/98 Bobbin HNC 4
1.53 10C
+19.91 29 78 09/98 Bobbin HNI 0.87 05H
+2.72 29 82 09/98 Bobbin HNC 12 1.26 17C
+4.28 29 84 09/98 Bobbin HNC 1
0.70 10C
+39.60 09/98 Bobbin HNC 6
0.42 10C
+19.50 29 92 09/98 Bobbin HNI 0.17 12C
+9.44 09/98 Bobbin HNC 34 0.33 18C
+7.97 29 94 09/98 Bobbin HNC 21 0.76 10C
+20.31 29 99 09/98 Bobbin HNC 15 0.97 07H
+37.35 29 100 09/98 Bobbin HNI 0.39 TSC
+3.00 09/98 Bobbin HNC 2
0.82 17C
+4.43 1
09/98 Bobbin HNC 6
1.55 06H
+6.33 09/98 Bobbin HNC 8
0.98 14C
+7.99 i
29 103 09/98 Bobbin NQI 0.36 15C
+12.86 i
29 104 09/98 Bobbin HNI 0.18 07H
+30.69 09/98 Bobbin HNI 0.22 07H
+10.82 09/98 Bobbin HNC 7
0.34 07H
+31.81 09/98 H/L Special Interest VOL 0.57 07H
+10.37 30 11 09/98 Bobbin HNI 0.37 07H
+26.27 30 13 09/98 Bobbin HNI 1.14 04H
+6.02 09/98 Bobbin HNI 1.65 12C
+11.56 09/98 Bobbin HNC 1
0.87 11C
+31.05 30 15 09/98 Bobbin HNC 10 0.51 18C
+12.02 30 18 09/98 Bobbin HNI 0.32 03H
+12.69 09/98 Bobbin HNC 21 0.36 06H
+10.61 30 29 09/98 Bobbin HNI 0.30 13C
+15.29 09/98 Bobbin HNC 13 0.92 09C
+1.18 09/98 Bobbin HNC 25 0.63 10C
+38.62 i
30 31 09/98 Bobbin HNI 1.03 19C
+3.65
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&lB,H/L Special Interest,H/L Tubesheet,MRPC Page 17 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 30 34 09/98 Bobbin NOI 0.38 10C
+21.30 30 35 09/98 Bobbin HNC 11 0.63 07H
+43.46 30 36 09/98 Bobbin HNC 10 0.78 13C
+32.60 30 37 09/98 Bobbin HNC 19 0.28 07H
+10.05 30 41 09/98 Bobbin ODI 10 1.24 13C
+4.89 09/98 Bobbin ODI 12 0.96 O1H
+17.61 09/98 Bobbin ODI 12 1.09 03H
+30.86 30 48 09/98 Bobbin HNC 11 0.83 O1H
+13.95 30 49 09/98 Bobbin HNC 19 1.00 04H
+39.26 30 51 09/98 Bobbin NQI 0.57 07H
+43.25 09/98 Bobbin ODI 12 0.56 10C
+39.47 30 56 09/98 Bobbin HNI 0.59 15C
+2.55 09/98 Bobbin HNI 1.00 13C
+15.98 09/98 Bobbin NOI 0.28 11C
+9.79 09/98 Bobbin HNC 28 0.35 13C
+27.85 09/98 Bobbin ODI 37 0.24 13C
+23.83 30 60 09/98 Bobbin ODI 27 0.22 06H
+6.26 30 61 09/98 Bobbin HNI 1.34 12C
+7.37 09/98 Bobbin HNI 2.22 12C
+21.85 30 62 09/98 Bobbin HNI 0.23 10C
+35.01 30 66 09/98 Bobbin HNI 1.28 14C
+9.28 09/98 C/L Special Interest VOL 0.89 14C
+9.60 30 68 09/98 Bobbin HNC 6
0.90 11C
+21.83 09/98 Bobbin HNC 24 0.29 10C
+41.36 i
09/98 Bobbin ODI 17 0.46 01H
+22.94 09/98 C/L Special Interest VOL 0.68 11C
+21.98 1
30 79 09/98 Bobbin HNI 1.56 15C
+6.57 09/98 Bobbin HNC 25 0.53 11C
+5.82 30 80 09/98 Bobbin HNC 14 0.32 13C
+26.95 09/98 Bobbin HNC 16 0.31 11C
+20.16 30 83 09/98 Bobbin HNC 19 1,82 05H
+29.20 09/98 Bobbin HNC 20 1.11 05H
+31.05 09/98 Bobbin HNC 22 2.26 05H
+34.91 09/98 H/L Special Interest VOL 1.18 06H
-11.83
~09/98 H/L Special Interest VOL 1.18 06H 13.72 09/98 H/L Special Interest VOL 1.35 06H
-8.00 30 88 09/98 Bobbin HNC 33 0.91 12C
+27.31 30 96 09/98 Bobbin HNI 0.41 10C
+10.15 09/98 Bobbin HNC 31 0.85 04H
+31.79 30 97 09/98 Bobbin ODI 16 0.39 02H
+33.57 09/98 H/L Special Interest VOL 0.60 03H
-2,33 30 98 09/98 Bobbin ODI 24 0.39 07H
+28.21 30 102 09/98 Bobbin HNC 22 0.26 11C
+10.11 30 103 09/98 Bobbin NOI 1.13 06H
+29.30 30 105 09/98 Bobbin HNC 13 0.39 11C
+10.98 31 13 09/98 Bobbin ODI 13 0.30 10C
+44.67 j
31 18 09/98 Bobbin HNI 0.74 10C
+35.81 j
09/98 Bobbin ODI 20 0.28 07H
+39.61 31 33 09/98 Bobbin HNC 12 0.38 07H
+25.18 i
C9/98 Bobbin HNC 34 0.46 07H
+21.67
)
09/98 Bobbin ODI 12 0.71 07H
+32.62 09/98 Bobbin ODI 27 0.32 07H
+26.03 31 34 09/98 Bobbin HNC 12 0.86 12C
+11.46 09/98 Bobbin HNC 22 0.35 10C
+37.35 31 35 09/98 Bobbin HNI 0.60 12C
+39.62 l
09/98 Bobbin HNI 2.03 19C
+4.80 03/98 C/L Special Interest VOL 0.98 19C
+4.95 09/98 C/L Special Interest VOL 1.31 19C
+4.93 1
31 40 09/98 Bobbin HNI 0.34 07H
+28.31 31 44 09/98 Bobbin HNC 22 1.56 16C
+13.70 09/98 C/L Special Interest VOL 0.74 16C
+14.05 31 51 09/98 Bobbin HNI 0.44 07H
+44.58 31 52 09/98 Bobbin NOI 0.20 07H
+3.10 09/98 Bobbin ODI 9
1.00 07H
+18.33 09/98 Bobbin ODI 14 0.97 07H
+17.40
. ~. - -. -.
I FTI TUBAN II (Vorsion 2.3) 01/31/1999 11:23:12 f
Catawba Nuclear Station - Unit Two S/G A l
09/98 RFO
~
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA i
' ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 16 0.46 10C
+4.83 31 53 09/98 Bobbin HNC 9
0.77 10C
+43.48 31 55 09/98 Bobbin ODI 9
0.78 17C
+8.87 09/98 Bobbin ODI 29 0.36 07H
+36.19 31 67 09/98 Bobbin HNI 0.33 10C
+42.13 t
31 68 09/98 Bobbin HNC 8
1.37 05H
+20.79
[
31 72 09/98 Bobbin HNI 0.95 05H
+41.41 31 73 09/98 Bobbin HNC 19 1.27 15C
+13.07 09 98 Bobbin ODI 34 0.24 11C
+10.92 i
31 75 09 98 Bobbin HNC 6
1.52 11C
+14.83 t
09/98 Bobbin HNC 9
0.85 15C
+16.70 l
31 77 09/98 Bobbin ODI 6
1.30 10C
+39.60 31 80 09/98 Bobbin HNC 17 0.53 03H
+15.21 l
31 81 09/98 Bobbin HNI 2.23 11C
+27.23 09/98 Bobbin NOI 1.47 11C
+25.95 09/98 Bobbin HNC 17 0.55 07H
+5.75
't 09/98 C/L Special Interest VOL 1.13 11C
+29.09 31 82 09/98 Bobbin HNI 0.68 03H
+10.58 09/98 Bobbin HNI 2.72 O1H
+9.35 09/98 Bobbin HNC 6
0.58 07H
+19.83 09/98 Bobbin ODI 3
0.85 14C
+9.02 31 92 09/98 Bobbin ODI 18 0.93 09C
-0.69 31 94 09/98 Bobbin HNI 0.36 10C
+42.44 31 96 09/98 Bobbin HNC 7
1.49 AV4
+2.53 31 99 09/98 Bobbin HNC 11 1.30 10C
+9.72 09/98 Bobbin HNC 14 1.31 13C
+26.64 09/98 Bobbin ODI 11 0.80 18C
+11.75 31 103 09/98 Bobbin WAR 18 0.82 AV2
-0.10 31 104 09/98 Bobbin HNI 0.61 19C
+3.35 09/98 Bobbin HNC 21 0.39 19C
+3.87 09/98 Bobbin HNC 22 0.50 19C
+1.57 32 13 09/98 Bobbin HNC 7
1.74 14C
+11.33 09/98 Bobbin HNC 16 0.53 15C
+4.37 09/98 C/L Special Interest VOL 1.03 14C
+11.33 32 14 09/98 Bobbin HNI 0.60 11C
+6.03 32 28 09/98 Bobbin ODI 8
1.46 16C
+15.28 32 40 09/98 Bobbin HNI 0.29 12C
+26.34 32 43 09/98 Bobbin ODI 19 0.59 07H
+23.74 32 45 09/98 Bobbin HNI 0.90 03H
+14.13 32 48 09/98 Bobbin ODI 22 0.31 07H
+35.72 32 70 09/98 Bobbin HNI 0.63 13C
+18.19 32 77 09/98 Bobbin HNC 6
1.58 12C
+35.23 32 79 09/98 Bobbin HNI 3.96 07H
+34.82 09/98 Bobbin HNI 1.28 17C
+4.24 to
+11.55 09/98 Bobbin HNC 29 1.38 12C
+11.67 to
+13.52 32 81 09/98 Bobbin HNC 1
0.66 13C
+29.15 32 82 09/98 Bobbin HNI 1.71 12C
+35.02 09/98 Bobbin ODI 7
0.49 12C
+31.82 32 83 09/98 Bobbin ODI 16 0.38 16C
+13.25 32 88 09/98 Bobbin HNI 0.49 12C
+33.18 32 89 09/98 Bobbin HNI 1.00 12C
+B.95 09/98 C/L Special Interest VOL 0.95 12C
+9.26 32 90 09/98 Bobbin HNI 0.77 04H
+32.49 32 94 09/98 Bobbin HNC 8
0.65 14C
+7.37 09/98 Bobbin ODI 8
0.36 10C
+2.91 09/98 Bobbin ODI 13 0.31 11C
+39.97 32 97 09/98 Bobbin HNC 13 0.88 07H
+38.62 32 103 09/98 Bobbin HNC 12 0.43 10C
+36.61 33 12 09/98 Bobbin HNC 29 1.03 11C
+6.67 09/98 Bobbin HNI 0.93 17C
+1.14 to
+7.25 33 15 09/98 Bobbin HNI 0.67 02H
+B.15 33 17 09/98 Bobbin RNI 1.35 15C
+2.20 33 22 09/98 Bobbin HNI 0.74 07H
+30.07 33 23 09/98 Bobbin HNI 0.54 10C
+33.82 33 28 09/98 Bobbin ODI 8
0.43 19C
+5.37
i l
FTZ TUBAN II (Version 2 3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO j
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 19 ATTACHMENT #1 INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 15 0.48 18C
+3.14 33 36 09/98 Bobbin HNI 0.66 10C
+36.42 33 41 09/98 Bobbin HNC 13 1.40 10C
+14.43 33 44 09/98 Bobbin HNC 7
1.28 16C
+5.40 33 47 09/98 Bobbin HNC 15 1.07 14C
+8.88 33 51 09/98 Bobbin ODI 14 0.66 12C
+13.70 09/98 Bobbin ODI 15 0.85 13C
+10.83 09/98 Bobbin ODI 18 0.52 11C
+25.77 33 59 09/98 Bobbin NQI 0.20 07H
+23.25 09/98 Bobbin ODI 13 0.30 10C
+12.75 33 61 09/98 Bobbin HNC 23 0.37 10C
+33.61 33 70 09/98 Bobbin HNC 6
0.42 10C
+26.54 09/98 Bobbin ODI 24 0.17 10C
+27.00 33 72 09/98 Bobbin HNC 9
0.75 10C
+11.69 33 76 09/98 Bobbin HNC 7
1.85 11C
+25.71 33 82 09/98 Bobbin HNC 14 1.16 15C
+3.94 09/98 Bobbin HNC 14 1.40 AV4
+19.52 33 93 09/98 Bobbin WAR 9
0.37 AV2
+0.00 33 95 09/98 Bobbin ODI 19 0.11 12C
+8.72 33 101 09/98 Bobbin NOI 0.21 19C
+5.65 34 14 09/98 Bobbin HNC 11 0.42 11C
+33.71 09/98 Bobbin HNC 14 0.27 11C
+34.29 09/98 Bobbin HNC 15 1.24 07H
+20,83 34 17 09/98 Bobbin HNI 0.60 10C
+34.44 34 18 09/98 Bobbin HNI 3.01 02H
+33.73 09/98 Bobbin HNC 25 0.40 18C
+9.51 34 22 09/98 Bobbin HNI 0.92 17C
+10.05 34 34 09/98 Bobbin HNI 0.51 16C
+13.98 34 39 09/98 Bobbin HNC 23 1.22 09C
+1.49 09/98 Bobbin ODI 17 0.50 14C
+2.95 34 42 09/98 Bobbin HNI 1.03 O1H
+15.81 34 45 09/98 Bobbin NOI 0.30 10C
+3.46 09/98 Bobbin HNC 15 1.47 10C
+11.14 34 52 09/98 Bobbin HNC 21 0.80 02H
+34.03 34 53 09/98 Bobbin ODI 7
0.33 13C
+9.71 34 55 09/98 Bobbin HNI 0.31 06H
+35.67 09/98 Bobbin HNI 0.71 06H
+19.77 09/98 Bobbin HNI 0.73 06H
+35.30 34 61 09/98 Bobbin HNI 5.40 02H
+12.94 34 63 09/98 Bobbin HNC 10 1.05 02H
+9.75 09/98 H/L Special Interest VOL 2.68 02H 49.53 34 69 09/98 Bobbin WAR 31 1.34 AV2
+0.00 34 70 09/98 Bobbin HNC 10 0.46 07H
+18.91 09/98 Bobbin HNC 17 0.38 10C
+37.44 09/98 Bobbin HNC 25 0.29 07H
+1.26 09/98 Bobbin HNC 28 0.32 10C
+30.29 09/98 Bobbin HNC 32 0.24 10C
+39.15 09/98 Bobbin HNC 32 0.32 07H
+26.05 34 85 09/98 Bobbin HNC 9
1.92 12C
+4.51 34 96 09/98 Bobbin HNC 13 2.05 17C
+8.47 35 15 09/98 Bobbin HNI 0.23 07H
+21.82 09/98 Bobbin HNI 0.54 07H
+28.36 09/98 Bobbin HNI 0.63 07H
+25.64 1
35 16 09/98 Bobbin HNI 0.67 07H
+37.73 l
09/98 Bobbin WAR 15 0.39 AV2
-0.15 09/98 Bobbin WAR 18 0.50 AV3
+0.00 35 21 09/98 Bobbin HNI 0.49 06H
+27.50 09/98 Bobbin HNI 1.19 12C
+19.60 09/98 C/L Special Interest VOL 1.41 12C
+19.63 i
l 35 25 09/98 Bobbin HNI 0.20 07H
+18.15 35 27 09/98 Bobbin HNI 2.03 03H
+23.72 35 28 09/98 Bobbin WAR 23 0.71 AV3
+0.00 1
35 30 09/98 Bobbin HNC 16 1.59 TSH
+2.44 i
09/98 Bobbin ODI 33 0.26 10C
+33.41 l
09/98 H/L Special Interest VOL 1.40 TSH
+2.55
. ~. -.
-. - ~ -
- ~-
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 20 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 35 32 09/98 Bobbin HNI 0.66 11C
+37.41 09/98 Bobbin HNI 0.86 07H
+20.74 09/98 Bobbin HNI 1.36 11C
+35.23 09/98 Bobbin HNI 2.01 11C
+36.12 09/98 C/L Special Interest VOL 0.60 11C
+37.58 09/98 C/L Special Interest VOL 1.32 11C
+35.23 09/98 C/L Special Interest VOL 1.57 11C
+36.13 35 33 09/98 Bobbin NOI 0.27 07H
+29.43 09/98 Bobbin HNC 2
0.39 07H
+42.36 09/98 Bobbin HNC 23 0.59 07H
+43.51 35 51 09/98 Bobbin NQI 0.24 07H
+40.67 l
l 09/98 Bobbin HNC 18 0.89 10C
+14.94 09/98 Bobbin ODI 11 0.35 10C
+33.21 35 74 09/98 Bobbin HNI 1.63 08H
+5.14 09/98 Bobbin HNC 12 0.81 10C
+12.82 35 92 09/98 Bobbin ODI 2
1.61 09C
-0.65 35 100 09/98 Bobbin HNI 0.49 14C
+5.77 09/98 Bobbin HNI 0.98 10C
+20.32 l
09/98 Bobbin HNC 13 1.54 14C
+7.28 09/98 Bobbin HNC 14 0.83 14C
+1.66 09/98 Bobbin HNC 18 0.60 14C
+13.43 09/98 Bobbin HNC 20 0.75 07H
+33.26 35 101 09/98 Bobbin HNC 6
0.89 10C
+36.68 09/98 Bobbin ODI 28 0.37 18C
+1.61 36 21 09/98 Bobbin HNI 0.56 18C
+0.81 i
36 27 09/98 Bobbin HNI 0.35 11C
+28,96 09/98 Bobbin HNC 24 0.48 12C
+30.68 36 31 09/98 Bobbin HNI 0.43 07H
+12.20 i
36 32 09/98 Bobbin HNI 2.51 17C
+13.95 36 35 09/98 Bobbin ODI 11 0.35 09C
-0.64 36 37 09/98 Bobbin ODI 18 0.81 13C
+7.01 r
09/98 C/L Special Interest VOL 0.65 13C
+6.95 36 43 09/98 Bobbin HNI 1.37 06H
+22.38 36 52 09/98 Bobbin HNC 8
1.05 11C
+22.60 36 59 09/98 Bobbin NQI 0.61 06H
+20.22 09/98 Bobbin NOI 0.61 10C
+17.56 36 68 09/98 Bobbin HNC 3
0.54 07H
+15.87 36 79 09/98 Bobbin HNC 14 0.38 10C
+38.73 09/98 Bobbin HNC 16 0.29 10C
+41.56 36 90 09/98 Bobbin HNI 0.48 12C
+37.41 36 98 09/98 Bobbin HNC 6
0.29 08H
+0.61 36 100 09/98 Bobbin HNI 0.28 07H
+39.27 09/98 Bobbin HNI 0.86 07H
+27.66 09/98 Bobbin HNI 1.01 12C
+24.78 j
37 22 09/98 Dcbbin HNI 0.79 15C
+11.83 37 23 09/98 Bobbin HNI 0.81 12C
+32.10 09/98 Bobbin HNI 3.17 12C
+17.81 09/98 C/L Special Interest VOL 0.85 12C
+32.10 09/98 C/L Special Interest VOL 1.72 12C
+18.76 l
09/98 C/L Special Interest VOL 1.90 12C
+17.81 37 27 09/98 Bobbin WAR 15 0.38 AV2
-0.05 i
37 49 09/98 Bobbin HNI 2.07 09C
+17.57 37 54 09/98 Bobbin HNI 0.35 07H
+17.03 09/98 Bobbin NQI 0.28 18C
+16.50 09/98 Bobbin NQI 1.18 17C
-1.64 to
+8.03 37 56 09/98 Bobbin HNI 0.38 05H
+26.75 37 62 09/98 Bobbin HNC 16 0.30 06H
+26.1F 37 65 09/98 Bobbin HNI 1.05 O1H
+24.58 37 66 09/98 Bobbit HNI 0.57 07H
+45.15 09/98 Bobbir.
ENI 0.66 07H
+44.83 i
37 70 09/98 Bobbin HNC 21 0.35 10C
+38.51 l
37 71 09/98 Bobbin HNI 0.75 02H
+13.76 09/S8 Bobbin HNI 1.13 17C
+14.90 37 93 09/98 Bobbin ODI 19 0.24 17C
+15.24 37 97 09/98 Bobbin NOI 0.54 08H
+11.03
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO l
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin HNC 4
1.10 07H
+22.26 37 99 09/98 Bobbin ODI 10 J.53 IOC
+23.69 09/98 Bobbin ODI 15 0.29 07H
+11.76 09/98 Bobbin
.ODI 17 0.34 07H
+28.21 to
+33.33 38 16 09/98 Bobbin NOI 0.30 07H
+15.79 38-17 09/98 Bobbin WAR 21 0.66 AV3
+0.00 38 25 09/98 Bobbin ~
NOI 0.26 08H
-0.68 09/98 Bobbin ODI 30 0.26 07H
+3.07 09/98 Bobbin WAR 26 0.41 AV3
-0.02 38 28 09/99 Bobbin HNC 15 0.44 07H
+33.59 38 31 09/98 Bobbin HNI 0.72 07H
+21.97 38 33 09/98 Bobbin ADI 1.42 17C
+12.12 09/98 C/L Special Interest VOL 0.48 17C
+12.27 38 35 09/98 Bobbin HNI 2.42 17C
+11.57 38 36 09/98 Bobbin HNI 0.84 17C
+13.88 i
09/98 Bobbin HNI 1.12 14C
+12.76 i
09/98 C/L Special Interest VOL 0.95 14C
+13.07 38 41 09/98 Bobbin NQI 0.31 07H
+37.65 09/98 Bobbin ODI 16 0.22 10C
+22.29 09/98 Bobbin ODI 19 0.41 07H
+40.66
)
38 42 09/98 Bobbin NQI 0.31 10C
+12.33 38 44 09/98 Bobbin HNI 0.77 04H
+30.67 09/98 Bobbin HNI 1.41 02H
+20.60 09/98 H/L Special Interest VOL 1.54 05H
-13.41 38 46 09/98 Bobbin HNI 0.42 18C
+1.12 38 50 09/98 Bobbin HNI 0.57 10C
+18.98 38 51 09/98 Bobbin HNC 12 0.49 14C
+10.66 38 55 09/98 Bobbin ODI 37 0.38 06H
+35.08 38 61 09/98 Bobbin HNI 0.46 08H
+1.41 38 64 09/98 Bobbin HNI 0.59 05H
+27.67 i
38 68 09/98 Bobbin HNC 8
1.24 04H
+3.78 i
38 74 09/98 Bobbin HNC 7
0.51 10C
+41.11 j
38 83 09/98 Bobbin HNC 14 0.57 07H
+35.89 38 89 09/98 Bobbin WAR 6
0.24 AV3
+0.00 1
38 91 09/98 Bobbin WAR 7
0.28 AV4
+0.00 38 93 09/98 Bobbin WAR 8
0.33 AV2
+0.05 38 96 09/98 Bobbin WAR 16 0.41 AV3
-0.10 09/98 Bobbin WAR 30 1.17 AV2
-0.32 09/98 UBEND SPEC. INT.
VOL 0.49 AV3
-0.10 09/98 UBEND SPEC. INT.
VOL 0.59 AV2
-0.32 38 97 09/98 Bobbin HNC 5
1.69 19C
+7.94 09/98 Bobbin WAR 15 0.60 AV4
+0.00 09/98 Bobbin WAR 16 0.73 AV3
+0.15 09/98 Bobbin WAR 30 1.78 AV2
-0.29 38 98 09/98 Bobbin WAR 9
0.38 AV3
+0.10 09/98 Bobbin WAR 11 0.46 AV2
-0.10 39 28 09/98 Bobbin HNC 19 0.40 10C
+31.48 39 32 09/98 Bobbin HNI 0.34 13C
+26.30 39 37 09/98 Bobbin HNI 0.45 06H
+24.46 39 44 09/98 Bobbin HNI 0.32 10C 436.76 39 46 09/98 Bobbin HNI 0.49 13C
+11.45 39 53 09/98 Bobbin HNC 8
0.67 03H
+3.71 09/98 Bobbin HNC 9
0.60 03H
+8.42 09/98 Bobbin ODI 4
0.81 03H
+6.61 09/98 Bobbin ODI 7
0.75 03H
+5.21 09/98 Bobbin ODI B
0.70 03H
+5.76 39 54 09/98 Bobbin HNC 6
0.59 10C
+13.20 09/98 Bobbin HNC 8
1.31 AV2
+8.72 09/98 Bobbin HNC 14 1.04 11C
+36.25 39 60 09/98 Bobbin HNC 25 0.61 10C
+36.13 39 62 09/98 Bobbin HNI 0.46 07H
+5.27 39 66 09/98 Bobbin HNI 0.91 OBH
+1.55 40 18 09/98 Bobbin WAR 31 1.37 AV3
+0.00 40 19 09/98 Bobbin HNI 0.43 07H
+30.84 09/98 Bobbin HNC 22 1.59 07H
+25.33
FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 22 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 40 23 09/98 Bobbin HNI 0.39 07H
+17.63 40 28 09/98 Bobbin HNI 0.66 12C
+16.01 09/98 Bobbin HNC 17 0.33 10C
+36.00 09/98 C/L Special Interest VOL 1.01 12C
+16.01 i
09/98 C/L Special Interest VOL 0.38 10C
+35.65 to
+37.89 40 43 09/98 Bobbin HNC 16 2.40 11C
+4.54 40 44 09/98 Bobbin HNI 0.35 16C
+2.01 09/98 Bobbin HNI 0.73 10C
+40.16 j
09/98 Bobbin HNC 5
1.37 10C
+42.85 l
09/98 Bobbin HNC 10 1.10 09C
+2.10 09/98 H/L Tubesheet VOL 2.51 TSH
+0.01 40 48 09/98 Bobbin HNC 3
0.69 10C
+42.88 1
40 50 09/98 Bobbin HNI 2.00 17C
+7.07 09/98 C/L Special Interest VOL 0.78 17C
+7.30 40 52 09/98 Bobbin HNC 27 0.75 02H
+26.22 09/98 H/L Special Interest VOL 1.99 03H
-9.96 i
40 54 09/98 Bobbin HNC 9
2.72 AV4
+29.15 09/98 Bobbin HNC 12 1,68 10C
+17.41 l
09/98 Bobbin HNC 16 0.87 10C
+5.13 09/98 Bobbin HNC 18 1.60 02H
+17.10 1
40 59 09/98 Bobbin HNI 1.66 AV1
+23.55 4
40 61 09/98 Bobbin HNI 0.40 12C
+2.06 09/98 C/L Special Interest VOL 0.25 12C
+2.23 40 63 09/98 Bobbin HNI 0.85 02H
+12.27 i
09/98 Bobbin HNI 0.93 03H
+12.92 40 64 09/98 Bobbin HNI 0.47 02H
+33.44 40 65 09/98 Bobbin HNC 3
0.87 08H
+1.63 40 68 09/98 Bobbin HNI 0.67 10C
+30.49 09/98 Bobbin HNC 11 0.81 08H
+1.74 40 69 09/98 Bobbin HNC 19 0.67 08H
+1.62 40 70 09/98 Bobbin HNC 26 0.60 08H
+1.80 09/98 Bobbin HNC 27 0.81 09C
+1.50 40 71 09/98 Bobbin HNC 15 0.67 OBH
+1.75 40 79 09/98 Bobbin HNC 18 1.04 09C
+11.59 40 86 09/98 Bobbin ENI 0.78 16C
+6.88 40 87 09/98 Bobbin HNC 1
1.11 16C
+4.65 40 91 09/98 Bobbin HNC 13 1.45 06H
+0.19 40 94 09/98 Bobbin WP.R 28 1.02 AV2
+0.00 40 95 09/98 Bobbin UAR 14 0.59 AV4
+0.10 09/98 Bobbin WAR 19 0.92 AV2
-0.19 41 22 09/98 Bobbin HNI 0.48 07H
+27.18 09/98 Bobbin NQI 0.24 10C
+38.28 41 27 09/98 Bobbin NQI 0.45 09C
+1.01 09/98 Bobbin NQI 0.70 07H
+36.86 09/98 Bobbin ODI 28 0.21 10C
+22.71 09/98 Bobbin ODI 30 0.24 10C
+24.48 41 44 09/98 Bobbin WAR 15 0.39 AV1
+0.00 41 45 09/98 Bobbin HNC 13 0.99 12C
+1.50 41 46 09/98 Bobbin NOI
,0.27 19C
+3.12 41 54 09/98 Bobbin HNC 12 0.16 07H
+12.19 41 63 09/98 Bobbin NQI 0.25 07H
+43.30 09/98 Bobbin HNC 22 0.27 06H
+15.25 41 68 09/98 Bobbin HNC 6
2.06 10C
+5.57 09/98 Bobbin HNC 12 1.11 02H
+12.08 41 81 09/98 Bobbin WAR 9
0.31 AV4
+0.14 09/98 Bobbin WAR
- 3 0.51 AV3
+0.12 09/98 Bobbin WAR 19 0.84 AV2
-0.02 41 82 09/98 Bobbin HNC 3
0.54 12C
+10.52 41 83 09/98 Bobbin WAR 16 0.52 AV2
+0.00 09/98 Bobbin WAR 20 0.61 AV3
+0.00 41 84 09/98 Bobbin HNI 0.35 OBH
-0.51 41 85 09/98 Bobbin WAR 16 0.72 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 0.66 AV3
-0.26 41 90 09/98 Bobbin WAR 14 0.34 AV3
+0.10 41 92 09/98 Bobbin WAR 7
0.28 AV4
+0.00 i
. ~ ~.. -
i FTI TUBAN II (Version 2.3) 01/31/1999 11:23:12 Catawba Euclear Statica - Unit Two S/G A 09/98 RFO f
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
Page 23 S
ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION l
09/98 Bobbin WAR 13 0.57 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 1.88 AV4
+0.00 09/98 UBEND SPEC. INT.
VOL 2.12 AV3
+0.00 1
41 93 09/98 Bobbin ODI 25 0.35 11C
+39.24 09/98 Bobbin WAR 9
0.36 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 1.26 AV4
+0.00 09/98 UBEND SPEC. INT.
VOL 1.46 AV3
+0.00 41 94 09/98 Bobbin WAR 6
0.25 AV4
+0.10 09/98 Bobbin WAR 17 0.76 AV2
-0.12 09/98 Bobbin WAR 25 1.36 AV3
+0.15 09/98 UBEND SPEC. INT.
VOL 1.85 AV2
+0.00 09/98 UBEND SPEC, INT.
VOL 1.95 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 2.55 AV4
+0.00 42 21 09/98 Bobbin HNI 0.89 13C
+20.28 09/98 C/L Special Interest VOL 1.23 13C
+20.67 42 22 09/98 Bobbin NQI 0.52 10C
+31.59 09/98 C/L Special Interest VOL 0.54 10C
+31.82 42 27 09/98 Bobbin HNC 31 0.43 07H
+19.38 42 30 09/98 Bobbin HNI 0.42 07H
+16.95 42 45 09/98 Bobbin HNI 0.97 07H
+37.23 09/98 Bobbin NQI 0.24 16C
+7.48 09/98 Bobbin ODI 17 0.70 16C
+5.49 42 48 09/98 Bobbin ODI 10 0.31 13C
+9.35 42 53 09/98 Bobbin HNI 4.26 04H
+25.93 09/98 Bobbin NQI 0.25 16C
+8.66 09/98 Bobbin ODI 15 0.32 10C
+6.56 42 54 09/98 Bobbin HNI 2.88 17C
+4.88 09/98 Bobbin HNI 4.81 15C
+7.96 42 61 09/98 Bobbin HNC 1
1.37 13C
+22.12 42 62 09/98 Bobbin HNI 0.40 07H
+9.43 42 64 09/98 Bobbin ODI 10 0.56 06H
+40.08 42 75 09/98 Bobbin HNI 0.62 12C
+13.81 09/98 Bobbin HNI 0.84 17C
+3.02 L
42 76 09/98 Bobbin ODI 6
1.32 10C
+31.58 t
42 81 09/98 Bobbin WAR 16 0.47 AV2
+0.00 42 85 09/98 Bobbin WAR 22 0.58 AV3
+0.10 09/98 Bobbin WAR 33 1.40 AV2
-0.27 42 91 09/98 Bobbin WAR 13 0.54 AV3
+0.00 42 92 09/98 Bobbin NOI 0.34 08H
+2.64 09/98 Bobbin HNC 18 0.37 07H
+25.10 09/98 Bobbin HNC 20 0.30 07H
+35.91 09/98 Bobbin ODI 6
0.28 06H
+26.72 43 29 09/98 Bobbin HNC 10 0.97 08H
-0.46 09/98 Bobbin HNC 27 0.39 09C
-0.66 43 31 09/98 Bobbin NOI 0.32 06H
+17.97 43 39 09/98 Bobbin NOI 0.49 02H
+16.27 09/98 Bobbin HNC 7
0.65 03H
+3.19 09/98 H/L Special Interest VOL 3.52 03H
-19.85 43 41 09/98 Bobbin HNC 4
1.87 02H
+26.24 09/98 H/L 5pecici Interest VOL 1.79 02H
+26.17 43 50 09/98 Bobbin HNC 15 0.97 05H
+22.68 09/98 H/L Special Interest VOL 1.40 05H
+22.68 43 52 09/98 Bobbin HNC 16 0.90 AV3
+11.21 43 54 09/98 Bobbin HNC 19 0.65 13C
+38.34 43 55 09/98 Bobbin ADI 1.89 AV3
+16.38 l
09/98 Bobbin ADI 2.47 AV3
+23.83 l
09/98 Bobbin HNI 2.33 AV4
+28.25 09/98 Bobbin HNI 2.41 AV3
+0.88 i
09/98 Bobbin HNI 2.95 AV4
+17.75 l
09/98 Bobbin HNC 12 0.04 13C
+3.98 l-09/98 Bobbin HNC 13 0.88 10C
+38.08 09/98 Bobbin HNC 21 0.89 14C
+16.18 i
i 09/98 Bobbin HNC 28 1.20 AV4
+20.40 l
09/98 C/L Special Interest VOL 0.53 14C
+16.18 l
43 68 09/98 Bobbin HNC 30 2.77 10C
+18.02 i
. ~..
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:23:12 Cattwba Nuclser Station - Unit Two S/G A 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 24 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 30 1.74 10C
+18.99 09/98 C/L Special Interest MMI 1.73 10C
+18.68 09/98 C/L Special Interest MMI 2.33 10C
+17.74 43 70 09/98 Bobbin HNC 1
0.71 07H
+14.60 43 91 09/98 Bobbin WAR 12 0.31 AV1
+0.00 09/98 Bobbin WAR 16 0.38 AV2
+0.00 09/98 Bobbin WAR 17 0.43 AV3
-0.17 09/98 Bobbin WAR 24 0.67 AV4
+0.00 09/98 UBEND SPEC. INT.
VOL 1.45 AV2
+0.00 09/98 UBEND SPEC. INT.
VOL 1.90 AV3
+0.00 09/98 UBEND SPEC. INT, VOL 2.20 AV1
+0.00 09/98 UBEND SPEC. INT.
VOL 2.48 AV4
+0.00 43 93 09/98 Bobbin HNC 14 0.79 11C
+11.45 44 23 09/98 Bobbin WAR 8
0.19 AV1
-0.05 09/98 Bobbin WAR 21 0.63 AV4
+0.00 09/98 Bobbin WAR 22 0.70 AV2
+0.00 09/98 Bobbin WAR 37 2.38 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 0.43 AV1
+0.00 09/98 UBEND SPEC. INT.
VOL 0.52 AV4
+0.00 09/98 UBEND SPEC. INT.
VOL 0.78 AV2
+0.00 09/98 UBEND SPEC. INT.
VOL 1.20 AV3
+0.00 44 25 09/98 Bobbin WAR 12 0.31 AV2
+0.00 44 28 09/98 Bobbin HNI 0.49 08H
-0.48 09/98 Bobbin HNC 8
1.05 13C
+4.03 44 30 09/98 Bobbin HNC 35 0.17 08H
-0.19 44 36 09/98 Bobbin HNC 3
0.41 09C
-0.64 44 40 09/98 Bobbin HNC 8
2.23 17C
+8.16 44 41 09/98 Bobbin HNI 1.55 12C
+6.65 44 43 09/98 Bobbin HNI 0.18 06H
+18.68 44 46 09/98 Bobbin NQI 0.58 19C
+8.05 09/98 Bobbin HNC 22 1.44 05H
+12.89 09/98 Bobbin ODI 13 0.51 TSC
+5.62 09/98 Bobbin ODI 17 0.45 TSC
+4.52 09/98 Bobbin ODI 34 0.41 11C
+25.56 44 47 09/98 Bobbin HNI 3.11 13C
+21.04 09/9C Bobbin HNI 3.53 13C
+8.83 09/98 Bobbin HNC 11 2.46 02H
+29.07 09/98 Bobbin HNC 16 1.72 02H
+16.26 09/98 C/L Special Interest VOL 1.06 13C
+21.13 09/98 C/L Special Interest VOL 1.11 13C
+8.54 09/98 H/L Special Interest VOL 1.20 03H
-6.50 09/98 H/L Special Interest VOL 1.83 03H
-19.61 44 51 09/98 Bobbin HNI 0.34 07H
+23.86 i
09/98 Bobbin HNI 1.02 13C
+36.87 09/98 Bobbin ODI 8
0.31 07H
+42.13 44 60 09/98 Bobbin HNC 23 0.68 07H
+31.49 09/98 Bobbin ODI 3
2.43 07H
+32.63 44 61 09/98 Bobbin HNC 27 1.86 11C
+2.75 i
44 62 09/98 Bobbin HNI 0.53 07H
+39.15 1
09/98 Bobbin HNI 1.90 07H
+40.31 44 63 09/98 Bobbin HNC 19 0.39 06H
+37.61 44 64 09/98 Bobbin HNI 0.54 O1H
+22.97 l
44 66 09/98 Bobbin HNI 0.54 07H
+44.90 l
09/98 Bobbin HNI 0.62 14C
+2.81 09/98 Bobbin HNI 0.63 13C
+31.00 09/98 Bobbin HNI 0.92 05H
+30.43 09/98 Bobbin HNI 6.31 AV4
+17.01 09/98 UBEND tPEC. INT.
VOL 4.90 AV4
+17.57 44 74 09/98 Bobbin HNI 1.40 02H
+15.15 09/98 Bobbin ODI 4
1.00 18C
+10.55 09/98 Bobbin ODI 11 0.71 17C
+16.86 44 75 09.38 Bobbin HNC 11 0.47 15C
+4.91 44 79 09/98 Bobbin HNI 3.84 06H
+39.89 09/98 H/L Special Interest VOL 2.49 07H
-2.67 l
44 81 09/98 Bobbin HNI 0.74 10C
+23.05 I
l l
1
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A J
09/98 RFO i
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC i
Page 25 ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND LTW VOLTS LOCATION 44 82 09/98' Bobbin NQI 0.24 03H.
+27.54 09/98 Bobbin ODI 13 0.92 07H
+44.60 44 89 09/98 Bobbin HNI 5.10 TSH
+3.80 45 26 09/98 Bobbin WAR 24 0.83 AV3
+0.05 09/98 UBEND. SPEC. INT.
VOL.
0.37 AV3
+0.00 45 30 09/98 Bobbin HNI 0.18 07H
+28.55.
09/98 Bobbin.
HNI 0.29 07H'
+28.77 45 34 09/98 Bobbin HNI 2.58 03H
+11.64 09/98 H/L Special Interest VOL 4.87 03H
+11.43 45 41 09/98 Bobbin HNI 0.47 15C
+26.13 45 54 09/98 Bobbin HNC 8
0.61 02H
+22.76 45 68 09/98 Bobbin HNC 31 0.30 06H
+19.03 45 74 09/98 ~ Bobbin ADI 1.61 15C
+28.16 45 75 09/98 Bobbin HNC 12 1.44 18C.
+15.28 09/98 Bobbin HNC 19 0.87 12C
+23.71 45 81 09/98 Bobbin HNC 13 1.31 07H
+25.39
-45 84 09/98 Bobbin HNC 5
0.48 11C
+27.99 09/98-Bobbin HNC 6
0.46 IOC
+22.50 45 88 09/98 Bobbin HNC 18 0.46 19C
+7.51 09/98 Bobbin ODI 25 0.46 19C
+0.57 45 89 09/98 Bobbin HNI 1.33 04H
+12.82 45 90 09/98 Bobbin WAR 13 0.56 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 1.76 AV3
+0.00 45 91 09/98 Bobbin WAR 13 0.33 AV3
-0.14 09/98 Bobbin WAR 16 0.40 AV2
+0.00 09/98 Bobbin WAR 27 0.83 AV4
+0.00 09/98 UBEND SPEC. INT.
VOL 0.38 AV3
-0.14 09/98 UBEND SPEC. INT.
VOL 0.49 AV4
+0.00 09/98-UBEND SPEC. INT.
VOL 0.51 AV2
-0.00 46 26 09/98 Bobbin HNI 1.51 02H
+17.97 09/98 H/L Special Interest VOL 3.10 02H
+17.35 46 30 09/98 Bobbin HNI 0.55 18C
+12.41 09/98 Bobbin NQI 0.26 06H
+22.57 09/98 Bobbin HNC 9
2.85 06H
+16.03 09/98 Bobbin HNC 19 1.37 17C
+29.53 03/98 C/L Snacial Interest VOL 0.85 17C
+29.84 46 31 09/98 Bobbin NQI 0.30 09C
+0.33 09/98 Bobbin NOI 0.76 08H.
-0.46 46 32 09/98 Bobbin HNI 2.15 06H
+33.24 09/98 Bobbin HNI 2.92 12C
+31.96 09/98 H/L Special Interest VOL 0.69 07H
-9.13 l
46 34 09/98 Bobbin HNI 0.24 07H
+26.91 46 37 09/98 Bobbin HNI 0.22 10C
+27.11 09/98 Bobbin HNC 12 3.14 03H
+8.05 09/98 Bobbin HNC 18 2.30 12C
+9.74 09/98 Bobbin ODI 15 0.33 10C
+12.50 46 45 09/98 Bobbin HNC 15 0.34 11C
+27.05 09/98 Bobbin ODI 11 0.32 15C
+28.70 46 53 09/98 Bobbin HNC 1
0.55 17C
+12.96 46 64 09/98 Bobbin HNI 1 51 03H
+35.13 46 87 09/98 Bobbin HNI 1.90 07H
+12.96 46 88 09/98 Bobbin HNC 15 1.28 05H
+11.00 1
46 89 09/98 Bobbin HNI 0.36 10C
+44.70 47 27 09/98 Bobbin HNC 13 2.20 12C
+21.41 09/98 Bobbin WAR 29 1.12 AV3
+0.00 47 28 09/98 Bobbin HNC 14 1.21 11C
+26,17 1
09/98 Bobbin ODI 16 1.03 09C
+15.92 09/98 Bobbin ODI 18 1.89 09C
+11.66 1
47 33 09/98 Bobbin HNI 0.68 15C
+22.01 09/98 Bobbin HNI 0.80 18C
+8.42 09/98 Bobbin HNI 1.16 17C
+28.89 47 34 09/98 Bobbin HNI 0.31 17C
+2.83 47 35 09/98 Bobbin HNI 0.35 03H
+29.47 09/98 Bobbin HNI 0.42 15C
+22.16 j
47 36 09/98 Bobbin HNI 2.69 17C
+4.73 l
I
l FTI TUBAN II (Version 2.3) 01/21/1999 11:23:12 Catawba Nuclear Station - Unit Two S/G A 09/98 RFO l
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
Page 26 ATTACHMENT #1 - INDICATIONS OF 1MPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION I
47 38 09/98 Bobbin HNI 0.44 19C
+0.66 09/98 C/L Special Interest VOL 1.09 19C
+0.73 47 42 09/98 Bobbin HNI 0.28 06H
+23.40 47 43 09/98 Bobbin HNC 3
2.20 AV1
+19.77 l
09/98 Bobbin HNC 19 2.54 AV4
+22.64 09/98 Bobbin ODI 27 0.32 15C
+27.91 09/98 C/L Special Interest VOL 0.71 15C
+27.92 47 46 09/98 Bobbin HNI 1.47 11C
+16.87 47 55 09/98 Bobbin HNI 2.13 04H
+21.22
)
09/98 Bobbin HNC 13 0.69 13C
+34.83 09/98 Bobbin HNC 21 0.89 10C
+21.42 09/98 Bobbin HNC 29 0.41 10C
+9.35 09/98 C/L Special Interest VOL 0.47 10C
+B.97 09/98 C/L Special Interest VOL 0.56 10C
+20.61 47 65 09/98 Bobbin HNI 1.61 10C
+6.75 47 67 09/98 Bobbin HNC 19 0.68 08H
+22.90 47 71 09/98 Bobbin HNC 13 1.20 06H
+37.70 47 15 09/98 Bobbin HNC 9
0.79 17C
+26.51 09/98 Bobbin ODI 7
1.92 TSH
+6.93 09/98 H/L Special Interest VOL 1.40 TSd
+6.70 j
47 77 09/98 Bobbin HNC 12 0.97 10C
+40.03 47 84 09/98 Bobbin HNC 7
0.96 06H
+34.44 48 31 09/98 Bobbin HNC 3
1.17 06H
+36.74 48 32 09/98 Bobbin HNI 0.53 07H
+25.36 48 35 09/98 Bobbin HNI 0.25 07H
+26.46 48 46 09/98 Bobbin HNI 0.24 07H
+22.64 j
09/98 Bobbin HNI 0.34 13C
+32.17 1
48 50 09/98 Bobbin ODI 4
1.67 07H
+34.96 48 52 09/98 Bobbin HNC 8
1.17 17C
+4.05 48 53 09/98 Bobbin HNI 0.63 07H
+44.64 l
48 56 09/98 Bobbin ODI 36 0.61 AV1
+17.02
)
48 59 09/98 Bobbin HNI 2.33 03H
+9.44 i
48 68 09/98 Bobbin HNI 1.66 12C
+23.72 09/98 Bobbin HNC 29 1.55 10C
+43.71 l
l 09/98 C/L Special Interest VOL 0.91 10C
+43.71 48 75 09/98 Bobbin HNC 5
0.77 10C
+43.38 09/98 Bobbin HNC 17 0.85 10C
+41.10 48 76 09/98 Bobbin HNC 30 0.29 15C
+15.47 09/98 Bobbin HNC 32 0.18 10C
+42.02
)
09/98 Bobbin ODI 19 0.30 10C
+43.23 48 78 09/98 Bobbin HNC 18 0.50 13C
+39.73 09/98 Bobbin HNC 23 0.62 13C
+38.48 l
09/98 Bobbin ODI 17 0.95 08H
+17.92 09/98 C/L Special Interest VOL 0.43 13C
+38.21 48 80 09/98 Bobbin HNC 9
0.73 07H
+22.39 l
48 84 09/98 Bobbin HNC 19 0.69 10C
+22.88 48 85 09/98 Bobbin HNI 0.47 10C
+43.16 49 31 09/98 Bobbin HNI 2.39 12C
+41.44 49 43 09/98 Bobbin HNI 1.73 15C
+13.80 09/98 Bobbin HNI 1.84 15C
+16.49 09/98 C/L Special Interest VOL 0.77 15C
+13.88 09/98 C/L Special Interest VOL 0.99 15C
+16.55 49 45 09/98 Bobbin HNC 11 0.87 15C
+13.49 49 47 09/98 Bobbin HNI 0.40 10C
+20.65 49 80 09/98 Bobbin HNI 2.45 07H
+17.15 j
Total Indications Found = 1680 Total Tubes Found = 905 i
t
i FTI TUBAN II (Version 2.3) 01/21/1999 11:25:38 i
Catavia Nuclear Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&18,H/L Special Interest,H/L Tubesheet,MRPC Page 1 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 1
6 09/98 Bobbin ADI 3.80 16C
+17.35 1
8 09/98 Bobbin ODI 11 1.09 06H
+31.90 1 14 09/98 Bobbin ADI 2.61 18C
+32.06 09/98 Bobbin ADI 3.50 16C
+3.31 09/98 Bobbin HNI 1.21 06H
+5.86 1 19 09/98 Bobbin NQI O.44 12C
+21.26 1 20 09/98 Bobbin NQI 0.38 02H
+0.19 1 40 09/98 Bobbin HNC 4
0.60 04H
+7.19 1 44 09/98 Bobbin ODI 9
0.23 TSC
+2.86 1 49 09/98 Bobbin HNI 0.14 TSH
+1.98 09/98 Bobbin HNI 0.27 TSH
+0.47 1 50 09/98 Bobbin ODI 10 0.55 TSC
+3.35 1 51 09/98 Bobbin HNI 0.40 19C
+3.85 09/98 Bobbin NQI 0.64 TSC
+4.00 09/98 Bobbin HNC 19 0.46 TSH
+2.49 1 52 09/98 Bobbin HNC 10 1.24 02H
+4.94 09/98 Bobbin ODI 35 0.48 TSH
+0.42 09/98 H/L Special Interest VOL 1.61 TSH
+0.65 1 54 09/98 Bobbin ODI 20 0.44 TSC
+2.10 1 56 09/98 Bobbin HNI 1.14 04H
+38.86 1 61 09/98 UBEND PLUS POINT MAI 1.11 09C
+4.71 1 63 09/98 Bobbin HNI 0.33 12C
+40.85 09/98 Bobbin HNI O.50 04H
+8.14 1 77 09/98 Bobbin HNI 0.96 18C
+15.66 1 81 09/98 Bobbin HNI 0.35 18C
+6.15 1 82 09/98 Bobbin HNI 0.29 10C
+29.95 1 84 09/98 Bobbin HNC 1
1.83 12C
+12.35 09/98 C/L Special Interect VOL 1.26 12C
+13.25 1 90 09/98 Bobbin HNI 0.30 03H
+14.04 1 91 09/98 Bobbin ElI 0.35 07H
+8.30 1 98 09/98 Bobbin NQI 0.29 19C
+7.09 2
2 09/98 Bobbin NOI 0.34 06H
+39.30 09/98 Bobbin HNC 23 0.99 O1H
+17.81 2
3 09/98 Bobbin HNC 20 1.37 O1H
+12.10 2
8 09/98 Bobbin ODI 15 1.36 19C
+6.12 2
9 09/98 Bobbin ADI 2.65 12C
+4.99 2 26 09/98 Bobbin HNC 4
0.89 18C
+30.61 09/98 C/L Special Interest VOL 0.73 18C
+30.43 2 27 09/98 Bobbin ODI 5
1.53 03H
+28.95 2 31 09/98 Bobbin NOI 0.60 18C
+33.43 2 33 09/98 Bobbin ODI 2
0.67 04H
+15.29 2 41 09/98 Bobbin HNC 27 0.42 16C
+16.11 2 43 09/98 Bobbin HNC 5
0.88 03H
+19.57 2 57 09/98 Bobbin HNI 0.91 07H
+18.41 09/98 Bobbin HNI 1.04 07H
+21.45 2 58 09/98 Bobbin HNI 0.38 05H
+21.34 2 60 09/98 Bobbin GDI 7
0.36 12C
+32.81 2 75 09/98 Bobbin HNI 1.44 05H
+27.08 2 77 09/98 Bobbin ODI 18 0.28 01H
+3.94 2 83 09/98 Bobbin HNI 0.78 04H
+0.79 2 85 09/98 Bobbin ODI 10 2.32 02H
+6.19 2 89 09/98 Bobbin HNC 23 0.88 11C
+36.85 09/98 C/L Special Interest VOL 0.93 11C
+37.04 2 96 09/98 Bobbin HNI 0.54 O1H
+2.28 2 100 09/98 Bobbin HNI 0.36 O1H
+24.79 09/98 Bobbin HNI 0.37 O1H
+22.39 2 101 09/98 Bobbin ODI 15 0.32 18C
+12.28 09/98 Bobbin NQI 2.47 18C
+17.41 to
+28..7 2 102 09/98 Bobbin ODT 20 0.27 16C
+20.86 09/98 Bobbin ODI 20 0.38 18C
+2.30 2 105 09/93 Bobbin HNI 1.69 O1H
+2 26 2 112 09/98 Bobbin HNI 0.31 03H
+ 2 ',. 6 8 3
4 09/98 Bobbin ADI 0.99 TSH
+3.47 3 14 09/98 Bobbin ODI 18 0.79 05H
+14.26 09/98 H/L Special Interest VOL 1.43 05H
+14.27
I FTI TUBAN II (Varsion 2.3) 01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 2 ATTACHMfNT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND tTW VOLTS LOCATION i
3 24 09/98 Bobbin HNC 14 1.53 12C
+28.02 3 26 09/98 Bobbin HNC 1
0.77 13C
+24.70 3 33 09/98 Bobbin HNI 0.59 10C
+18.36 09/98 Bobbin HNC 5
0.56 O1H
+25.43 3 36 09/98 Bobbin HNI 0.57 02H
+33.00 3 38 09/98 Bobbin HNI 0.58 03H
+33.01 09/98 Bobbin HNC 7
1.12 13C
+9.19 3 43 09/98 Bobbin HNI O.59 O1H
+17.48 3 47 09/98 Bobbin ODI 22 0.41 18C
+16,69 3 49 09/98 Bobbin ODI 21 0.46 15C
+5.69 3 50 09/98 Bobbin HNC 8
1.47 11C
+22.22 3 52 09/98 Bobbin HNC 3
0.80 04H
+12.78 09/98 Bobbin HNC 18 1.30 04H
+13.28 3 55 09/98 Bobbin HNI 0.54 11C
+19.13 3 60 09/98 Bobbin HNI 0.71 03H
+11.28 09/98 Bobbin HNI 1.47 03H
+13.27 3 61 09/98 Bobbin HNI 0.29 07H
+2.87 09/98 Bobbin HNI 0.39 07H
+2.82 3 62 09/98 Bobbin HNI 0.30 02H
-0.48 3 63 09/98 Bobbin HNC 9
1.52 10C
+9.92 3 75 09/98 Bobbin HNI 3.76 02H
+17.03 09/98 H/L Special Interest VOL 1.54 02H
+17.24 3 76 09/98 Bobbin NOI O.33 03H
+12.78 3 78 09/98 Bobbin HNI 0.16 13C
+36.21 3 91 09/98 Bobbin HNI 0.21 04H
+0.65 3 103 09/98 Bobbin HNI 0.13 16C
+6.99 3 111 09/98 Bobbin NQI 0.16 18C
+8.30 4 11 09/98 Bobbin HNC 10 0.92 07H
+13.99 09/98 Bobbin ODI 10 0.73 10C
+40.09 4 25 09/98 Bobbin HNC 12 0.70 11C
+13.88 4 43 99/98 Bobbin HNI 1.86 O1H
+5.93 4 53 03/98 Bobbin NOI 0.47 18C
+7.50 09/98 Bobbin HNC 6
1.36 11C
+31.12 4 54 09/98 Bobbin HNC 4
0.77 07H
+18.10 09/98 Bobbin HNC 6
0.68 07H
+20.19 09/98 Bobbin HNC 6
1.04 07H
+18.27 09/98 Bobbin HNC 9
0.70 07H
+14.30 09/98 Bobbin HNC 10 0.60 07H
+19.91 09/98 Bobbin HNC 22 0.72 0'iH
+14.20 4 59 09/98 Bobbin HNI 0.74 07H
+12.17 09/98 Bobbin HNI 0.47 OTH
+19.70 09/98 Bobbin HNI 0.61 07H
+16.25 09/98 Bobbin HNI O.87 07H
+24.69 09/98 H/L Special Interest VOL 1.57 07H
+15.47 4 73 09/98 Bobbin HNI 1.18 DEH
+6.43 09/98 H/L Speciel Interest VOL 1.96 05H
+6.59 4 75 09/98 Bobbin HNI 2.54 06H
+5.17 4 93 09/98 Bobbin HNI 0.26 12C
+27.59 09/98 C/L Special Interest VOL 0.71 12C
+28.05 4 104 09/98 Bobbin ODI 19 0.57 11C
+33.78 4 106 09/98 Bobbin HNI 1.12 04H
+12.60 5
1 09/98 Bobbin NQI 0.33 08H
-0.53 5
5 09/98 Bobbin HNC 13 0.38 12C
+28.91 5 23 09/98 Bobbin HNC 13 1.36 07H
+14.67 5-47 09/98 Bobbin HNC 27 0.31 16C
+15.32 5 51 09/98 Bobbin ODI 12 0.24 14C
+6.38 5 59 09/98 Bobbin HNI 0.39 07H
+36.80 09/98 Bobbin HNI 0.43 07H
+ 2 5. 0 '.
5 60 09/98 Bobbin HNI 0.85 07H
+20.80 09/98 Bobbin HNI 0.87 07H
+20.76 09/98 H/L Special Interest VOL 0.04 07H
+20.57 09/98 H/L Special Interest VOL 1.26 07H
+19.61 5 78 09/98 Bobbin HNI 2.28 13C
+7.53 09/98 C/L Special Interest VOL 0.89 13C
+7.42 5 89 09/98 Bobbin HNI 0.62 02H
+9.47
. - -. - ~ -.
. - -. - - - - _ _. ~. - - =.. -
.FTI TUBAN II (Version 2.3).
01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two S/G B' 09/98 RFO l Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 3 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB t
- ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 6
6 09/98 Bobbin HNI 0.60 12C
+11.42 6
7 09/98 Bobbin HNI 0.72 16C
+8.70 6 14 09/98 Bobbin HNI 0.72 02H
+17.44 i
6 45 09/98 Bobbin HNI 1.28 08H
+7.41 09/98 Bobbin NQI 0.34 15C
+6.99 6 51 09/98 Bobbin HNI 0 33 10C
+2.65 09/ 8 Bobbin-HNC 13 0.84 10C
+26.09 9
6 90 Of/98 Bobbin ADI 0.73 02H
+8.82 09/38 Bobbin ODI 5
0.56 10C
+10.40-6 111'09/98 Bobbin ADI 1.88 03H
+18.73 l
7 6 09/98 Bobbin HNI 2.54 13C
+27.75' 7
8 09/98 Bobbin HNI 0.49 04H
+10.49 09/98 Bobbin HNI 0.56 04H
+13.08 7 26 09/98 Bobbin HNC 6 '1.11 03H
+21.06 7 33 09/98 Bobbin HNI 0.36 02H
+30.61 09/98 Bobbin HNC 15 0.46 05H
+35.78 7 36 09/98 Bobbin ODI 14 0.79 11C
+13.28 7 51 09/98 Bobbin HNC 22 0.52 10C
+3.37 l
09/98 Bobbin ODI 3
0.69 06H
+36.10 7 52 09/98 Bobbin NQI 0.86 07H
+19.70 09/98 Bobbin HNC 1
2.46 10C
+21.27 09/98 Bobbin HNC 13 0.54 10C
+29.59 l
7 6*2 09/98 Bobbin HNI 1.12 15C
+9.34 09/98 C/L Special Interest VOL 0.87 15C
+11.00 7 71 09/98 Bobbin NOI 0.25 16C
+3.74 7 82 09/98 Bobbin HNC 15 3.13 TSC
+5.87 09/98 C/L Special Interest VOL 1.33 TSC
+5.40
-7 101 09/98 Bobbin HNC 7
7.68 14C
+14.65 8 85 09/98 Bobbin HNC 15 1.65 11C
+3.40 09/98 C/L Special Interest VOL 1.03 11C
+2.93 1
8 93 09/98 Bobbin HNI 0.76 TSC
+2.95 l
09/98 Bobbin ODI 24 0.52 TSC
+5.70 1
09/98 C/L Special Interest VOL 0.31 TSC
+5.32 J
-8 103 09/98 Bobbin HNI 3.56 14C
+2.65 1
09/98 C/L Special Interest VOL 1.38 14C
+2.45
-J
.8 112 09/98 Bobbin HNI 0.44 O1H
+2.45 I
9 34 09/98 Bobbin NOI 0.23 12C
+12.70 9 46.09/98 Bobbin HNC 3
0.79 13C
+25.67 9 47 09/98 Bobbin HNI 0.95 02H
+17.11 09/98 H/L Special Interest VOL 2.30 02H
+17.52 9 70 09/98 Bobbin HNI 0.52 07H
+13.08 9 - 85 09/98 Bobbin HNI 4.33 O1H
+10.49 9 106 09/98 Bobbin ODI 26 0.50 18C
+2.48 09/98 C/L Special Interest VOL 0.61 18C
+2.48 9 112 09/98 Bobbin HNC 15 0.49 17C
+7.56 10 5 09/98 Bobbin ODI 5
0.35 10C
+20.44 10 6 09/98 Bobbin HNC 18 0.45 10C
+30.23 10 13 09/98 Bobbin ODI 13 0.61 07H
+34.06 10 17 09/98 Bobbin DWI 2.14 06H
+14.93 09/98 Bobbin NOI 0.42 10C
+6.65 1-10 70 09/98 Bobbin HNI 0.23 13C
+1.98 1
09/98 Bobbin HNC 1
0.97 13C
+6.39 09/98 Bobbin ODI 5
0.20 14C
+5.14 10 75 09/98 Bobbin HNC 8
1.31 10C
+42.47 L
. 09/98 C/L Special Interest VOL 1.70 09C
-3.34 i
10- 81 09/98 Bobbin ODI 30 0.40 17C
+1.24 10 113 09/98 Bobbin HNC 5
0.47 13C
+11.71 11 5 09/98 Bobbin HNC 29 0.31 10C
+33.47 l
11' 12 09/98 Bobbin ADI 0.79 04H
+23.01
]
11 59 09/98 Bobbin HNI 0.43 13C
+5.96 09/98 Bobbin HNI 0.82 12C
+19.58 d
09/98 - Bobbin ENI 1.48 14C
+5.62 i
-09/98 Bobbin HNC 16 1.72 11C
+3.90 09/98 Bobbin HNC 26 1.53 15C
+5.65 11 110 09/98 Bobbin HNI 0.44 11C
+26.74 f
,,y
..w,
-m
t FTI TUBAN II (Version 2.3) 01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 12 16 09/98 Bobbin HNI 0.59 11C
+16.03 12 32 09/98 Bobbin HNI 1.40 04H
+5.36 09/98. H/L Special Interest VOL-3.96 04H
+5.05 12 33 09/98 Bobbin ODI 13 0.33 11C
+8.03 12 88 09/98 Bobbin HNI 0.66 10C
+25.85 12 91 09/98 Bobbin HNI 0.48 07H
+17.70 09/98 Bobbin HFC 11 0.48 07H
+20.67 09/98 Bobbin HN? '26 0.37 10C
+12.63 l
12'113 09/98 Bobbin OD1 11 0.25 13C
+7.17 13 11 09/98 Bobbin HF1 0.30 10C
+44.25 09/98 Bobbin HUC 25 0.22 10C
+44.03 j
13 0.3 09/98 Bobbin N2I 0.85 04H
+3.04 09/98 Bobbin ODI 26 0.55 11C
+20.00 09/98 Bobbin ODI 31 0.33 15C
+2.77 09/98 Bobbin ODI 38 0.50 13C
+31.62 13 43 09/98 Bobbin HNC 34 0.26 13C
+22.64 l
13 44 09/98 Bobbin HNI 4.52 03H
+13.29 13 50 09/98 Bobbin NQI 1.59 06H
+25.64 09/98 Bobbin ODI 11 1.04 04H
+20.08 13 89 09/98 Bobbin HNI 0.54 TSH
+3.92 13 93 09/98 Bobbin HNI 0.36 O1H
+2.55 l
13 96 09/98 Bobbin HNI 0.88 12C
+14.43 13 99 09/98 Bobbin HNI 0.35 09C
-0.69 13 100 09/98 Bobbin HNI 0.88 05H
+18.07 09/98 Bobbin HNI 1.49 O1H
+22.56 i
09/98 Bobbin HNC 10 0.55 16C
+8.98 5
09'98 Bobbin ODI 13 0.46 12C
+4.09 09/98 C/L Special Interest VOL 0.37 16C 48.79 13 104 09/98 Bobbin HNC 5
0.86 05H
+28.60 14 3 09/98 Bobbin HNI 0.38 11C
+41.43 14 5 09/98 Bobbin HNI 0.84 14C
+2.82 09/98 Bobbin ODI 27 0.29 07H
+38.98 14 9 09/98 Bobbin HNI 0.69 12C
+8.71 14 12 09/98 Bobbin ADI 0.81 12C
+13.79 l
09/98 Bobbin HNI 0.72 12C
+16.15 09/98 Bobbin HNI 1.04 12C
+11.02 i
14 15 09/98 Bobbin NOI 0.41 07H
+15.73 14 20 09/98 Bobbin ODI 17 0.48 07H
+11.43 14 26 09/98 Bobbin HNI 0.82 18C
+10.32 l
14 31 09/98 Bobbin HNC 8
0.36 13C
+15.92 14 34 09/98 Bobbin HNI 0.96 05H
+25.11 14 45 09/98 Bobbin ODI 30 0.24 10C
+40.55 14 53 09/98 Bobbin HNC 9
0.34 14C
+9.02 14 69 09/98 Bobbin NQI 0.38 07H
+42.88 14 89 09/98 Bobbin HNI 2.87 16C
+9.16 14 92 09/98 Bobbin HNC 28 0.92 07H
+11.00 09/98 H/L Special Interest VOL 1.32 07H
+11.36 14 94 09/98 Bobbin HNC 11 0.47 07H
+17.27 09/98 Bobbin HNC 28 0.30 07H
+32.56 14 96 09/98 Bobbin HNI 1.07 07H
+43.2?
09/98 Bobbin HNC 10 0.37 10C
+39.05 14 105 09/98 Bobbin ADI 0.90 19C
+1.25 7
09/98 Bobbin NQI 0.17 16C
+8.82 09/98 Bobbin HNC 12 1.42 O1H
+6.50 15 14 09/98 Bobbin HNI 0.44 13C
+22.96 l
15 35 09/98 Bobbin HNI 0.35 11C
+10.24
-09/98 Bobbin HNI 0.46 12C
+25.78 09/98 Bobbin HNI 0.75 11C
+7.24 15 55 09/98 Bobbin HNI 0.31 07H
+29.02 l
15 58 09/98 Bobbin ODI 15 0.28 10C
+25.00 l
15 70 09/98 Bobbin HNI 1.52 12C
+31.10 l
09/98 C/L Special Interest VOL 0.64 11C
-13.66 09/98 C/L Special Interest VOL 1,43 11C
-12.11 15 78 09/98 Bobbin ODI 21 0.40 14C
+9.00 15 79 09/98 Bobbin HNC 22 1.79 15C
+2.27
FTI TUBAN ZI (Version 2.3) 01/31/1999 11:25:38 Catawba Wuclear Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 5 ATTACID!ENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 C/L Special Interest VOL 1.23 15C
+2.56 15 102 09/98 Bobbin HNI 1.05 18C
+13.47 15 104 09/98 Bobbin ODI 5
0.34 07H
+29.69 15 107 09/98 Bobbin HNC 2
0.64 10C
+27.80 09/98 Bobbin HNC 35 0.30 10C
+26.55 09/98 Bobbin ODI 14 0.64 06H
+37.53 16 8 09/98 Bobbin ODI 38 0.23 07H
+37.47 16 47 09/98 Bobbin ADI 1.14 15C
+7.38 09/98 Bobbin ADI 1.17 15C
+5.86 16 59 09/98 Bobbin HNI 1.43 O1H
+21.94 09/98 H/L Special Interest VOL 2.41 O1H
+21.94 16 71 09/98 Bobbin HNC 20 0.39 04H 49.08 09/98 H/L Special Interest VOL 0.75 04H
+9.11 16 73 09/98 Bobbin NOI 0.26 O1H
+6.27 16 89 09/98 Bobbin HNC 1
1.40 11C
+30.46 09/98 Bobbin HNC 8
0.92 11C
+36.06 09/98 Bobbin ODI 34 0.35 17C
+1.91 16 92 09/98 Bobbin HNI 0.33 11C
+16.31 09/98 C/L Special Interest VOL 0.55 11C
+16.83 16 103 09/98 Bobbin HNC 22 0.55 16C
+15.52 09/98 C/L Special Interest VOL 0.92 16C
+15.52 16 104 09/98 Bobbin NQI 0.33 03H
+34.53 09/98 Bobbin NOI 0.55 03H
+26.43 i
09/98 Bobbin HNC 8
1.10 04H
+20.49 09/98 Bobbin HNC 9
1.01 04H
+3.96 09/98 Bobbin HNC 12 0.89 04H
+9.01 09/98 Bobbin ODI 14 1.35 TSH
+2.41 09/98 H/L Tubesheet VOL 1.38 TSH
+1.87 09/98 H/L Special Interest VOL 1.43 TSH
+2.08 17 19 09/98 Bobbin ODI 7
0.38 07H
+22.49 09/98 Bobbin ODI 12 0.38 07H
+20.58 09/98 Bobbin ODI 18 0.35 07H
+14.24 17 22 09/98 Bobbin HNC 17 0.32 11C
+18.64 17 31 09/98 Bobbin HNC 31 0.33 07H
+41.96 17 33 09/98 Bobbin NQI 0.41 03H
+32.73 09/98 Bobbin NQI 0.56 03H
+31.17 17 55 09/98 Bobbin HNC 13 0.98 05H
+24.03 17 72 09/98 Bobbin HNI 0.00 12C
+3.87 09/98 C/L Special Interest VOL 0.44 12C
+4.22 17 105 09/98 Bobbin ADI 5.66 AV4
+10.30 18 4 09/98 Bobbin HNI 1.24 10C
+22.42 l
09/98 Bobbin NQI 0.23 07H
+40.78 09/98 Bobbin HNC 26 1.03 10C
+41.49 09/98 Bobbin ODI 1R 0.50 07H
+42.78 18 6 09/98 Bobbin HNI 2.07 04H
+38.21 18 15 09/98 Bobbin HNI 0.31 12C
+19.25 18 19 09/98 Bobbin NQI 0.61 10C
+45.24 09/98 Bobbin HNC 16 0.44 11C
+30.31 18 20 09/98 Bobbin NQI 0.50 07H
+22.47 09/98 Bobbin NOI 0.66 07H
+30.68 l
18 26 09/98 Bobbin HNI 0.78 05H
+20.66 09/98 Bobbin HNI 0.93 05H
+16.85 18 48 09/98 Bobbin HNI 0.52 02H
+33.71 18 49 09/98 Bobbin ODI 11 1.56 13C
+5.89 18 52 09/98 Bobbin HNC 9
0.73 11C
+3.80 j
09/98 Bobbin HNC 18 0.86 11C
+7.69 18 55 09/98 Bobbin HNC 2
1.21 12C
+26.12 09/98 C/L Special Interest VOL 0.80 12C
+26.12 18 59 09/98 Bobbin HNI O.93 14C
+16.76 09/98 Bobbin HNI 0.63 12C
+9.98 to
+23.08 i
09/98 C/L Special Interest VOL 1.18 12C
+9.98 to
+23.08 18 65 09/98 Bobbin HNC 4
1.50 02H
+8.70 09/98 Bobbin ODI 9
0.88 02H
+18.32 l
09/98 H/L Special Interest VOL 0.52 02H
+8.51 18 87 09/98 Bobbin HNI 4.12 13C
+38.19
k FTI TUBAN II (Version 2.3) 01/21/1999 11:74 38 Catawba Nuclear Station - Unit Two j
S/G B l
09/98 RPO r
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 6 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB I
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION f
09/98 C/L Special Interest VOL 0.92 12C
-5.19 18 89 09/98 Bobbin HNI 0.67 04H
+22.43 i
18 105 09/98 Bobbin HNC 13 0.64 10C
+12.86 i
19 8 09/98 Bobbin-ADI 1.49 06H
+20.14 19 10 09/98 Bobbin ODI 17 0.53 12C
+9.42' 19 12 09/98 Bobbin HNI 1.15 12C
+9.51 19 18 09/98' Bobbin ODI 12 0.40 16C
+9.07 19 31 09/98 Bobbin HNI 0.50 03H
+10.90
(
19 41 09/98 Bobbin HNI 2.34 01H
+4.63 19 53 09/98 Bobbin ADI 0.37 18C
+14.33 09/98 Bobbin HNI 0.35 14C
+9.33 l
09/98 Bobbin HNC 13 0.60 14C
+10.68 3
19 56 09/98 Bobbin ODI 2
1.22 02H
+18.16 19 57 09/98 Bobbin HNI 0.56 03H
+30.22 09/98. Bobbin HNC 4
0.36 13C
+7.10 09/98 Bobbin HNC 6
0.56 13C
+6.62 19 73 09/98 Bobbin NOI 0.31 10C
.+20.28 19 75 09/98 Bobbin HNI 0.64 12C
+19.83 19 83 09/98 Bobbin HNC 4
0.74 03H
+21.89 09/98 H/L Special Interest VOL 2.33 03H
+21.84 19 87 09/98 Bobbin HNI 0.57 16C
+4.03 19 94 09/98 Bobbin HNI 0.21 10C
+41.55 19 106 09/98 Bobbin HNI 1.71 AV1
+10.12 19 110 09/98 Bobbin HNC 17 0.40 07H
+32.88 20 13 09/98 Bobbin HNC 12 0.79 11C
+37.74 20 17 09/98 Bobbin HNC 3
0.77 17C
+3.61 20 18 09/98 Bobbin NOI 0.21 05H
+0.73 20 34 09/98 Bobbin ODI 15 0.57 O1H
+6.78 20 37 09/98 Bobbin HNI 0.30 15C
+11.40 09/98 Bobbin HNI 0.67 11C
+38.92 09/98 Bobbin HNI 0.78 10C
+35.16 20 62 09/98 Bobbin ADI 0.77 13C
+8.35 09/98 Bobbin HNI 1.49 16C
+2.47
.0 82 09/98 Bobbin HNC 10 1.34 11C
+37.38 20 86 09/98 Bobbin HNI 0.64 11C
+13.38 09/98 Bobbin HNI 1.15 07H
+34.07 20 95 09/98 Bobbia ODI 13 0.22 06H
+17.36 20 96 09/98 Bobbin HNC 3
1.71 12C
+27.34 20 104 09/98 H/L Tubesheet VOL 0.79 TSH
+0.07 l
20 106 09/98 Bobbin HNC 15 1.01 06H
+3.46 l
20 107 09/98 Bobbin ODI 5
0.48 10C
+42.39 20 110 09/98 Bobbin ODI 27 0.48 TSH
+3.70 21 15 09/98 Bobbin ODI 8
1.52 18C
+4.70 l
21 18 09/98-Bobbin ODI 15 0.30 07H
+30.44 l
09/98 Bobbin ODI 20 0.34 11C
+41.17 i
21 20 09/98 Bobbin ADI 1.30 11C
+3.69 l
09/98-Bobbin ADI 3.06 10C
+36.13 21 26 09/98 Bobbin HNI 0.43 13C
+34.32 21 30 09/98 Bobbin HNI 0.75 16C
+15.20 21 34 09/98 Bobbin HNC 15 0.23 19C
+4.34 21
'36 09/98 Bobbin HNC 26 0.71 02H
+34.02 21 38 09/98 Bobbin HNI 0.41 17C
+13.08 21 45 09/98 Bobbin HNC 10 0.30 18C
+5.86 09/98 Bobbin HNC 20 0.38 11C
+36.10 21 49 09/98 Bobbin HNC 10 0.95 17C
+5.27 21 56 09/98 Bobbin HNI 4.89 12C
+24.50 21 49 09/98 Bobbin HNI 0.67 08H
+0.36 t
21 60 09/98 Bobbin HNC 4
0.67 15C
+15.70 1
09/98 Bobbin HNC 5
0.84 15C
+10.56 i
21 78 09/98 Bobbin HNC 9
1.00 02H
+28.54 21 79 09/98 Bobbin HNC 15 1.8~ 16C
+13.23 09/98 C/L Special Interest VOL 1.44 16C
+13.26 4
21 83 09/98 Bobbin ODI 3
0.73 10C
+14.65 09/98 Bobbin ODI 12 0.48 10C
+24.54 21 100 09/98 Bobbin ODI B
1.19 05H
+25.80
i l
FTI TUBAN II (Version 2.3) 01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two i
S/G B I
09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 7 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 22 15 09/98 Bobbin HNC 20 0.95 12C
+37.66 09/98 Bobbin ODI 6
1.62 15C
+16.43 22 24 09/98 Bobbin HNI 0.49 03H
+9.92 22 28 09/98 Bobbin HNI 0.38 18C
+13.91 09/98 Bobbin HNI 0.80 18C
+12.72 22 30 09/98 Bobbin ODI 13 2.13 02H
+22.35 22 42 09/98 Bobbin HNI 0.65 TSC
+7.69 22 97 09/98 Bobbin HNC 17 2.73 03H
+6.00 22 109 09/98 Bobbin HNC 12 0.64 11C
+35.29 23 7 09/98 Bobbin NQI 0.38 12C
+4.24 09/98 Bobbin ODI 17 0.91 12C
+12.11 23 15 09/98 Bobbin HNI 0.51 18C
+15.75 23 19 09/98 Bobbin ODI 24 0.29 07H
+33.22 23 20 09/98 Bobbin NOI 0.34 07H
+34.26 09/98 Bobbin HNC 6
1.37 09C
+11.31 23 25 09/98 Bobbin HNI 0.67 10C
+26.30 23 29 09/98 Bobbin HNC 9
0.48 15C
+7.47 23 32 09/98 Bobbin HNI 1.08 12C
+39.54 2? 79 09/98 Bobbin NOI 0.49 12C
+25.03 23 85 09/98 Bobbin HNI 0.14 12C
+25.82 23 86 09/98 Bobbin HNI 1,53 O1H
+18.22 23 99 09/98 Bobbin HNI 2.71 09C
+17.17 23 108 09/98 Bobbin HNI 0.32 O1H
+14.85 24 7 09/98 Bobbin ODI 3
0.47 07H
+3.94 24 15 09/98 Bobbin ODI 6
0.40 18C
+2.06 24 24 09/98 Bobbin HNI 0.67 02H
+1.66 i
24 45 09/98 Bobbin HNC 6
0.47 07H
+19.63 24 52 09/98 Bobbin ADI 3.21 12C
+5.92 09/98 Bobbin NOI 0.29 TSH
+8.08 24 55 09/98 Bobbin HNI 0.73 10C
+36.16 09/98 Bobbin NOI 0.29 TSC
+5.54 24 63 09/98 Bobbin HNI 2.20 17C
+14.82 09/98 C/L Special Interest VOL 0.80 17C
+14.54 24 66 09/98 H/L Tubesheet VOL 0.39 TSH
+0.22 24 68 09/98 Bobbin HNI 2.88 19C
+4.23 24 86 09/98 Bobbin ODI 14 0.37 07H
+42.62 24 91 09/98 Bobbin HNI 3.48 02H
+4.05 1
09/98 Bobbin HNI 2.86 13C
+23.75 to
+37.99 09/98 H/L Special Interest VOL 2.53 02H
+4.97 24 94 09/98 Bobbin HNC 7
1.08 12C
+31.96 09/98 Bobbin HNC 12 0.57 02H
+19.15 24 99 09/98 Bobbin HNI 1.88 04H
+2.50 24 108 09/98 Bobbin ODI 13 0.94 AV4
+8.68 25 8 09/98 Bobbin HNC 6
1.16 13C
+8.22 09/98 C/L Special Interest VOL 0.98 13C
+8.55 25 10 09/98 Bobbin NQI 0.24 14C
+5.64 25 15 09/98 Bobbin ODI 19 0.38 03H
+24.20 25 42 09/98 Bobbin HNI 0.53 03H
+11.41 09/98 Bobbin HNC 4
0.94 01H
+1.01 25 50 09/98 Bobbin HNC 7
1.11 10C
+5.34 l
25 55 09/98 Bobbin HNI 0 82 10C
+18.40 09/98 Bobbin HNC 14 1.24 10C
+18.93 25 67 09/98 Bobbin HNC 24 1.50 09C
+21.50 25 75 09/98 Bobbin ADI 0.97 03H
+17.79 09/98 Bobbin HNC 8
1.66 16C
+7.91 09/98 Bobbin HNC 15 0.59 16C
+13.40 09/98 C/L Special Interest VOL 0.55 16C
+13.33 09/98 C/L Special Interest VOL 1.23 16C
+7.98 25 81 09/98 Bobbin HNI 1.27 10C
+23.16 09/98 Bobbin HNI 1.11 13C
+38.53 to
+41.86 09/98 Bobbin HNI 2.45 12C
+5.15 to
+37.90 09/98 C/L Special Interest VOL 1.33 10C
+23.03 09/98 C/L Special Interest VOL 0.73 12C
+4.40 to
+12.10 I.
09/98 C/L Special Interest VOL 0.97 12C
-5.38 to
-1.03 09/98 C/L Special Interest VOL 1.16 12C
+28.47 to
+38.25 3
. -.. _ ~. -..
.~.
l FTI TUBAN II (Version 2.3) 01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two i
S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion ePt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC 1
ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 25 85 09/98 : Bobbin HNI 3.29 OBH
+13.94 l
25 86 09/98 Bobbin ODI 14 0.51 10C
+18.75 l
25 88 09/98 Bobbin HNI 1.47 05H
+20.90 09/98 H/L Special Interest VOL 2.36 05H
+20.80 l
25 91 09/98 Bobbin NQI 0.22 07H
+23.28 l
26 8 09/98 Bobbin HNI 0.97 06H
+35.98 26 29 09/98 Bobbin HNI 0.59 06H
+2.93 09/98 H/L Special Interest VOL 1.36 06H
+2.87 l
09/98 H/L Special Interest VOL 1.59 06H
+3.65 26 38 09/98 Bobbin HNI 1.71 16C
+6.87 09/98 C/L Special. Interest VOL 0.59 16C
+6.62 26 50 09/98 Bobbin ADI 2.35 08H
+20.58 09/98. Bobbin ADI 2.70 08H
+17.27 09/98 Bobbin ADI 1.64 12C
+27.66 to
+38.59 09/98 C/L Special Interest VOL 0.13 11C
-15.34 to
-4.41 26 52 09/98 Bobbin HNI 0.71 17C
+7.02 26 54 09/98 Bobbin ADI 1.14 15C
+1.97 09/98 C/L Special Interest VOL 0.33 15C
+1.56 26 61 09/98 Bobbin ADI 1.15 12C
+13.95 26 62 09/98 Bobbin ADI 3.47 12C
+12.01 09/98 C/L Special Interest VOL 0.94 12C
+12.00 26 66 09/98 Bobbin HNI 0.54 12C
+23.12 09/98 Bobbin HNI 2.57 02H
+15.59 26 83 09/98 Bobbin HNI 1.25 17C
+4.49 09/98 Bobbin ODI 13 0.54 18C
+4.34 26 86 09/98 Bobbin HNI 0.46 01H
+13.36 09/98 Bobbin HNI 0.61 11C
+5.61 09/98 Bobbin HNI 0.98 15C
+7.98 09/98 Bobbin ODI 20 0.85 03H
+20.02 09/98 Bobbin HNI 0.59 10C
+37.58 to
+40.13 09/98 Bobbin HNI 0.83 16C
+5.21 to
+7.27 09/98 Bobbin HNI 1.28 18C
+14.48 to
+16.61 09/98 C/L Special Interest VOL 0.49 11C
+5.58 09/98 C/L Special Interest VOL 0.53 16C
+5.96 09/98 C/L Special Interest VOL 0.58 15C
+8.29 09/98 C/L Special Interest VOL 0.58 16C
+7.12 09/98 C/L Special Interest VOL 0.65 18C
+15.51 09/98 C/L Special Interest VOL 0.80 18C
+16.71 09/98 C/L Special Interest VOL 0.91 10C
+37.59 to
+40.13 26 96 09/98 Bobbin HNI 1.19 07H
+43.07 26 102 09/98 Bobbin ODI 19 0.70 07H
+42.99 26 105 09/98 Bobbin HNI 0.70 OBH
+12.68 27 10 09/98 Bobbin HNC 18 1.77 10C
+43.21 27 27 09/98 Bobbin HNI 2.15 10C
+43.38 27 31 09/98 Bobbin HNI 1.50 O1H
+27.36 27 39 09/98. Bobbin HNC 8
1.05 02H
+22.16 27' 43 09/98 Bobbin HNC 28 0.52 12C
+15.10 09/98 Bobbin ODI 8
0.84 12C
+32.81 27 54 09/98 Bobbin HNI 0.84 03H
+11.12 27 55 09/98 Bobbin HNI 0.78 07H
+34.95 09/98 27 60 09/98 ~ Bobbin HNC 20 0.72 07H
+30.92 Bobbin HNC 18 0.52 07H
+43.84 09/98 Bobbin ODI 23 0.94 AV2
+0.00 27 75 09/98 Bobbin HNC 11 0.56 10C
+12.57 27 80 09/98 Bobbin
.HNI 0.42 11C
+14.53 28 9'09/98 Bobbin NOI 0.22 14C
+13.64 28 35 09/98 Bobbin HNC 10 1.00 17C
+1.73 09/98 C/L Special Interest VOL 1.21 17C
+1.70 28 37 09/98 Bobbin NQI-0.41 AV1
+9.20 l
28 42 09/98 Bobbin HNC 11 1.07 07H
+25.72 l
28 52 09/98 Bobbin HNI 0.60 11C
+26.83 l
28 59 09/98 Bobbin NQI 0.31 09C
-1.14 28 84 09/98 Bobbin HNI 1.43 10C
+39.57 09/98 Bobbin HNI 1.90 16C
+6.82 28 85 09/98 Bobbin HNI 0.33 08H
+0.75
. ~
}
FTI TUBAN II (Vareion 2.3) 01/21/1999 11:25:38 Catawba Nuclonr Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&18,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCITION 28 93 09/98 Bobbin HNI 2.66 AV1
+15.77 28 94 09/98 Bobbin HNI 0.58 07H
+44.85 09/98 Bobbin HNC 30 0.33 12C
+18.31 29 55 09/98 Bobbin ADI 0.38 07H
+30.44 09/98 Bobbin ADI 1.10 07H
+31.58 09/98 Bobbin NOI 0.36 12C
+25.12 09/98 Bobbin ODI 7
0.46 10C
+33.01 09/98 Bobbin ODI 20 0.29 10C
+32.45 29 61 09/98 Bobbin ODI 15 0.59 04H
+15.32 29 67 09/98 Bobbin HNC 16 1.35 O1H
+8.24 09/98 Bobbin HNC 18 1.53 01H
+7.95 29 68 09/98 Bobbin HNC 5
0.92 06H
+35.21
)
29 85 09/98 Bobbin HNI 0.85 03H
+26.65 09/98 Bobbin NOI 0.29 03H
+25.37 29 88 09/98 Bobbin ODI 6
0.87 07H
+14.76 29 95 09/98 Bobbin HNC 14 0.43 03H
+15.22 09/98 Bobbin ODI 8
0.47 02H
+34.33 29 98 09/98 Bobbin HNC 6
1.33 13C
+34.78 09/98 C/L Special Interest VOL 0.82 12C
-8.64 29 102 09/98 Bobbin HNI 0.32 10C
+43.90 29 104 09/98 Bobbin HNC 3
1.90 13C
+39.62 09/98 Bobbin ODI 7
1.24 12C
+5.58 09/98 C/L Special Interest VOL 0.64 12C
+5.93 j
09/98 C/L Special Interest VOL 0.97 12C
-3.38 30 12 09/98 Bobbin ODI 14 0.41 19C
+7.55 30 25 09/98 Bobbin NOI 0.39 19C
+3.77 09/98 Bobbin ODI 12 0.33 19C
+2.17 30 31 09/98 Bobbin HNI 0.50 OBH
+6.24 30 52 09/98 Bobbin HNI 1.47 18C
+B.84 09/98 C/L Special Interest VOL 0.74 18C
+8.76 30 64 09/98 Bobbin HNI 1.86 TSC
+2.27 09/98 Bobbin HNC 12 2.79 02H
+13.55 09/98 Bobbin HNC 19 0.76 02H
+7.20 30 68 09/98 Bobbin HNC 3
0.61 02H
+18.05 30 73 09/98 Eobbin HNI 0.92 12C
+15.34 09/98 Bobbin HNI 0.93 10C
+5.00 09/98 Bobbin HNC 17 0.73 12C
+10.89 09/98 Bobbin HNC 23 1.54 04H
+20.08 09/98 C/L Special Interest VOL 0.66 12C
+10.93 09/98 C/L Special Interest VOL 0.94 12C
+15.75 09/98 C/L Special Interest VOL 1.64 10C
+5.03 30 89 09/98 Bobbin HNI 0.86 18C
+15.83 09/98 C/L Special Interest VOL 1.59 18C
+15.83 30 94 09/98 Bobbin HNC 9
0.75 10C
+36.23 09/98 C/L Special Interest VOL 0.48 10C
+36.03 30 95 09/98 Bobbin HNI 0.79 AV4
+7.24 09/98 Bobbin NQI 0.96 09C
+21.02 09/98 Bobbin HNC 21 0.97 AV4
+11.11 30 104 09/98 Bobbin WAR 15 0.54 AV3
-0.26 31 19 09/98 Bobbin NQI 0.64 17C
-0.48 09/98 Bobbin HNC 20 0.57 10C
+42.53 09/98 C/L Special Interest VOL 1.75 17C
-0.43 31 31 09/98 Bobbin HNC 6
1.14 11C
+18.76 09/98 C/L Special Interest VOL 0.85 11C
+18.11 31 32 09/98 Bobbin HNC 8
1.17 16C
+6.49 31 60 09/98 Bobbin NOI O.38 09C
-1.55 31 70 09/98 Bobbin HNI 0.54 O1H
+4.88 09/98 Bobbin HNI 0.85 O1H
+7.25 31 78 09/98 Bobbin HNC 8
1.74 07H
+14.00 09/98 H/L Special Interest VOL 2.13 07H
+13.79 31 83 09/98 Bobbin HNI 1.84 17C
+12.60 09/98 C/L Special Interest VOL 1.03 17C
+12.60 31 94 09/98 Bobbin HNI 1.15 02H
+26.89 31 101 09/98 Bobbin HNC 13 0.75 18C
+5.46 32 14 09/98 Bobbin HNC 8
0.73 13C
+10.89 i
~. -
. - - ~ ~.
. ~.. -.
l l
FTI TUBAN II (Version 2.3) 01/21/1999 11:25:38 i
Cctewba Nuclecr Station - Unit Two S/G B 09/98 RFO Robbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC i
Page 10 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB-ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 C/L Special Interest VOL 2.23 13C
+10.89 32 19 09/98 Bobbin NQI 0.46 08H
-0.44 32 25 09/98 Bobbin AD1 3.05 13C
+24.63 l
09/98 C/L Special Interest VOL 1.48 13C
+25.01 l
32 53 09/98 Bobbin HNI 3.23 07H
+14.44 32 60 09/98 Bobbin KNC 15 0.72 04H
+23.26 09/9B Bobbin ODI 15 0.93 05H
+29.62 09/98 H/L Special Interest VOL 1.18 06H
-13.38 32 75 09/98 Bobbin ODI 20 0.28 03H
+16.32 32 80 09/98 Bobbin ADI 0.97 12C
+9.51 32 83 09/98 Bobbin HNI 0.24 11C
+33.27 09/98 C/L Special Interest VOL 1.25 11C
+33.27 32 90 09/98 Bobbin HNC 11 0.85 18C
+13.11 09/98 C/L Special Interest VOL 1.50 18C
+13.11 32 93 09/98 Bobbin HNC 16 1.73 05H
+25.54 32 101 09/98 Bobbin HNI 0.59 03H
+6.04 32 103 09 98 Bobbin WAR 9
0.28 AV3
+0.00 09 98 Bobbin WAR 11 0.38 AV2
+0.00 l
09 98 Bobbin WAR 12 0.40 AV4
+0.00 33 14 09/98 Bobbin HNI 0.72 07H
+35.48 i
33 17 09/98 Bobbin HNI 0.87 07H
+43.63 l
09/98 Bobbin HNC 22 0.99 07H
+41.93 33 65 09/98 Bobbin HNC 14 2.59 18C
+15.60 09/98 Bobbin CDI 19 0.47 12C
+15.46 33 69 09/98 Bobbin HNC 26 0.50 08H
+1.15 33 71 09/98 Bobbin HNC 19 1.78 08H
+1.43 l
l 33 72 09/98 Bobbin HNC 11 1.74 08H
+1.73 t
33 79 09/98 Bobbin HNI 2.02 07H
+31.36 I
33 80 09/98 Bobbin HNI 1.14 13C
+25.86 i
09/98 C/L Special Interest VOL 1.31 13C 425.86 l
33 86 09/98 Bobbin HNI 0.40 03H
+30.87 09/98 Bobbin HNI 0.45 11C
+13.14 09/98 Bobbin HNI 0.60 05H
+8.42 09/98 Bobbin ODI 7
0.37 06H
+14.59 09/S8 C/L Special Interest VOL 0.35 11C
+13.50 33 94 09/98 Bobbin HNI 1.14 02H
+2.40 to
+13.84 33 95 09/98 Bobbin KNI 0.46 04H
+9.35 to
+17.47 33 103 09/98 Bobbin WAR 11 0.37 AV1
-0.19 34 35 09/98 Bobbin HNC 6
0.53 11C
+8.18 34 37 09/98 Bobbin ODI B
0.28 11C
+32.30 34 62 09/98 Bobbin ODI 4
2.58 10C
+25.43 09/98 Bobbin ODI 6
0.48 12C
+33.98 09/98 C/L Special Interest VOL 2.33 10C
+24.25 34 81 09/98 Bobbin HNI 2.76 O1H
+5.50 34 92 09/98 Bobbin KNC 11 0.89 O1H
+20.70 1
34 96 09/98 Bobbin HNI 0.63 04H
+0.00 to
+9.89 l
09/98 Bobbin HNI 1.43 03H
+25.77 to
+34.31 34 100 09/98 Bobbin ODI 6
1.52 07H
+29.2?
l 09/98 H/L Special Interest VOL 1.94 07H
+29.20 l
35 16 09/98 H/L Tubesheet VOL 0.35 TSH
+0.02 35 34 09/98 Bobbin HNC 21 1.90 O1H
+5.46 35 35 09/98 Bobbin HNC 22 0.52 07H
+15.95 35 37 09/98 - Bobbin HNC 6
0.63 12C
+34.45 09/98 C/L Special Interest VOL 1.49 12C
+34.13 i
35 41 09/98 Bobbin NOI 0 84 O1H
+0.42 09/98 H/L Special Interest VOL 0.86 01H
+0.55 L
35 42 09/98 Bobbin ODI 33 0.26 12C
+38.45 l
35 48 09/98 Bobbin HNC 18 0.80 15C
+11.74 i
09/98 C/L Special Interest VOL 0.82 15C
+11.74 1
35 60 09/98 Bobbin HNI 0.49 04H
+27.01 35 64 09/98 Bobbin HNC 28 0.64 11C
+14.06 4
35 66 09/98 Bobbin KNI 0.44 TSH
+3.25 09/98 H/L Special Interest VOL 1.21 TSH
+2.96 35 81 09/98 Bobbin HNI 0.41 12C
+1.24 09/98 C/L Special Interest VOL 0.64 12C 41.15 i
t
_-_.--.-_...-.--_.._n l
FTI TUBAN II (Varmion 2.3) 01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two S/G B-09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 11 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 35 91 09/98 Bobbin HNI 0.34 18C
+1.17 35 93 09/98 Bobbin HNI 0.41 12C
+35.43 to
+40.15 36 16 09/98 Bobbin NQI 0.38 06H
+24.54 09 98 Bobbin NOI 0.42 07H
+3.26 09 98 H/L Tubesheet VOL 0.13 TSH
+0.04 09 98 Bobbin ADI 1.39 07H
+23.13 to
+28.31 36 24 09 98 Bobbin ADI 1.53 AV4
+2.81 09/98 Bobbin ADI 3.14 AV4
+5.27 36 29 09/98 Bobbin HNI 0.63 15C
+12.57 36 34 09/98 ' Bobbin HNI 0.84 06H
+36.93 09/98 H/L Special Interest VOL 1.51 06H
+36.71 36 35 09/98 Bobbin NQI 0.55 07H
+8.82 09/98 Bobbin HNC 14 0.91 07H
+28.14 36 63 09/98 Bobbin HNI 0.39 19C
+6.54 l
09/98 Bobbin HNI 0.54 19C
+3.98 09/98 H/L Tubesheet VOL 0.77 TSH
+0.07 36 79 09/98 Bobbin HNI 0.72 O1H
+14.31 09/98 Bobbin HNI 0.79 05H
+20.71 09/98 Bobbin HNI 1.34 07H
+27.53 09/98 H/L Special Interest VOL 1.30 OGH
+20.88 09/98 H/L Special Interest
.VOL 2.08 01H
+14.14 36 82 09/98 Bobbin HNI 0.56 03H
+0.22 i
09/98 H/L Special Interest VOL 1.62 03H
+0.16
)
l 36 84 09/98 Bobbin HNI 2.08 06H
+29.73 36 94 09/98 Bobbin HNI 0.71 15C
+13.69 09/98 C/L Special Interest VOL 0.80 15C
+14.17 36 97 09/98 Bobbin NQI 0.36 11C
+30.42 36 99 09/98 Bobbin WAR 8
0.29 AV4
+0.00 09/98 UBEND SPEC. INT.
VOL 0.27 AV4
+0.00 37 29 09/98 Bobbin NOI 0.38 06H
+37.96 37' 38 09/98 Bobbin HNC 1
0.96 16C
+5.22 37 40 09/98 Bobbin HNC 4
1.93 19C
+5.10 1
09/98 Bobbin HNC 5
2.16 02H
+32.41 i
09/98 Bobbin HNC 6
1.38 OSH
+25.83 37 44 09/98 Bobbin HNC 5
0.88 02H
+16.34 37 67 09/98 Bobbin HNC 5
1.40 06H
+3.51 37 88 09/98 Bobbin NQI 0.45 AV4
+8.89 37 89 09/98 Bobbin HNC 2
1.84 14C
+11.62 37 96 09/98 Bobbin HNI 2.00 17C
+6.92 37 99 09 98 Bobbin WAR 17 0.61 AV4
+0.00 l
l 38 18 09 98 Bobbin NOI 0.27 08H
-0.71 38 23 09 98 Bobbin COI 25 0.48 TSC
+4.93 l
09 98 C/L Special Interest VOL 0.48 TSC
+4.34 38 24 09/98 Bobbin HNC 3
1.78 11C
+30.94 09/98 Bobbin ODI 21 0.28 07H
+11.43 38 27 09/98 Bobbin HNI 0.65 13C
+4.99 38 36 09/98 Bobbin HNI 0.79 07H
+12.55 38 54 09/98 Bobbin HNI 2.90 O1H
+18.75 38 59 09/98 Bobbin ODI 8
1.40 09C
+9.63 38 62 09/98 Bobbin ODI 12 0.73 07H
+44.55 l
38 64 09/98 Bobbin ODI 6
0.78 18C
+9.32 l
38 65 09/98 Bobbin HNC 6
2.24 18C
+12.31 38 69 09/98 Bobbin HNI 0.89 11C
+29.20 09/98 C/L Special Interest VOL 2.14 11C
+29.20 38 75 09/98 Bobbin HNI 0.46 14C
+7.63 09/98 Bobbin HNC 3
0.89 17C
+13.17 r
09/98 C/L Special Interest VOL 0.88 14C
+7.63 1
38 76 09/98 Bobbin HNI 1.00 04H
+27.91 i
38 80 09/98 Bobbin WAR 8
0.26 AV4
-0.06 09/98 Bobbin WAR 28 1.38 AV1
-0.06 09/98 Bobbin WAR 28 1.39 AV2
-0.04 2
j 09/98 Bobbin WAR 39 2.88 AV3
+0.04 09/98 UBEND SPEC. INT.
VOL 2.02 AV3
+0.00 38 83 09/98 Bobbin HNI 0.28 03H
+5.84 09/98 Bobbin HNI 0.47 03H
+5.24 i
w
~~
.. ~... -.. ~ - -. - - - - - ~ _ - -.. - - -. ~. -. _. -
l l
l FTI TUBAN II (Varsion 2.3) 01/21/1999 11:25:38 i
Catcwb3 Nuclesr Stttion - Unit Two l
S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC
_i l
l l
Page 12 l
ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB RCW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION I
38 85 09/98 Bobbin HNI 0.44 13C
+41.39 09/98 Bobbin HNI 0.47 02H
+11.34 09/98 Bobbin HNI 0.57 02H
+10.24 09/98 Bobbin HNI 1.18 19C
+3.50 09/98 Bobbin HNI 2.55 04H
+4.14 09 98 Bobbin HNC 26 0.72 TSH
+6.54 09 98 H/L Special Interest VOL 1.21 TSH
+6.07 38 86 09 98 Bobbin HNI 0.83 03H
+7.40 09 98 Bobbin HNI 1.60 14C
+13.94 38 92 09/98 Bobbin HNI 1.96 04H
+29.95 39 29 09/98 Bobbin HNC 5
0.51 O1H
+20.98 i
39 35 09/98 Bobbin ODI 21 0.54 10C
+42.81 39 46 09/98 Bobbin HNC 1
1.05 AV1
+14.37 09/98 Bobbin HNC 6
0.94 06H
+31.75 09/98 Bobbin HNC 6
1.28 02H
+7.91 09/98 Bobbin HNC 7
0.98 10C
+8.68 09/98 C/L Special Interest VOL 0.90 10C
+8.80 39 47 09/98 Bobbin ODI 18 0.31 10C
+32.87 l
39 63 09/98 Bobbin ODI 24 0.82 09C
+1.46 39 64 09/98 Bobbin ODI 6
0.88 11C
+21.85 39 70 09/98 Bobbin HNC 28 0.82 08H
+2.10 39 72 09/98 Bobbin HNC 5
0.47 TSC
+3.81 09/98 Bobbin ODI 16 0.52 13C
+39.74 39 75 09/98 Bobbin HNI 0.93 08H
+1.87 39 92 09/98 Bobbin HNC 11 1.31 O1H
+8.57 39 95 09/98 Bobbin NOI 1.95 05H
+10.60 to
+13.04 39 96 09/98 Bobbin ODI 7
1.06 03H-
+25.87 40 18 09/98 Bobbin NQI 0.51 TSH
+1.77
)
40 25 09/98 Bobbin HNC 25 1.48 AV4
+4.54 i
40 26 09/98 Bobbin ODI 14 0.53 03H
+7.30 40 33 09/98 Bobbin HNI 0.63 11C
+3.70 40 37 09/98 Bobbin HNC 5
0.82 13C
+8.20 40 41 09/98 Bobbin ODI 8
0.46 11C
+39.76 40 50 09/98 Bobbin HNC 5
0.53 07H
+44.72 40 59 09/98 Bobbin ADI 3.98 09C
+32.66 40 60 09/98 Bchbin HNC 12 0.66 02H
+10.92 09/98 H/L Special Interest VOL 1.54 02H
+10.96 1
40 80 09/98 Bobbin HNI 0.87 11C
+28.36 40 88 09/98 Bobbin HNI 1.96 AV1
+12.29 41 25 09/98 Bobbin HNC 14 0.98 13C
+2.43 1
41 29 09/98 Bobbin HNI 1.17 03H
+6.56 09/98 Bobbin ODI 5
0.34.11C
+4.56 09/98 H/L Special Interest VOL 2.27 03H
+6.18 41 45 09/98 Bobbin NOI 0.30 11C
+31.35 l
09/98 Bobbin HNC 5
0.88 11C
+35.44 41 50 09/98 Bobbin HNC 19 0.83 TSC
+5.25 09/98 C/L Special Interest VOL 1.21 TSC
+5.20 41 53 09/98 Bobbin HNC 13 2.09 01H
+17.69 09/98 Bobbin ODI 20 1.00 OdH
+16.41 09/98 H/L Special Interest VOL 1.69 O1H
+16.92 j
41 60 09/98 Bobbin LNC 18 0.75 02H
+27.97 i
41 61 09/98 Bobbin NOI 0.31 07H
+29.68 41 76 09/98 Bobbin HNI 3.52 10C
+29.37 to
+32.78 09/98 C/L Special Interest VOL 1.45 10C
+29.37 to
+32.78 1
41 78 09/98 Bobbin HNI 1.94 TSC
+2.01 41 80 09/98 Bobbin HNC 28 1.07 15C
+5.44 09/98 C/L Special Interest VOL 0.99 15C
+5.58 41 84 09/98 Bobbin ADI 2.17 16C
+8.11 09/98 C/L Special Interest VOL 0.45 16C
+8.25 41 92 09/98 Bobbin HNI 0.89 09C
+18.95 41 93 09/98 Bobbin NOI 0.24 11C
+31.22 42 21 09/98 Bobbin NOI 3.42 TSH
+1.40 l
09/98 Bobbin EdC 20 0.31 10C
+2.42 09/98 H/L Special Interest VOL 6.35 TSH
+1.19 42 23 09/98 Bobbin HNI 0.89 16C
+8.52 I
.--.~.
FTI TUBAN II (Varsion 2.3)-
01/21/1999 11:25:38 Catawba Nuclear Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 C/L Special Interest VOL 1.24 16C
+9.01 42 24 09/98 Bobbin ADI 2.01 AV3
+22.61 42 25 09/98 Bobbin ODI 37 0.43 08H
-0.52
'42 30 09/98 Bobbin NQI 0.26 18C
+4.07 09/98 Bobbin ODI 14 0.51 07H
+20.89 42 34 09/98 Bobbin HNI 0.61 09C
+16.78 42 41 09/98 Bobbin HNC 11 0.91 01H
+18.23 42 45 09/98 Bobbin HNC 21' O.67 18C
+0.51 09/98-C/L Special Interest VOL 0.84 18C
+0.51 42 59 09/98 ' Bobbin ODI 6
3.13 12C
+40.19 09/98 C/L Special Interest VOL 1.16 11C
-2.74 42 61 09/98 Bobbin ADI 2.91 04H
+7.87 09/98 Bobbin ADI 4.84 03H
+15.68 42 68 09/98 Bobbin HNC 6
2.41 05H
+31.11
- 42. 86 09/98 Bobbin HNI 0.33 13C
-0.14 42 87 09/98 Bobbin NQI 0.31 14C
+5.03 42 92 09/98 -Bobbin HNC 8
0.33 12C
+20.11 09/98 Bobbin HNC 10 0.42 12C
+18.17 42 93 09/98 Bobbin ODI 8
0.68 01H
+18.76 09/98 Bobbin NQI 2.05 AV1
-11.84 to
+28.20 43 26 09/98 Bobbin ODI 34 0.31 14C
+14.84 09/98 C/L Special Interest VOL 0.39 14C
+14.78 43 39 09/98 Bobbin HNI 0.37 10C
+43.59 09/98 Bobbin HNI 0.51 18C
+14.12 to
+17.36 43 47 09/98 Bobbin HNI 1.84 12C
+15.66 09/98 Bobbin HNC 15 2.33 AV4
+27.14 09/98 C/L Special Interest VOL 1.53 12C
+15.71 43 48 09/98 Bobbin ODI 16 0.29 12C
+15.68 43 50 09/98 Bobbin HNC 8
4.51 13C
+33.31 09/98 C/L Special Interest VOL 2.09 13C
+33.31 43 62 09/98 Bobbin ODI 2
0.92 O1H
+20.63 43 66 09/98 Bobbin HNC 13 1.66 14C
+3.86 09/98 C/L Special Interest VOL 1.20 14C
+13.00 to
+17.68 43 90 09/98 Bobbin HNC 15 0.85 14C
+9.14 43 91 09/98 Bobbin HNC 18 0.50 11C
+8.16 43 93 09/98 Bobbin HNI 0.70 TSH
+3.98 44 23 09/98 Bobbin ODI-16 0.80 19C
+3.55 44 30 09/98 Bobbin HNC 24 0.86 AV1
+30.22 44 33 09/98 Bobbin HNC 23 1.36 17C
+7.42 44 35 09/98 Bobbin ODI 20 0.30 11C
+22.81 44 36 09/98 Bobbin-HNC 17 0.42 07H
+6.69 44 39 09/98 Bobbin HNC 18 1.17 13C
+10.97 l
09/98 C/L Special Interest VOL 1.22 13C
+11.25 44 49 09/98 Bobbin HNC 7
1.46 11C
+39.30 44 54 09/98 Bobbin HNI 2.55 10C
+23.77 09/98 Bobbin HNI 3.55 02H
+10.44 j
09/98 Bobbin HNC 16 0.68 10C
+6.91 i
09/98 H/L Special Interest VOL 3.18 02H
+11.69 i
44 72 09/98. Bobbin HNI 1.10 14C
+2.14 i
44 84 09/98 Bobbin HNI 0.69 03H
+11.64 09/98 Bobbin HNC 7
0.49 10C
+22.78 44 91 0900 Bobbin HNC 8
0.48 O1H
+18.89 09/98 Bobbin WAR 14 0.53 AV2
+0.00 09/98 UBEND SPEC. INT, VOL 3.65 AV2
+0.00 44 92 09/98 Bobbin HNI 2.20 04H
+36.14 45 38 09/98 Bobbin NQI 0.40 17C
+18.29 09/98 Bobbin NQI 0.41 15C
+18.72 09/98 Bobbin ODI 26 0.74 18C
+8.39 45 39 09/98 Bobbin HNI 0.71 AV3
+1.36 45 41 09/98 Bobbin HNI 0.38 10C
+43.00
)
45 42 09/98 Bobbin HNI 0.39 07H
+42.63 09/98 Bobbin ODI 16 0.52 10C
+43.15 45 47 09/98 Bobbin NQI 0.31 15C
+21.60 09/98 Bobbin HNC 10 3.13 13C
+10.73 09/98 Bobbin.
HNC 15 1.39 17C
+27.84
.~
FTI TUBAN II (Varcion 2.3) 01/21/1999 11:25:38 Catawba Nuciscr Stction - Unit Two S/G B l
09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION l
09/98 H/L Tubesheet VOL 0.73 TSH
+0.01 l
45 55 09/98 Bobbin HNC 6
2.87 11C
+31.86 09/98 C/L Special Interest VOL 1.39 10C
-11.27 45 60 09 98 Bobbin ODI 1
1.22 12C
+22.19 i
45 61 09 98 Bobbin HNC 14 1.94 02H
+3.48 45 64 09/98 Bobbin HNI 2.75 10C
+45.24 45-66 09/98 Bobbin ODI 13 0.31 10C
+2.40 45 67 09/98 Bobbin ODI 17 0.50 TSH
+6.30 45 68 09 98 Bobbin HNI 0.18 10C
+24.31 45 73 09 98 Bobbin ODI 16 0.36 15C
+17.89 09 98 C/L Special Interest VOL 0.69 15C
+18.40 45 77 09 98 Bobbin HNI 1.31 04H
+5.72 09 98 Bobbin HNC 3
1.55 17C
+18.52 09/98 C/L Special Interest VOL 1.26 17C
+18.52 45 81 09/98 Bobbin H?.:C 10 1.03 02H
+24.39 09/98 Bobbin HNC 23 1.73 02H
+29.63 09/98 H/L Special Interest VOL 2.00 02H
+29.59 45 85 09/98 Bobbin HNC 10 0.94 10C
+26.59 46 27 09/98 Bobbin ODI 29 0.32 09C
-0.70 46 39 09/98 Bobbin HNC 18 0.53 10C
+37.36 46 41 09/98 Bobbin HNC 14 1.08 07H
+44.44 09/98 Bobbin ODI 9
0.37 11C
+20.82 46 54 09/98 Bobbin NOI 0.22 O1H
+0,50 09/98 H/L Special Interest VOL 1.03 O1H
+0.54 i
46 56 09 98 Bobbin WAR 7
0.22 AV2
+0.15 09 98 UBEND SPEC. INT.
VOL 0.25 AV2
+0.00 46 60 09/98 Bobbin HNC 10 0.43 17C
+24.03 3
09/98 Bobbin HNC 15 0.39 17C
+13.13 1
09/98 Bobbin HNC 24 0.69 17C
+26.16 09/98 C/L Special Interest VOL 0.68 17C
+13.59 1
09/98 C/L Special Interest VOL 0.73 17C
+24.51 09/98 C/L Special Interest VOL 0.88 17C
+27.02 46 71 09/98 Bobbin HNI 0.58 13C
+2.32 46 77 09/98 Bobbin HNC 24 1.98 15C
+19.94 09/98 C/L Special Interest VOL 2.14 15C
+19.94 46 82 09/98 Bobbin HNI 1.38 15C
+7.51 09/99 Bobbin HNC 10 1.30 17C
+15.75 09/90 Bobbin HNC 21 0.85 12C
+39.28 47 27 09/98 Bobbin WAR 11 0.40 AV4
-0.18 09/98 Bobbin WAR 16 0.60 AV3
+0.55 47 29 09/98 Bobbin HNI 0.73 13C
+30.34 09/98 C/L Special Interest VOL 1.09 13C
+29.51 47 32 09/98 Bobbin HNC 23 0.51 15C
+15.72 47 35 09/98 Bobbin ODI 19 0.30 06H
+5.92 47 38 09/98 Bobbin HNC 33 0.89 10C
+44.53 47 44 09/98 Bobbin HNC 11 0.95 11C
+34.04 47 62 09/98 Bobbin NQI 1.24 AV4
+25.73 09/98 Bobbin ODI 20 8.92 03H
+27.83 i
09/98 H/L Special Interest VOL 1.09 04H
-7.49 47 72 09/98 Bobbin HNC 17 1.07 02H
+14.78 09/98 Bobbin HNC 20 1.45 03H
+6.26 09/98 H/L Special Interest VOL 1.03 02H
+14.57 47 82 09 98 Bobbin NQI 0.63 13C
+32.99 l
47 83 09 98 Bobbin HNI 1.23 12C
+19.24 t
47 86 09/98 Bobbin HNC 14-1.09 15C
+26.93 09/98 C/L Special Interest VOL 0.54 15C
+26.90 47 88 09/98 Bobbin WAR 10 0.34 AV2
+0.00 48 30 09/98 Bobbin HNC 22 1.10 02H
+27.35 48 35 09/98 Bobbin ODI 15 0.34 11C
+30.38 48 36 09/98 Bobbin HNI 0.64 AV3
+13.05
)
f 09/98 Bobbin HNI 1.37 AV3
+4.91 l
48 37'09/98 Bobbin ODI 7
0.30.11C
+26.66 48 39 09/98 Bobbin NQI 1.78 17C
+0.11 l
09/98 C/L Special Interest VOL 1.38 17C
+0.15 j
48-40 09/98 Bobbin NQI 0.44 13C
+19.64 i
l
.~
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:25:38 I
Catawba Nuclear Station - Unit Two S/G B 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC i
Page 15 ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS i
INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND LTW VOLTS LOCATION l
09/98 C/L Special Interest VOL 0.72 13C-
+19.99 48 44 09/98 Bobbin ODI 5
0.29 11C
+15.86 l
48 50 09/98 Bobbin HNI 0.36 12C
+2.27 09/98 Bobbin HNI 0.93 10C
+43.34 48 74 09/98 Bobbin HNC 8
1.47 11C
+16.02 09/98 C/L Special: Interest VOL 1.20 11C
+19.16 49 45 09/98 Bobbin HNC 6
0.36 15C
+24.99 i
49 46 09/98 Bobbin HNC 9 2.35 13C
+19.75 49 50 09/98 Bobbin NQI 0.42 07H
+42.10 09/98 Bobbin HNC 6
0.62 11C
+23.88 49-61 09/98 Bobbin HNI 0.60 13C
-0.37 09/98 Bobbin NQI 0.45 09C
+4.91 09/98 C/L Special Interest VOL 1.35 13C
-0.33 49 69 09/98 Bobbin HNI 0.47 03H
+24.59 49 70 09/98 Bobbin HNI 0.14 15C
+18.57 49 72 09/98 Bobbin HNC 8
0.42 07H
+27.15 49 73 09/98 Bobbin HNC 14 0.31 07H
+32.91 49 84 09/98 Bobbin HNI 0.61 05H
+31.77 09/98 Bobbin NOI 0.31 13C
+33.23 09/98 Bobbin HNC 6
0.92 05H
+36.29 i
09/98 C/L Special Interest VOL 0.47 12C
-9.69 09/98 H/L Special Interest VOL 1.16 06H
-11.95 Total Indications Found = 932 Total Tubes Found = 573 t
f f
FTI TUBAN II (Varnion 2.3) 01/21/1999 11:27:12 Catawb3 Nuclear Station - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC 1
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION J
1 6 09/98 Bobbin ODI 32 0.26 19C
+2.79 1 13 09/98 Bobbin HNI 0.86 18C
+21.52 1 15 09/98 Bobbin NQI 1.22 16C
+21.66 1 16 09/98 Bobbin HNC 24 0.70 O1H
+4.33 1 18 09/98 Bobbin ODI 29 0.27 18C
+15.53 1 19 09/98 Bobbin HNC 28 0.80 O1H
+22.48 1
20 09/98 Bobbin HNI 0.25 18C
+29.05 1 30 09/98 Bobbin HNI 1.27 04H
+40.99 09/98 Bobbin HNI 1.39 05H
+1.83 09/98 Bobbin HNI 2.46 05H
+5.19 09/98 Bobbin HNC 20 1.09 05H
+6.95 09/98 H/L Special Interest VOL 0.61 05H
+5.45 09/98 H/L Special Interest VOL 0.65 05H
+2.03 09/98 H/L Special Interest VOL 0.75 05H
+7.58 1 31 09 98 Bobbin ODI 15 1.07 10C
+37.33 1 40 09 98 Bobbin HNI 0.79 03H
+0.47 1 49 09/98 Bobbin HNC 7
0.37 18C
+18.65 1 55 09/98 Bobbin HNC 17 0.39 16C
-1.53 1 62 09/98 Bobbin HNC 6
1.10 18C
+17.37 1 63 09/98 Bobbin ODI 16 0.22 19C
+3.10 1 77 09/98 Bobbin HNI 0.43 05H
+16.60 1 78 09/98 Bobbin HNI 0.31 04H
+14.04 09/98 Bobbin HNI 0.41 02H
+12.58 1 79 09/98 Bobbin HNI 3.99 18C
+12.55 to 423.06 l
1 84 09/98 Bobbin HNI 0.89 18C
+18.67 09/98 C/L Special Interest VOL 0.84 18C
+18.69 1 104 09/98 Bobbin HNI 0.53 02H
+27.29 l
1 113 09/98 Bobbin ODI 17 0.48 14C
+4.50 2 13 09/98 Bobbin ADI 1.42 13C
+28.39 09/98 C/L Special Interest VOL 0.50 13C
+29.97 2 23 09/98 Bobbin HNI 0.49 13C
+15.56 2 31 09/98 Bobbin HNC 34 0.42 19C
+6.67 2 37 09/98 Bobbin HNI 0.64 10C
+34.20 2 46 09/98 Bobbin NOI 0.63 14C
+9.73 2 55 09/98 Bobbin NOI 0.47 04H
+34.02 09/98 Bobbin ODI 18 0.31 04H
+6.99 09/98 H/L Special Interest VOL 1.83 04H
+34.61 2 64 09/98 Bobbin HNI 0.66 13C
+5.52 09/98 Bobbin HNI 1.09 13C
+4.25 09/98 Bobbin HNI 1.22 13C
+3.02 09/98 Bobbin NOI 0.31 13C
+6.78 09/98 Bobbin NOI 0.97 13C
+1.66 2 66 09/98 Bobbin HNC 9
1.27 16C
+18.70 2 68 09/98 Bobbin HNI 0.54 O1H
+26.67 09/98 H/L Special Interest VOL 0.39 O1H 426.72 09/98 H/L Special Interest VOL 0.74 O1H
+11.36 2 73 09/98 Bobbin HNI 1.21 04H
+2.78 09/98 H/L Special Interest VOL 1.72 04H
+2.78 2 74 09/98 Bobbin HNI 0.91 01H
+5.72 09/98 Bobbin HNI 1.76 12C
+30.31 09/98 Bobbin HNI 2.31 12C
+29.28 09/98 C/L Special Interest VOL 0.78 11C
-13.55 09/98 C/L Special Interest VOL 1.40 11C
-12.56 2 75 09/98 Bobbin HNC 12 0.92 16C
+25.11 2 76 09/98 Bobbin HNC 11 1.53 06H
+34.81 09/98 H/L Special Interest VOL 1.38 07H
-9.15 2 84 09/98 Bobbin HNI 0.51 06H
+2.37 2 85 09/98 Bobbin HNC 7
0.94 13C
+13.09 09/98 C/L Special Interest VOL 0.77 13C
+13.18 2 102 09/98 Bobbin HNC 7
1.48 11C
+20.50 2 107 09/98 Bobbin HNI 0.59 05H
+12.57 3
3 09/98 Bobbin NQI 0.29 15C
+4.23 09/98 Bobbin NOI 0.33 15C
+4.24 3 14 09/98 Bobbin NQI 0.46 13C
+10.35 09/98 Bobbin NQI 0.48 13C
+10.39
FTI T1 HUM II (Varzion 2.3) 01/21/1999 11:27:12 Ccttwba Nuclezr Station - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 3 23 09/98 Bobbin HNC 3
3.99 TSC
+8.08 09/98 Bobbin HNC 3
4.05 TSC
+8.08 09/98 C/L Special Interest VOL 1.60 19C
-0.70 3 25 09/98 Bobbin HNI 0.30 14C
+13.42 09/98 Bobbin HNI 0.37 14C
+13.44 3 27 09/98 Bobbin HNI 1.94 14C
+7.96 09/98 Bobbin HNI 2.03 14C
+8.08 09/98 Bobbin NQI 0.35 13C
+35.04 09/98 Bobbin NQI 0.36 13C
+34.99 3 77 09/98 Bobbin ADI 1.35 13C
+39.98 3 78 09/98 Bobbin ODI 24 0.54 13C
+0.83 09/98 C/L Special Interest VOL 0.54 13C
+0.67 3 97 09/98 Bobbin HNI 4.13 13C
+14.63 09/98 Bobbin HNI 4.40 18C
+12.35 09/98 Bobbin HNI 5.04 TSC
+3.34 09/98 C/L Special Interest VOL 1.64 13C
+13.80 09/98 C/L Special Interest VOL 1.87 TSC
+2.97 09/98 C/L Special Interest VOL 1.91 13C
+13.92 09 98 C/L Special Interest VOL 2.14 TSC
+2.87 09 98 C/L Special Interest VOL 2.59 17C
-6.45 09/98 C/L Special Interest VOL 2.72 18C
+12.41 4 18 09/98 Bobbin NOI 0.27 13C
+37.07 09/98 Bobbin NQI 0.29 13C
+37.06 4 23 09/98 Bobbin NOI 0.33 15C
+10.57 09/98 Bobbin NOI O.55 15C
+10.57 4 27 09/98 Bobbi n HNI 0.46 05H
+23.46 09/98 Bobbin HNI 0.53 05H
+26.63 09/98 Bobbin HNT 0.59 05H
+39.24 09/98 Bobbin HNC 10 2.01 05H
+18.91 09/98 H/L Special Interest VOL 0.66 05H
+23.66 09/98 H/L Special Interest VOL 1.21 05H
+26.57 09/98 H/L Special Interest VOL 1.53 05H
+39.59 09/98 H/L Special Interest VOL 2.59 05H
+19.09 4 31 09 98 Bobbin NOI 1.02 12C
+16.14 09 98 Bobbin NOI 1.15 12C
+16.13 09/98 C/L Special Interest VOL 0.72 12C
+17.78 4 37 09/98 Bobbin HNC 26 0.17 15C
+14.46 09/98 Bobbin ODI 21 0.18 15C
+14.51 4 38 09/98 Bobbin HNI 0.83 01H
+11.45 4 39 09/98 Bobbin HNI 0.74 TSH
+2.61 09/98 Bobbin NOI 0.38 10C
+37.53 to
+41.64 09/98 Bobbin NQI 0.80 10C
+36.78 to
+41.51 09/98 H/L Special Interest VOL 1.11 TSH
+2.85 4 49 09/98 Bobbin NQI 0.29 03H
+3.38 4 69 09/98 Bobbin ADI 1.76 11C
+20.92 09/98 C/L Special Interest VOL 1.37 13C
+22.52 4 84 09 98 Bobbin ODI 9
0.87 10C
+43.16 09 98 Bobbin HNI 0.74 05H
+0.93 to
+11.96 4 103 09/98 Bobbin HNI 2.44 02H
+32.67 09/98 H/L Special Interest VOL 0.57 02H
+33.30 09/98 H/L Special Interest VOL 0.85 02H
+31.89 4 113 09/98 Bobbin ADI 1.99 13C
+22.80 09/98 Bobbin ADI 2.21 13C
+22.72 09/98 C/L Special Interest VOL 0.48 13C
+4.02 09/98 C/L Special Interest VOL 0.53 13C
+4.94 09/98 C/L Special Interest VOL 0.80 13C
+24.12 5
9 09/98 Bobbin HNC 5
0.36 13C
+7.69 09/98 Bobbin HNC 9
0.35 13C
+7.74 09/98 C/L Special Interest VOL 0.42 13C
+8.35 5 32 09/98 Bobbin HNC 15 1.40 04H
+8.81 09/98 H/L Special Interest VOL 0.96 04H
+9.24 5 49 09/98 Bobbin HNI 0.45 15C
+16.71 09/98 Bobbin HNI 0.53 15C
+16.74 5 64 09/98 Bobbin ODI 20 0.25 12C
+40.46 5 72 09/98 Bobbin HNI 1.28 05H
+13.87
FTI TUBAN II (Varmion 2.3) 01/21/1999 11:27:12 CItcwba Nuclczr Station - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 5 80 09/98 Bobbin HNI 2.02 16C
+13.42 5 87 09/98 Bobbin HNI 0.71 05H
+20.62 09/98 Bobbin HNI 0.77 05H
+20,60 5 92 09/98 Bobbin HNI 2.84 13C
+2.94 5 101 09/98 Bobbin HNI 0.31 O1H
+21.91 5 104 09/98 Bobbin HNI 1.09 04H
+25.20 09/98 H/L Special Interest VOL 0.65 04H
+25.20 5 107 09/98 Bobbin HNI 1.11 TSH
+6.21 6 68 09/98 Bobbin HNC 12 0.75 01H
+10.74 6 86 09/98 Bobbin HNI 0.37 12C
+6.55 6 89 09/98 Bobbin HNC 29 0.37 03H
+16.74 6 99 09/98 Bobbin HNC 11 1.06 03H
+18.66 09/98 H/L Special Interest VOL 1.42 03H
+18.64 6 103 09/98 Bobbin ADI 1.53 04H
+5.45 09/98 Bobbin ADI 1.86 04H
+3.05 09/90 H/L Special Interest VOL 0.73 04H
+5.67 7 35 09/98 Bobbih HNC 8
1.41 18C
+16.15 09/98 C/L Special Interest VOL 0.89 17C
-2.13 7 38 09/98 Bobbin HNI 0.37 04H
+20.73 to
+27.60 7 39 09/98 Bobbin HNC 14 3.84 04H
+4.11 7 41 09/98 Bobbin ADI 1.22 O1H
+10.70 09/98 Bobbin NOI 0.46 06H
+3.63 09/98 Bobbin ODI 19 0.72 02H
+19.18 09/98 Bobbin ODI 23 0.26 02H
+11.79 j
09/98 Bobbin ODI 26 0.83 O1H
+2.77 09/98 H/L Special Interest VOL 1.47 02H
+20.55 7 44 09/98 Bobbin HNC 2
0.47 O1H
+11.93 7 49 09/98 Bobbin NOI 0.41 18C
+10.07 7 64 09/98 Bobbin ODI 6
0.23 10C
+27.29 09/98 Bobbin ODI 16 0.18 O1H
+4.73 7 72 09/98 Bobbin HNI 0.31 13C
+1.63 I
09/98 Bobbin HNI 0.45 13C
+3.56 09/98 Bobbin HNT 0.46 13C
+7.19 09/98 Bobbin HNI 0.54 13C
+6.64 09/98 Bobbin HNI 0.85 13C
+12.47 09/98 Bobbin NOI 0.43 23C
+33.32 09/98 Bobbin NQI 0.42 15C
+4.27 to
+7.94 7 81 09/98 Bobbin HNI O.94 14C
+9.38 7 83 09/98 Bobbin ADI 0.95 13C
+29.44 09/98 Bobbin HNI 0.35 12C
+7.99 09/98 Bobbin HNI 0.38 12C
+11.02 09/98 Bobbin NOI 0.37 13C
+23.65 09/98 C/L Special Interest VOL 0.37 12C
+8.19 7 84 09/98 Bobbin HNC 7
1.41 11C
+22.17 7 99 09/98 Bobbin NOI 0.26 15C
+10.28 7 106 09/98 Bobbin ODI 11 0.37 12C
+34.53 8 30 09/98 Bobbin NOI 0.30 17C
+6.63 8 31 09/98 Bobbin HNC 22 0.28 OSH
+29.69 8 35 09/98 Bobbin NOI 0.22 14C
+15.83 8 50 09/98 Bobbin HNI 2.81 05H
+1.43 8 76 09/98 Bobbin HNC 30 1.87 OSH
+33.15 09/98 H/L Special Interest VOL 1.57 05H
+33.33 8 83 09/98 Bobbin HNC 8
0.82 12C
+28.13 8 85 09/98 Bobbin HNI 1.13 O1H
+21.74 09/98 H/L Special Interest VOL 2.88 O1H
+21.70 8 103 09/98 Bobbin HNI 0.57 16C
+10.58 8 110 09/98 Bobbin HNI 1.66 05H
+25.98 i
9 8 09/98 Bobbin HNI 3.01 11C
+34.56 l
9 14 09/90 Bobbin ADI 1.90 18C
+15.91 09/98 Bobbin NOI 0.36 02H
+30.31 09/98 H/L Special Interest VOL 2.03 02H
+30.13 9 18 09/98 Bobbin HNI 0.93 10C
+24.82 9 38 09/98 Bobbin HNI 6.97 02H
+11.22 09/98 H/L Special Interest VOL 3.16 02H
+12.11 9 41 09/98 Bobbin HNI 0.82 17C
+8.52
2 e
l FTI TUBAN II (Version 2.3) 01/21/1999 11:27:12 Cat. wba Nuclear Station - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS I
INDS OF IMPERFECTIONS - SGC 1
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION i
9 49 09/98 Bobbin NQI 0.88 07H
+7.67 I
09/98 H/L Special Interest VOL 1.75 07H
+7.37 9 84 09/98 Bobbin HNC 20 0.42 04H
+22.30 9 95 09/98 Bobbin HNI 0.84 07H
+40.54 9 98 09/98 Bobbin HNI 1,91 07H
+20.82 9 112 09/98 Bobbin HNI 0.67 03H
+21.47 09/98 Bobbin HNI 0.88 04H
+30.10 09/98 Bobbin HNI 1.33 04H
+33.00 09/98 Bobbin HNC 21 0.73 04H
+32.26 09/98 Bobbin ODI 13 0.80 04H
+35.59 09/98 Bobbin HNI 2.14 05H
+2.81 to
+21.39 09/98 H/L Special Interest VOL 0.22 04H
+30.90 09/98 H/L Special Interest VOL 1.04 05H
+2.81 to
+21.39 10 4 09/98 Bobbin HNI O.22 13C
+14.24 09/98 Bobbin HNC 16 0.63 15C
+5.82 10 11 09/98 Bobbin HNC 33 1.82 02H
+11.02 10 20 09/98 Bobbin HNI 0.34 14C
+13.70 10 43 09/98 Bobbin HNI 0.50 13C
+23.74
)
10 51 09/98 Bobbin HNI 0.46 17C 416.48 10 68 09/98 Bobbin HNC 5
0.51 04H
+7.40 10 69 09/98 Bobbin HNI 0.71 12C
+29.73 10 78 09/98 Bobbin HNI 0.40 18C
+2.39 09/98 Bobbin HNC 18 0.98 18C
+6.35 10 79 09/98 Bobbin ADI 3.31 13C
+23.95 09/98 C/L Special Interest VOL 1.45 13C
+23.56 10 81 09/98 Bobbin HNI 0.60 17C
+12.18 11 2 09/98 Bobbin NOI 0.29 14C 410.65 11 41 09/98 Bobbin HNC 10 0.77 11C
+4.94 11 61 09/98 Bobbin HNC 17 0.40 10C
+26.69 11 68 09/98 Bobbin HNI 1.01 06H
+30.16 11 83 09/98 Bobbin HNC 21 0.51 14C
+12.14 j
11 87 09/98 Bobbin ODI 15 0.50 17C
+11.51 09/98 C/L Special Interest VOL 0.91 16C
-8,54 11 93 09/98 Bobbin HNI 0.50 16C
+9.05 09/98 Bobbin HNI 0.68 03H
+2C.75 09/98 Bobbin HNC 25 0 61 03H
+25.46 09/98 Bobbin ODI 26 0.64 11C
+32.75 11 98 09/98 Bobbin HNC 2
0.42 06H
+22.16 09/98 H/L Special Interest VOL 2.13 06H
+22.50 11 99 09 98 Bobbin ODI 22 1.19 TSC
+7.23 l
09 98 C/L Special Interest VOL 1.44 19C
-2.32 09/98 C/L Special Interest VOL 2.06 TSC
+6.56 11 102 09/98 Bobbin HNI 0.39 13C
+17.23 09/98 C/L Special Interest VOL 0.60 13C
-1.28 11 107 09/98 Bobbin HNC 19 2.17 02H
+31.17 09/98 H/L Special Interest VOL 1.91 02H
+31.17 11 109 09/98 Bobbin HNI 0.25 11C
+22.87 11 112 09/98 Bobbin HNI 1.58 10C
+26.28 12 15 09/98 Bobbin HNI 0.27 TSH
+4.00 09/98 Bobbin HNI 1.25 TSH 43.43 12 21 09/98 Bobbin NOI 0.22 19C
+2.63 09/98 Bobbin ODI 11 0.34 03H
+2.04 12 30 09/98 Bobbin HNC 32 0.43 13C
+15.08 12 41 09/98 Bobbin HNI O.32 17C
+2.76 09/98 Bobbin HNI 0.81 17C
+7.26 09/98 C/L Special Interest VOL 0.92 17C
+7.31 12 56 09/98 Bobbin HNI 0.41 12C
+20.45 12 59 09/98 Bobbin ODI 4
0.57 07H
+38.49 12 69 09/98 Bobbin HNI 0.74 13C
+38.61 i
12 74 09/98 Bobbin HNC 17 0.56 08H
+0.75 12 77 09/98 Bobbin HNC 4
0.63 19C
+3.33 12 93 09/98 Bobbin HNI 0.96 05H
+1.99 to
+10.81 12 102 09/98 Bobbin HNC 7
0.40 17C
+9.16 l
13 8 09/98 Bobbin HNI 0.30 10C
+7.08 09/98 Bobbin NQI 0.34 07H
+15.12 i
~ _.
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:27:12 Catzwba Nuclsar Station - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion 4Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 5 ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 13 9 09/98 Bobbin HNI 0.37 07H
+30.08 13 35 09/98 Bobbin HNI 0.46 06H
+39.29 09/98 Bobbin HNC 18 0.72 10C
+3.07 09/98 Bobbin HNC 20 0.24 11C
+29.62 09/98 Bobbin ODI 20 0.21 TSH
+2.10 13 78 09/98 Bobbin ADI 4.66 18C
+10.36 09/98 Bobbin NOI 0.56 19C
+6.83 09/98 Bobbin NOI 1.03 19C
+7.85 09/98 C/L Special Interest VOL 1.21 19C
+7.15 09/98 C/L Special Interest VOL 1.78 19C
+8.15 13 91 09/98 Bobbin HNI 0.83 16C
+10.41 09/98 Bobbin HNC 4
0.76 O1H
+10.89 09/98 C/L Special Interest VOL 0.80 15C
-7.42 13 110 09/98 Bobbin HNC 20 0.63 12C
+2.49 13 111 09/98 Bobbin ODI 16 0.31 10C
+12.28 09/98 Bobbin ODI 20 0.32 10C
+12.15 14 5 09/98 Bobbin ODI 17 0.60 07H
+42.49 14 6 09/98 Bobbin NOI 0.32 07H
+28.54 14 15 09/98 Bobbin ODI 34 0.14 15C
+10.78 14 16 09/98 Bobbin ODI 20 0.36 11C
+6.20 14 17 09/98 Bobbin NOI 0.86 15C
+8.85 09/98 Bobbin NOI 0.89 18C
+3.26 09/98 Bobbin HNC 27 1.41 18C
+0.91 09/98 Bobbin ODI 4
0.91 19C
+3.95 14 19 09/98 Bobbin HNI 0.80 TSC
+6.68 09/98 Bobbin NOI 0.54 03H
+0.13 09/98 C/L Special Interest VOL 0.77 TSC
+6.81 09/98 H/L Special Interest VOL 2.15 03H
-0.10 14 30 09/98 Bobbin HNI 0.83 11C
+15.52 14 51 09/98 Bobbin HNI 0.24 04H
+7.36 14 63 09/98 Bobbin ODI 18 0.21 18C
+14.18 14 69 09/98 Bobbin HNI 0.29 10C
+23.62 14 108 09/98 Bobbin HNI 0.89 13C
+2.64 15 6 09/98 Bobbin HNC 4
0.84 07H
+26.48 09/98 Bobbin HNC 7
1.00 17C
+13.11 15 23 09/98 Bobbin ADI 2.39 11C
+32.05 09/98 Bobbin HNI 0.37 11C
+35.73 15 50 09/98 Bobbin HNI 0.52 03H
+3.64 15 64 09/98 Bobbin HNI 0.66 TSC
+4.17 15 98 09/98 Bobbin HNI 0.60 13C
+39.21 15 99 09/98 Bobbin HNI 0.46 10C
+9.22 09/98 Bobbin HNI 0.93 11C
+20.81 09/98 Bobbin HNI 1.43 11C
+29.04 09/98 Bobbin HNI 1.53 05H
+15.01 09/98 Bobbin HNI 1.73 AV1
+7.48 09/98 Bobbin HNC 17 0.96 11C
+41.65 09/98 H/L Special Interest VOL 2.18 05H
+15.09 15 104 09/98 Bobbin HNI 2.45 12C
+35.11 16 6 09/98 Bobbin ODI 16 0.31 07H
+28.22 16 43 09/98 Bobbin HNI 0.88 TSH
+4.09 16 52 09/98 Bobbin ODI 15 0.83 TSH
+3.85 16 62 09/98 Bobbin HNI 0.74 06H
+34.63 16 65 09/98 Bobbin HNC 27 0.69 10C
+29.52 16 78 09/98 Bobbin NQI 0.18 10C
+28.09 09/98 Bobbin HNC 15 0.21 07H
+34.36 09/98 Bobbin HNC 23 0.49 07H
+21.51 09/98 Bobbin ODI 4
1.11 12C
+16.81 09/98 Bobbin ODI 31 0.24 07H
+26.30 09/98 Bobbin NOI 0.76 10C
+31.44 to
+33.98 09/98 C/L Special Interest VOL 0.99 12C
+16.20 l
16 91 09/98 Bobbin HNI 0.49 07H
+10.07 16 110 09/98 Bobbin ODI 9
0.47 14C
+9.40 17 14 09/98 Bobbin NOI 0.23 12C
+32.69 09/98 Bobbin HNC 28 0.43 13C
+19.49 17 36 09/98 Bobbin NQI 0.24 12C
+35.54
FTI TURAN II (Varsion 2.3) 01/21/1999 11:27:12 i
l Cettwb3 Nuclear Stction - Unit Two S/G C j
09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 17 73 09/98 Bobbin HNI 0.34 10C
+12.32 17 81 09/98 Bobbin HNI 0.52 04H
+1.35 17 88 09/98 Bobbin HNI 0.87 15C
+15.75 09/98 C/L Special Interest VOL 0.63 14C
-2.32 17 89 09/98 Bobbin HNI 0.46 18C
+4.31 17 91 09/98 Bobbin HNI 1.19 18C
+11.80 09/98 C/L Special Interest VOL 1.01 18C
+11.81 17 101 09/98 Bobbin HNI 0.78 04H
+16.27 18 15 09/98 Bobbin HNI 0.39 TSH
+5.26 09/98 Bobbin HNI 0.42 14C
+6.79 09/98 Bobbin HNI 0.42 15C
+10.54 18 29 09/98 Bobbin HNC 20 1.65 TSC
+7.46 l
09/98 C/L Special Interest VOL 2.25 TSC
+7.55 18 36 09/98 Bobbin HNC 1
1.04 03H
+29.78 18 44 09/98 Bobbin ADI 2.45 02H
+15.54 09/98 H/L Special Interest VOL 2.12 02H
+16.96 18 63 09/98 Bobbin HNI 0.38 12C
+2.74 09/98 Bobbin HNC 9
0.62 13C
+33.57 09/98 Bobbin ODI 1
0.55 13C
+30.52 18 69 09/98 Bobbin NOI 0.33 17C
+2.47 09/98 Bobbin NQI 0.74 07H
+41.14 18 85 09/98 Bobbin HNI 1.27 TSH
+3.44 18 86 09/98 Bobbin NOI 0.25 10C
+30.27 18 102 09/98 Bobbin HNI 1.03 10C
+25.68 09/98 C/L Special Interest VOL 1.54 10C
+25.82 19 6 09/98 Bobbin HNC 4
0.32 17C
+8.05 19 25 09/98 Bobbin ODI 27 0.32 11C
+34.79 l
19 29 09/98 Bobbin NOI 0.49 02H
+25.22 l
09/98 Bobbin NOI 0.95 07H
+25.48 09/98 H/L Special Interest VOL 0.81 07H
+24.94 09/98 H/L Special Interest VOL 2.39 02H
+25.12 19 31 09/98 Bobbin ODI 12 1.30 AV4
+23.01 19 45 09/98 Bobbin ADI 1.44 07H
+20.47 to
+40.62 19 46 09/98 Bobbin HNI 0.53 17C
+4.81 19 52 09/98 Bobbin ODI 19 0.86 11C
+5.98 19 63 09/98 Bobbin HNI 0.74 14C
+3.64 19 88 09/98 Bobbin HNI 1.04 11C
+29.51 19 93 09/98 Bobbin HNC 12 0.32 07H
+26.95 19 102 09/98 Bobbin HNI 0.44 03H
+21.78 19 107 09/98 Bobbin HNC 18 2.31 07H
+30.48 19 108 09/98 Bobbin HNI 0.68 07H
+43.47 20 24 09/98 Bobbin HNI 0.45 18C
+6.50 09/98 Bobbin HNI 0.53 15C
+7.79 20 29 09/98 Bobbin HNC 8
2.58 10C
+7.66 09/98 C/L Special Interest VOL 2.01 10C
+7.55 20 43 09/98 Bobbin HNI 0.56 11C
+34.16 20 47 09/98 Bobbin HNI 3.71 11C
+27.82 09/98 Bobbin NQI 0.34 10C
+3.44 20 59 09/98 Bobbin HNI 0.39 10C
+42.32 20 62 09/98 Bobbin HNC 16 0.90 10C
+44.13 20 64 09/98 Bobbin HNI 0.17 11C
+40.12 09/98 Bobbin HNC 11 0.91 07H
+3.13 09/98 Bobbin HNC 23 0.49 10C
+8.15 20 65 09/98 Bobbin NOI 0.31 10C
+22.05 20 66 09/98 Bobbin ODI 9
0.33 04H
+7.27 20 69 09/98 H/L Tubesheet VOL 0.24 TSH
+0.06 20 74 09/98 Bobbin HNC 5
1.11 12C
+27.32 20 82 09/98 Bobbin HNI 1.82 05H
+14.20 20 89 09/98 Bobbin HNC 17 0.57 07H
+29.77 a~
20 92 09/98 Bobbin HNI 1.45 07H
+44.62 20 98 09/98 Bobbin ODI 3
0.41 10C
+7.95 21 5 09/98 Bobbin NOI 0.14 17C
+10.95 09/98 Bobbin NOI 0.20 17C
+6.89 21 24 09/98 Bobbin HNC 8
2.72 12C
+41.04 l
21 31 09/98 Bobbin HNI 0.24 13C
+22.60
. _ ~ - -.
l l
FTI TURAN II (Vsreion 2.3) 01/21/1999 11:27:12 C2tcwb Nuclear Station - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
l l
l ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 21 33 09/98 Bobbin HNC 13 0.69 10C
+29.50 21 44 09/98 Bobbin HNC 9
0.73 03H
+27.57 21 47 09/98 Bobbin HNI 1.96 10C
+34.02 09/98 C/L Special Interest VOL 1.50 09C
-11.63 21 64 09/98 Bobbin HNI 0.42 04H
+30.80
)
21 66 09/98 Bobbin HNI 0.21 07H
+25.50 i
21 67 09/98 Bobbin HNC 9
0.58 10C
+34.58 09/98 Bobbin HNC 31 0.35 10C
+33.44 21 81 09/98 Bobbin HNI 0.86 12C
+35.59 09/98 Bobbin HNI 0.95 12C
+38.34 09/98 C/L Special Interest VOL 1.56 11C
-4.78 09/98 C/L Special Interest VOL 1.80 11C
-1.69 21 91 09/98 Bobbin HNC 19 0.63 10C
+11.52 09/98 C/L Special Interest VOL 0.54 10C
+11.52 21 94 09/98 Bobbin HNI 0.50 11C
+35.47 09/98 C/L Special Interest VOL 0.23 10C
-7.50 21 95 09 98 Bobbin HNI 0.37 O1H
+24.39 09 98 Bobbin HNI 0.66 O1H
+5.81 21 98 09/98 Bobbin HNI 1.57 07H
+28.56 21 100 09/98 Bobbin HNC 13 0.89 12C
+15.93 22 17 09/98 Bobbin HNC 23 2.35 13C
+1.90 22 32 09/98 Bobbin HNC 12 0.48 11C
+2.17 22 44 09/98 Bobbin HNC 24 0.95 13C
+37.02 09/98 C/L Special Interest VOL 0.67 12C
-6.03 09/98 C/L Special Interest VOL 0.70 12C
-5.90 22 72 09/98 Bobbin ODI 24 0.38 07H
+29.15 1
22 73 09/98 Bobbin HNI 0.54 04H
-0.30 22 75 09/98 Bobbin HNC 7
0.60 12C
+19.99 l
09/98 Bobbin ODI 31 0.44 10C
+21.92 l
22 77 09/98 Bobbin HNC 8
0.56 10C
+41.15 22 80 09/98 Bobbin ADI 2.65 13C
+12.78 i
22 90 09/98 Bobbin HNC 25 1.54 06H
+2.77 09/98 H/L Special Interest VOL 1.87 06H
+2.77 22 93 09/98 Bobbin HNC 14 1.10 07H
+41.52 09/98 Bobbin HNC 29 0.36 10C
+42.35 22 100 09/98 Bobbin HNC 11 1.49 15C
+13.25 22 104 09/98 Bobbin HNI 0.84 17C
+4.79 22 107 09/98 Bobbin HNI 0.76 12C
+36.34 09/98 Bobbin HNC 2
0.52 07H
+23.31 23 6 09/98 Bobbin NQI 0.20 14C
+9.80 09/98 Bobbin HNC 5
1.20 12C
+22.88 09/98 Bobbin HNC 18 1.56 OBH
+6.86 23 33 09/98 Bobbin HNC 3
0.95 04H
+23.48 09/98 H/L Special Interest VOL 0.90 04H
+23.24 09/98 H/L Special Interest VOL 0.91 04H
+24.88 23 35 09/98 Bobbin HNC 23 0.84 02H
+7.63 23 73 09/98 Bobbin HNC 27 0.94 02H
+30.48 09/98 H/L Special Interest VOL 1.29 02H
+30.80 23 76 09/98 Bobbin NOI 0.42 10C
+35.53 23 83 09/98 Bobbin HNI 0.33 12C
+11.13 09/98 Bobbin NQI 0.28 07H
+5.98 23 86 09/98 Bobbin NQI 0.87 11C
+5.59 09/98 C/L Special Interest VOL 1.04 11C
+5.59 23 87 09/98 Bobbin HNI 0.30 16C
+12.86 23 90 09/98 Bobbin ODI 26 0.33 07H
+28.41 23 91 09/98 Bobbin ODI 17 0.30 07H
+1.54 23 102 09/98 Bobbin HNI 1.16 10C
+20.34 09/98 Bobbin HNC 11 1.34 12C
+7.42 24 8 09/98 Bobbin HNC 8
1.22 05H
+4.96 24 20 09/98 Bobbin ADI 1.23 05H
+15.69 09/98 H/L Special Interest VOL 1.20 05H
+15.57 i
24 27 09/98 Bobbin HNI 0.56 06H
+26.18 l
24 60 09/98 Bobbin HNC 9
0.76 10C
+42.21 09/98 Bobbin HNC 13 0.56 10C
+38.18 09/98 Bobbin HNC 26 0.36 10C
+35.08
FTI TUBAN II (Version 2.3) 01/21/1999 11:27:12 C&tcwba Nuclear Station - Unit Two S/G C
\\
l 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 8 ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09 98 Bobbin ODI 11 0.32 10C
+40.69 24 61 09 98 Bobbin HNC 12 0.53 17C
+11.01 24 64 09/98 Bobbin HNC 26 0.33 12C
+8.62 24 65 09/98 Bobbin HNI O.75 10C
+4.03 09/98 Bobbin HNI 1.19 18C
+3.95 24 66 09/98 Bobbin HNI 0.41 17C
+11.96 09/98 Bobbin HNI 0.46 15C
+2.03 24 75 09/98 Bobbin ODI 10 0.60 10C
+20.38 24 86 09/98 Bobbin ODI 22 0.21 10C
+41.88 24 87 09/98 Bobbin HNI 1.25 10C
+19.93 25 7 09/98 Bobbin HNC 29 0.19 17C
+5.59 25 29 09/98 Bobbin ODI 25 0.36 OBH
-0.65 25 30 09/98 Bobbin ODI 26 0.64 07H
+40.93 25 39 09/98 Bobbin HNI O.46 07H
+36.18 25 45 09/98 Bobbin HNI 1.58 07H
+16.77 25 50 09/98 Bobbin HNI 0.65 12C
+23.44 25 55 09/98 Bobbin ODI 23 0.25 17C
+16.49 25 56 09/98 Bobbin HNC 19 0.96 TSH
+1.76 09/98 H/L Tubesheet VOL 0.79 TSH
+2.02 09/98 H/L 6pecial Interest VOL 1.32 TSH
+2.03 25 64 09/98 Bobbin HNI 0.66 04H
+33.06 25 66 09/98 Bobbin ODI 16 0.36 07H
+2.74 25 75 09/98 Bobbin HNC 20 0.72 02H
+32.28 09/98 Bobbin ODI 11 0.58 03H
+11.10 09/98 H/L Special Interest VOL 0.69 02H
+32.28 09/98 H/L Special Interest VOL 0.74 03H
+11.10 25 79 09/98 Bobbin HNI 1.07 O1H
+26.75 09/98 Bobbin ODI 10 0.29 07H
+37.09 09/98 H/L Special Interest VOL 2.87 O1H
+25.78 25 83 09/98 Bobbin ADI 2.13 07H
+14.60 25 86 09/98 Bobbin NQI 0.48 16C
+12.02 26 10 09/98 Bobbin NQI 0.17 19C
+6.78 26 23 09/98 Bobbin HNC 12 0.48 19C
+4.91 26 40 09/98 Bobbin ODI 3
0.35 10C
+21.98 26 59 09/98 Bobbin HNI 1.31 14C
+9.86 26 60 09/98 Bobbin ODI 5
2.28 10C
+27.40 26 63 09/98 Bobbin ODI 11 0.52 14C
+5.96 26 66 09/98 Bobbin HNI 1.08 03H
+21.30 09/98 H/L Special Interest VOL 1.06 03H
+21.29 26 67 09/98 Bobbin ADI 1.54 16C
+9.16 09/98 Bobbin ODI 8
0.25 14C
+10.34 26 72 09/98 Bobbin HNI 1.10 13C
+12.72 26 77 09/98 Bobbin NOI 0.28 07H
+35.52 26 85 09/98 Bobbin ODI 17 0.34 07H
+7.87 26 90 09/98 Bobbin ODI 9
0.33 17C
+5.56 26 97 09/98 Bobbin ADI 1.26 15C
+14.96 09/98 C/L Special Interest VOL 0.38 15C
+15.56 09/98 C/L Special Interest VOL 0.42 15C
+14.58 26 101 09/98 Bobbin ODI 11 1.18 TSC
+3.62 27 9 09/98 Bobbin WAR 30 1.19 AV2
-0.04 27 15 09/98 Bobbin ODI 26 0.63 17C
+0.84 09/98 C/L Special Interest VOL 0.76 17C
+0.91 27 24 09/98 Bobbin HNI 0.73 07H
+44.12 09/98 Bobbin ODI 12 0.52 12C
+7.36 27 43 09/98 Bobbin HNC 3
0.54 14C
+7.42 27 54 09/98 Bobbin NOI 0.33 07H
+2.07 27 59 09/98 Bobbin ODI 9
0.95 04H
+26.13 27 60 09/98 Bobbin HNC 11 1.41 07H
+9.47 l
27 64 09/98 Bobbin NOI 0.17 10C
+26.20 27 65 09/98 Bobbin ODI 9
0.47 07H
+29.44 j
27 72 09/98 Bobbin ADI 2.67 14C
+7.13 l
27 80 09/98 Bobbin NQI 0.45 07H
+25.67 1
09/98 Bobbin HNC 2
0.76 07H
+14.20 09/98 Bobbin ODI 23 0.38 07H
+1.22 27 83 09/98 Bobbin HNC 19 0.63 15C
+15.56
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:27:12 Catawba Nuclecr Stction - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 9 ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 27 84 09/98 Bobbin ODI 34 0.30 14C
+6.96 1
27 98 09/98 Bobbin HNI 0.81 19C
+5.03 28 10 09/98 Bobbin WAR 17 0.47 AV2
-0.03 28 11 09/98 Bobbin HNI 0.75 05H
+20.86 09/98 Bobbin NQI 0.76 05H
+23.98 09/98 Bobbin HNC 18 0.99 05H
+36.60 09/98 Bobbin ODI 21 1.12 04H
+41.48 i
09/98 H/L Special Interest VOL 1.70 05H
-1.77 09/98 H/L Special Interest VOL 2.19 05H
+6.44 to
+28.46 1
28 27 09/98 Bobbin HNC 11 1.24 11C
+31.32 28 34 09/98 Bobbin HNC 9
0.60 17C
+4.52 28 48 09/98 Bobbin HNC 7
0.72 14C
+9.17 28 60 09/98 Bobbin ODI 24 2.43 18C
+15.39 28 69 09/98 Bobbin ODI 35 0.29 12C
+0.39 09/98 C/L Special Interest VOL 0.71 12C
+5.78 to
+10.92 28 71 09/98 Bobbin ODI 20 0.67 10C
+41.36 09/98 C/L Special Interest VOL 0.55 09C
-4.09 28 72 09/98 Bobbin HNI 1.16 10C
+39.72 09/98 Bobbin HNI 2.14 11C
+34.23 09/98 C/L Special Interest VOL 1.45 10C
-8.23 28 77 09/98 Bobbin HNI 0.54 10C
+36.63 28 83 09/98 Bobbin HNI 0.50 12C
+24.32 09/98 Bobbin HNI 0.94 12C
+22.87 28 91 09/98 Bobbin HNI 1.25 13C
+27.58 09/98 Bobbin NQI 0.54 11C
+6.47 09/98 C/L Special Interest VOL 0.90 11C
+6.47 09/98 C/L Special Interest VOL 1.17 12C
-15.59 28 92 09/98 Bobbin ADI 3.95 14C
+13.73 09/98 Bobbin HNI 0.33 17C
+11.37 09/98 C/L Special Interest VOL 1.43 14C
+13.73 28 100 09/98 Bobbin HNI 1.87 17C
+13.32 28 104 09/98 Bobbin NOI 0.28 09C
-0.71 1
28 105 09/98 Bobbin WAR 19 0.66 AV3
+0.00 29 10 09/98 Bobbin WAR 14 0.40 AV3
+0.05 29 12 09/98 Bobbin WAR 11 0.43 AV2
+0.07 29 42 09/98 Bobbin HNC 19 0.34 10C
+33.72 29 50 09/98 Bobbin ADI 1.49 11C
+25.46 29 59 09/98 Bobbin HNC 12 1.51 18C
+16.37 29 65 09/98 Bobbin NOI 0.20 10C
+40.29 29 71 09/98 Bobbin HNC 17 0.30 10C
+39.33 29 74 09/98 Bobbin HNC 21 0.96 O1H
+25.85 29 75 09/98 Bobbin ADI 4.86 07H
+18.92 09/98 Bobbin HNC 15 0.65 07H
+36.84 l
29 76 09/98 Bobbin NOI 0.19 10C
+32.08 09/98 Bobbin NQI 0.21 07H
+37.66 09/98 Bobbin HNC 27 0.22 07H
+15.93 09/98 Bobbin ODI 13 0.36 10C
+22.93 i
09/98 Bobbin ODI 32 0.35 10C
+34.67 29 90 09/98 Bobbin HNI 1.22 11C
+3.98 09/98 Bobbin NQI 0.23 18C
+4.34 29 92 09/98 Bobbin HNI 0.64 15C
+15.04 29 98 09/98 Bobbin HNI 0.85 11C
+34.68 09/98 Bobbin ODI 26 0.35 16C
+12.85 29 101 09/98 Bobbin ODI B
0.54 19C
+5.15 30 24 09/98 Bobbin HNC 8
0.59 10C
+44.56 30 30 09/98 Bobbin HNI 0.76 04H
+38.20 l
30 39 09/98 Bobbin HNC 27 1.79 10C
+27.79 30 41 09/98 Bobbin HNI 0.46 16C
+5.31 l
09/98 Bobbin HNI 1.91 16C
+13.37 09/98 Bobbin HNI 3.78 16C
-1.16 i
09/98 Bobbin HNC 13 0.99 16C
+1.68 f
09/98 Bobbin HNI 0.90 06H
+10.64 to
+24.27 l
09/98 Bobbin HNI 1.30 17C
+34.19 to
+16.84 09/98 C/L Special Interest VOL 0.72 16C
-3.60 09/98 C/L Special Interest VOL 0.90 16C
+1.33
FTI TUBAN II (Vcrsion 2.3) 01/21/1999 11:27:12 Catcwba Nucle =r Stction - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND LTH VOLTS LOCATION 09/98 C/L Special Interest VOL 1.04 16C
-1.35 30 54 09/98 Bobbin HNI 0.81 14C
+10.38 09/98 Bobbin HNC 18 1.74 05H
+5.03 30 64 09/98 Bobbin ODI 18 0.39 10C
+40.44 09/98 Bobbin ODI 25 0.51 07H
+33.47 09/98 Bobbin ODI 33 0.37 10C
+37.68 30 67 09/98 Bobbin ADI 2.61 13C
+7.91 09/98 Bobbin ADI 4.53 AV1
+7.54 30 72 09/98 Bobbin HNI 0.18 11C
+19.10 09/98 Bobbin HNI 0.56 12C
+19.21 09/98 Bobbin HNC 17 0.89 05H
+10.88 09/98 C/L Special Interest VOL 0.71 12C
+19.21 30 75 09/98 Bobbin HNC 17 1.56 11C
+14.50 30 81 09/98 Bobbin NOI 0.87 11C
+35.68 09/98 Bobbin ODI 5
0.36 07H
+7.12 09/98 Bobbin ODI 23 0.19 11C
+18.78 09/98 Bobbin ODI 26 0.30 10C
+43.32 30 87 09/98 Bobbin HNI 0.64 02H
+19.35 31 12 09/98 Bobbin WAR 20 0.61 AV3
+0.00 31 24 09/98 Bobbin HNC 23 0.71 10C
+28.74 31 44 09/98 Bobbin HNI 0.53 03H
+10.88 l
31 49 09/98 Bobbin HNC 30 1.66 09C
+3.30 31 66 09/98 Bobbin HNI 1.66 10C
+40.04 09/98 Bobbin NQI 0.19 10C
+35.75 31 69 09/98 Bobbin ODI 16 0.47 14C
+1.46 31 94 09/98 Bobbin ODI 13 0.33 17C
+9.99 32 12 09/98 Bobbin HNI 0.16 11C
+28.50 09/98 Bobbin HNI 0.23 11C
+11.26 09/98 Bobbin WAR 14 0.39 AV1
-0.07 i
09/98 Bobbin WAR 25 0.89 AV2
+0.16 09/98 Bobbin WAR 32 1.44 AV4
+0.00 1
09/98 Bobbin WAR 42 2.79 AV3
+0.07 09/98 UBEND SPEC. INT.
VOL 0.46 AV1
+0.02 09/98 UBEND SPEC. INT.
VOL 0.65 AV2
+0.08 09/98 UBEND SPEC. INT.
VOL 0.68 AV4
-0.09 i
09/98 UBEND SPEC. INT.
VOL 1.16 AV3
+0.08 32 23 09/98 Bobbin ODI 16 0.30 07H
+44.70 32 43 09/98 Bobbin HNC 8
0.44 11C
+20.07 32 45 09/98 Bobbin HNI 0.51 10C
+22.06 32 46 09/98 Bobbin HNI 0.57 06H
+40.04 32 47 09/98 Bobbin HNI 1.63 AV1
+14.10 09/98 UBEND SPEC. INT.
VOL 1.58 AV1
+13.66 32 61 09/98 Bobbin ADI 1.82 05H
+18.48 32 62 09/98 Bobbin ODI 22 0.37 14C
+6.17 32 65 09/98 Bobbin HNI 1.32 10C
+14.06 32 71 09/98 Bobbin NOI 0.33 12C
+22.00 09/98 Bobbin NQI 1.16 AV3
+5.21 09/98 Bobbin HNC 10 0.73 12C
+23.08 32 73 09/98 Bobbin HNC 21 0.50 12C
+33.94 32 77 09/98 Bobbin HNC 8
1.51 AV1
+17.42 32 82 09/98 Bobbin HNI 0.36 12C
+21.34 32 83 09/98 Bobbin NOI 0.25 07H
+3.64 32 81 09/98 Bobbin HNI 0.80 O1H
+24.03 32 85 09/98 Bobbin HNC 23 0.26 16C
+5.67 32 86 09/98 Bobbin HNI 1.44 AV4
+7.13 32 90 09/98 Bobbin NOI 0.32 07H
+44.36 32 92 09/98 Bobbin ODI 32 0.27 14C
+16.50 32 93 09/98 Bobbin HNI 0.35 05H
+25.69 l
32 96 09/98 Bobbin NQI 0.37 13C
+1.90 l
32 103 09/98 Bobbin ODI 17 0.46 10C
+35.22 t
33 12 09/98 Bobbin ODI 18 0.18 17C
+4.45 09/98 Bobbin WAR 18 0.51 AV2
-0.06 09/98 Bobbin WAR 23 0.71 AV1
-0.01 09/98 Bobbin WAR 23 0.71 AV1
-0.01 33 14 09/98 Bobbin WAR 10 0.25 AV3
+0.14
l l
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:27:12 Catawb3 Nuclser Stction - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - IIH)ICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND LTW VOLTS LOCATION 09/98 Bobbin WAR 20 0.58 AV2
-0.08 09/98 UBEND SPEC. INT.
VOL 0.46 AV3
+0.10 1
09/98 UBEND SPEC. INT.
VOL 0.70 AV2
-0.05 33 17 09/98 Bobbin HNI 0.67 O1H
+26.07 09/98 Bobbin HNI 0.82 O1H
+26.69 33 45 09/98 Bobbin HNI 0.72 16C
+14.60 33 49 09/98 Bobbin HNC 15 2.80 O1H
+11.64 09/98 H/L Special Interest VOL 3.54 O1H
+11.64 33 55 09/98 Bobbin HNC 20 0.75 AV1
+11.85 33 59 09/98 Bobbin HNC 13 2.08 10C
+36.54 33 64 09 98 Bobbin ODI 14 1.12 04H
+9.75 33 65 09 98 Bobbin ADI 1.84 04H
+6.22 09 98 Bobbin HNI 1.24 02H
+13.17 09/98 H/L Special Interest VOL 0.18 04H
+6.81 09/98 H/L Special Interest VOL 0.28 02H
+13.27 33 68 09/98 Bobbin HNC 28 0.67 10C
+39.35 33 80 09/98 Bobbin HNI 0.50 18C
+3.97 33 90 09/98 Bobbin HNI 0.53 17C
+3.76 33 94 09/98 Bobbin HNC 25 0.27 10C
+41.65 34 14 09/98 Bobbin HNI 0.17 11C
+5.84 1
34 20 09/98 Bobbin HNI 0.44 05H
+3.64 09/98 Bobbin HNI 0.52 06H
+9.81 09/98 Bobbin HNI 0.56 12C
+15.48 09/98 Bobbin HNI 0.57 07H
+40.53 09/98 Bobbin HNI 0.67 14C
+3.80 09/98 Bobbin HNI 0.93 10C
+6.06 34 22 09/98 Bobbin HNC 19 0.49 10C
+3.94 34 24 09/98 Bobbin HNC 14 1,42 09C
+1.54 34 28 09/98 Bobbin HNI 0.39 13C
+32.17 09/98 Bobbin HNI 0.42 13C
+27.14 09/98 Bobbin NQI 0.30 13C
+19.01 09/98 Bobbin HNC 22 0.53 13C
+24.95 34 33 09/98 Bobbin ODI 9
0.40 11C
+34.27 34 39 09/98 Bobbin HNC 14 0.54 11C
+10.53 34 63 09/98 Bobbin NQI 0.28 06H
+36.61 34 68 09/98 Bobbin HNI 1.11 11C
+6.36 34 72 09/98 Bobbin ADI 0.85 03H
+21.25 09/98 Bobbin ADI 0.86 05H
+36.16 09/98 Bobbin ADI 0.98 03H
+22.70 09/98 Bobbin ADI 2.03 O1H
+3.40 09/98 Bobbin HNI 0.65 18C
+7.90 09/98 Bobbin NOI 0.47 10C
+38.36 09/98 Bobbin HNC 24 0.39 10C
+0.81 09/98 C/L Special Interest VOL 0.52 10C
+8.81 09/98 C/L Special Interest VOL 0.71 09C
-7.24 09/98 C/L Special Interest VOL 0.93 18C
+8.07 09/98 H/L Special Interest VOL 0.17 O1H
+3.55 09/98 H/L Special Interest VOL 1.19 03H
+22.75 09/98 H/L Special Interest VOL 1.57 03H
+21.27 34 88 09/98 Bobbin HNI 0.58 10C
+11.54 35 19 09/98 Bobbin NQI 0.27 10C
+36.61 35 24 09/98 Bobbin HNI 0.22 11C
+20.94 09/98 Bobbin HNI 0.60 04H
+10.14 09/98 Bobbin HNI 1.22 10C
+5.94 09/98 Bobbin ODI 18 0.31 09C
-0.70 35 27 09/98 Bobbin HNC 6
0.82 O1H
+15.55 35 34 09/98 Bobbin HNC 18 0.47 14C
+12.54 35 41 09/98 Bobbin HNI 0.55 11C
+33.78 35 61 09/98 Bobbin HNI 0.28 04H
+12.56 09/98 Bobbin NOI 0.30 08H
-0.10 35 64 09/98 Bobbin HNI 0.87 02H
+22.02 35 65 09/98 Bobbin HNC 25 1.09 TSH
+1.38 1
09/98 Bobbin ODI 4
0.61 O1H
+5.85 w,D9/98 H/L Tubesheet VOL 0.89 TSH
+1.42 09/98 H/L Special Interest VOL 1.20 O1H
+6.25
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:27:12 Catawba Nuclear Stetion - Unit Two S/G C 09/98 RFO J
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS
~
INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 35 74 09/98 Bobbin NOI 0.32 08H
-0.54 09/98 Bobbin HNC 15 0.78 IOC
+39.87 35 80 09/98 Bobbin HNC 24 0.52 17C
+7.66 35 87 09/98 Bobbin ODI 30 0.36 04H
+14.92 35 89 09/98 Bobbin HNC 3
2.26 07H
+6.55 36 21 09/98 Bobbin HNC 9
0.78 10C
+35.87 36 31 09/98 Bobbin HNC 6
1.93 11C
+36.93 09/98 C/L Special Interest VOL 0.76 10C
-6.12 36 40 09/98 Bobbin HNC 8
0.92 13C
+40.50 09/98 C/L Special Interest VOL 0.67 12C
-2.36 36 85 09/98 Bobbin HNI 0.30 10C
+42.76 09/98 Bobbin HNI 0.35 10C
+23.36 09/98 Bobbin NOI 0.40 08H
-0.51 09/98 Bobbin NOI 1.49 08H
+1.62 09/98 Bobbin HNC 25 0.41 10C
+30.84 1
09/98 Bobbin HNC 31 0.24 10C
+26.27 09/98 C/L Special Interest VOL 0.40 09C
-14.03 09/98 C/L Special Interest VOL 0.92 09C
-21.19 36 98 09/98 Bobbin WAR 17 0.46 AV2
+0.00 37 23 09/98 Bobbin HNC 33 0.19 11C
+34.89 1
37 40 09/98 Bobbin HNI 0.40 02H
+19.11 09/98 Bobbin HNI 1.05 AV1
+17.89
)
09/98 Bobbin HNI 2.11 04H
+20.61 09/98 Bobbin HNC 20 1.06 07H
+2.67 09/98 H/L Special Interest VOL 0.93 02H
+20.04 09/98 H/L Special Interest VOL 1.03 02H
+20.04 09/98 H/L Special Interest VOL 1.83 07H
+2.61 09/98 H/L Special Interest VOL 2.20 07H
+2.61 37 41 09/98 Bobbin HNI 1.35 09C
+24.91 37 45 09/98 Bobbin HNI 1.01 09C
+1.45 37 55 09/98 Bobbin ODI 19 1.04 17C
+1.51 09/98 C/L Special Interest VOL 0.57 17C
+1.54 2
37 61 09/98 Bobbin HNI 0.49 11C
+26.65 l
09/98 Bobbin NOI 0.53 AV3
+19.26 09/98 Bobbin ODI 14 1.11 13C
+34.78 09/98 Bobbin ADI 3.28 11C
+36.24 to
+41.69 09/98 C/L Special Interest VOL 1.13 12C
-8.02 37 68 09/98 Bobbin HNI 0.91 12C
+29.44 37 90 09/98 Bobbin HNC 16 1.08 TSH
+5.58 37 98 09/98 Bobbin ODI 13 1.47 09C
+12.95 38 17 09/98 Bobbin WAR 17 0.50 AV2
+0.00 38 23 09/98 Bobbin WAR 8
0.33 AV4
+0.05 09/98 UBEND SPEC. INT.
VOL 2.37 AV4
+0.04 38 27 09/98 Bobbin HNC 5
1.57 11C
+25.65 38 34 09/98 Bobbin WAR 13 0.35 AV2
-0.08 38 39 09/98 Bobbin HNC 13 0.98 17C
+5.61 09/98 Bobbin HNC 29 0.48 10C
+28.37 09/98 Bobbin ODI 26 0.31 07H
+40.26 38 41 09/98 Bobbin HNC 8
1.49 AV1
+13.20 09/98 Bobbin HNC 12 0.44 AV1
+23.54 09/98 Bobbin ODI 15 0.30 14C
+13.42 09/98 Bobbin ODI 28 0.41 11C
+22.54 38 47 09/9J Bobbin NQI 0.22 AV1
+26.41 38 63 09/98 Bobbin HNI 0.71 02H
+11.48 38 69 09/98 Bobbin HNI 0.56 04H
+16.08 38 72 09/98 Bobbin ADI 0.26 11C
+31.64 l
09/98 Bobbin ODI 14 0.24 16C
+6.42 38 74 09/98 Bobbin HNC 4
1.71 10C
+34.77 09/98 Bobbin ODI 19 2.63 09C
+22.64 38 88 09/98 Bobbin ADI 4.46 09C
+17.09 38 90 09/98 Bobbin ODI 11 3.62 19C
+5.01 09/98 C/L Special Interest VOL 1.57 19C
+5.17 38 94 09/98 Bobbin HNI 2.91 AV4
+13.46 09/98 Bobbin HNI 3.79 04H
+12.14 38 96 09/98 Bobbin HNC 5
1.10 10C
+26.89
_ _ _ _ _ _ I l
I FTI TUBAN II (Varsion 2.3) 01/21/1999 11:27:12 Catswba Nuclcar Stetion - Unit Two l
S/G C 09/98 RFO
)
~ Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
1 ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION l
38 ~ 97 09/98 Bobbin HNC 16 0.81 10C
'+39.47 09/98 Bobbin WAR 19 0.60 AV2
-0.05 38 99 09/98 Bobbin WAR 22 0.74 AV3
+0.05 09/98 Bobbin WAR 34 1.60 AV4
+0.02 09/98 UBEND SPEC. INT.
VOL 0.66 AV3
-0.18 09/98 UBEND SPEC. INT.
VOL 0.97 AV4
-0.01 39 17 09/98 Bobbin WAR 9
0.23 AV1
-0.11 39 27 09/98 Bobbin WAR 19 0.58 AV3
-0.05 39 40 09/98 Bobbin ODI 22 0.32 11C
+37.15 39 46 09/98 Bobbin HNC 12 0.37 13C
+12.75 09/98 C/L Special Interest VOL 0.86 13C
+12.79 39 62 09 98 Bobbin HNI 1.03 13C
+15.22 09 98 C/L Special Interest VOL 1.23 13C
+16.72 39 66 09/98 Bobbin ODI 11 1.50 04H
+27.09 09/98 H/L Special Interest VOL 1.67 04H
+27.09 39 73 09/98 Bobbin NOI 0.38 10C
+38.86 39 80 09/98 Bobbin ODI 16 0.30 07H
+33.33 39 94 09/98 Bobbin WAR 17 0.49 AV3
+0.00 39 97 09/98 Bobbin WAR 12 0.32 AV3
+0.00 09/98 Bobbin WAR 14 0.36 AV2
+0.00 09/98 Bobbin WAR 19 0.52 AV4
+0.00 39 98 09/98 Bobbin HNI 0.27 10C
+32.18 09/98 Bobbin HNI 0.34 10C
+36.94 40 18 09/98 Bobbin NQI 0.60 09C
+1.57 09/98 Bobbin WAR 11 0.28 AV3
-0.19 09/98 Bobbin WAR 13 0.33 AV4
-0.07 09/98 Bobbin WAR 14 0.37 AV1
-0.12 09/98 UBEND SPEC. INT, VOL 0.35 AV4
+0.00 40 19 09/98 Bobbin ODI 22 0.35 10C
+29.16 09/98 Bobbin ODI 25 0.33 09C
+1.59 40 69 09/98 Bobbin HNI 0.58 11C
+21.63 09/98 Bobbin HNI 0.80 07H
+11.42 40 76 09/98 Bobbin HNC 6
1.04 11C
+29.58 09/98 C/L Special Interest VOL 0.85 11C
+28.14 09/98 C/L Special Interest VOL 1.06 11C
+29.81 40 81 09/98 Bobbin HNI 0.33 TSH
+3.76 40 82 09/98 Bobbin HNC 3
0.35 06H
+34.04 40 84 09/98 Bobbin HNI 0.39 11C
+28.35 40 85 09/98 Bobbin ODI 14 1.50 TSH
+0.75 09/98 H/L Tubesheet
.VOL 1.13 TSH
+0.75 09/98 H/L Special Interest VOL 1.65 TSH
+0.15 40 88 09 98 Bobbin HNC 17 0.38 10C
+33.79 40 90 09 98 Bobbin HNC 14 2.91 11C
+26.30 40 97 09/98 Bobbin HNC 1
0.80 10C
+37.99 i
41 20 09/98 Bobbin WAR 11 0.27 AV2
-0.01 l
09/98 Bobbin WAR 13 0.34 AV3
-0.19 09/98 Bobbin WAR 14 0.39 AV1
-0.06 41 34 09/98 Bobbin HNC 3
0.42 14C
+10.01 41 44 09/98 Bobbin HNI 1.79 09C
+1.79 i
41 46 09/98 Bobbin HNC 23 1.65 09C
+2,02 41 53 09/98 Bobbin ODI 19 0.27 100
+43.19 i
41 61 09/98 Bobbin ADI 1.51 12C
+31.49 I
41 68 09/98 Bobbin HNI 0.38 11C
+32.04 41 71 09/98 Bobbin NOI 0.24 15C
+14.39 41 83 09/98 Bobbin NOI 0.93 05H
+34.26 09/98 H/L Special Interest VOL 1.91 05H
+34.26 l
42 26 09/98 Bobbin HNI 1 30 AV2
+10.80 42 51 09/98 Bobbin HNI 0.92 11C
+30.69 l
09/98 Bobbin ODI 10 0.50 10C
+16.67 i
t 42 68 09/98 Bobbin HNC 22 0.87 12C
+19.77 42 80 09/98 Bobbin HNI 0.73 11C
+1.52 42 84 09/98 Bobbin HNI 0.29 05H
+36.32 42 87 09/98 Bobbin HNI 0.61 19C
+5.72 42 89 09 98 Bobbin HNC 12 0.55 07H
+22.84 42 90 09 98 Bobbin HNC 11 0.57 14C
+5.52
FTI TUBAN II (Varsion 2.3)-
01/21/1999 11:27:12 Catcwb2 Nuclser Stction - Unit Two S/J C 09/98 RFO Cobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 43 23 09/98 Bobbin HNI 1.16 O1H
+3.70 09/98 Bobbin HNC 10 1.35 07H
+15.23 43 29 09/98 Bobbin HNC 2
1.49 16C
+9.51 09/98 Bobbin ODI 14 0.83 17C
+15.88 43 45 09/98 Bobbin HNI 0.72 11C
+9.73 09/98 Bobbin NOI 0.59 10C
+43.78 43 55 09/98 Bobbin HNC 6
1.49 11C
+20.50 09/98 Bobbin HNC 10 2.41 05H
+42.14 43 59 09/98 Bobbin ODI 9
1.26 IOC
+15.17 43 66 09/98 Bobbin HNC 32 0.20 06H
+33.33 43 74 09/98 Bobbin ADI 1.19 06H
+35.95 09/98 Bobbin HNC 2
0.61 05H
+32.15 43 86 09/98 Bobbin HNI 0.62 13C
+40.00 09/98 Bobbin HNI 0.64 13C
+29.14
'~
09/98 Bobbin HNI 1,46 12C
+11.63 09/98 Bobbio HNI 3.02 12C
+10.04 09/98 C/L Special Interest VOL 0.88 12C
+10.04 09/98 C/L Special Interest VOL 1.03 12C
+11.63 43 92 09/98 Bobbin ODI 24 0.35 10C
+32.56 09/98 C/L Special Interest VOL 0.42 09C
-13.44 44 23 09/98 Bobbin WAR 14 0.58 AV3
-0.12 09/98 UBEND SPEC. INT.
VOL 0.12 AV3
+0.06 44 43 09/98 Bobbin NQI 0.40 18C
+14.03 09/98 Bobbin NOI 0.57 18C
+15.24 44 41 09/98 Bobbin ODI 10 0.62 13C
+39.35 09/98 Bobbin ODI 17 1.04 13C
+38.71 44 46 09/98 Bobbin NOI 0.25 13C
+1.94 44 54 09/98 H/L Tubesheet "OL 1.51 TSH
+0.72 44 71 09/98 Bobbin ODI 19 0.45 18C
+2.63 44 76 09/98 Bobbin HNC 12 0.66 14C
+5.67 44 82 09/98 Bobbin WAR 11 0.28 AV4
+0.00 09/98 Bobbin WAR 26 0.89 AV3
+0.00 09/98 Bobbin WAR 33 1.34 AV2
+0.00 09/98 UBEND SPEC. INT.
VOL 0.27 AV4
-0.20 09/98 UBEND SPEC. INT.
VOL 0.78 AV3
-0.12 09/98 UBEND SPEC. INT.
VOL 0.93 AV2
+0.27 44 86 09/98 Bobbin ODI 6
0.42 11C
+30.49 09/98 Bobbin ODI 6
0.56 11C
+15.78 44 87 09/98 Bobbin HNI 2.86 18C
+11.17 09/98 Bobbin ODI 14 0.24 11C
+39.15 09/98 C/L Special Interest VOL 1.08 17C
-7.42 44 88 09/98 Bobbin HNI 0.51 16C
+11.38 44 92 09/98 Bobbic WAR 8
0.21 AV4
+0.07 09/98 Bobbin WAR 10 0.25 AV3
+0.00 45 50 09/98 Bobbin HNC 3
1.80 17C
+25.98 45 54 09/98 Bobbin ODI 3
1.20 03H
+19.47 09/98 H/L Special Interest VOL 2.28 03H 19.47 45 59 09/98 Bobbin ADI 2.94 09C
+31.88 09/98 Bobbin HNI 0.27 11C
+18.02 09/98 Bobbin HNI 0.43 04H
+8.77 09/98 Bobbin HNI 0.83 13C
+24.16 09/98 Bobbin NQI 0.51 11C
+0.57 09/98 Bobbin HNC 29 2.72 13C
+6.85 09/98 C/L Special Interest VOL 1.45 13C 46.62 45 60 09/98 Bobbin ADI 1.27 13C
+18.03 09/98 C/L Special Interest VOL 0.75 13C
+19.58 45 61 09/98 Bobbin HNI O.84 13C
+18.20 45 62 09/98 Bobbin HNC 14 1.99 02H
+12.53 09/98 H/L Special Interest VOL 0.36 02H
+12.25 45 67 09/98 Bobbin HNC 27 0.83 02H
+14.20 45 70 09/98 Bobbin NOI 0.33 O1H
+7.45 09/98 Bobbin NOI 0.55 01H
+8.91 45 86 09/98 Bobbin HNI 0.78 12C
+40.97
(
45 88 09/98 Bobbin HNC 5
0.71 07H
+39.80 09/98 Bobbin HNC 7
0.97 02H
+18.69
FTI TUBAN II (Vareion 2.3) 01/21/1999 11:27:12 C;ttwba NuclOnr Stction - Unit Two S/G C 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 10 1.07 07H
+42.47 46 34 09/98 Bobbin HNI 0.66 12C
+11.79 09/98 C/L Special Interest VOL 0.70 12C
+12.15 46 41 09/98 Bobbin HNC 16 0.80 07H
+6.38 46 46 09/98 Bobbin HNI 0.47 11C
+39.51 09/98 C/L Special Interest VOL 0.67 11C
+39.27 46 47 09/98 Bobbin HNI 0.86 13C
+17.88 09/98 Bobbin HNC 7
0.60 13C
+4.72 09/98 Bobbin HNC 21 1.27 13C
+10.10 46 49 09/98 Bobbin HNC 12 0.35 11C
+31.52 46 55 09/98 Bobbin HNC 29 0.60 07H
+44.70 46 73 09/98 Bobbin NOI 0.13 08H
-0.51 46 75 09/En Bobbin HNC 6
1.17 13C
+9.18 46 81 09/9a Bobbin ODI 17 0.30 12C
+32.82 09/98 C/L Special Interest VOL 0.62 12C
+32.34 46 89 09/98 Bobbin ODI 36 0.35 10C
+30.38 47 28 09/98 Bobbin ODI 14 0.82 TSH
+4.63 09/98 H/L Special Interest VOL 0.98 TSH
+4.62 47 42 09/98 Bobbin HNC 22 0.39 15C
+32.91 09/98 Bobbin ODI 8
0.39 11C
+41.98 09/98 Bobbin ODI 15 5.03 09C
+26.99 47 49 09/98 Bobbin HNI 1.96 12C
+6.94 47 65 09/98 Bobbin ODI 14 0.43 04H
+6.06 47 67 09/98 Bobbin ADI 1.88 08H
+18.56 47 75 09/98 Bobbin HNI 0.28 08H
-0.54 47 76 09/98 Bobbin HNI 0.29 08H
-0.59 47 82 09/98 Bobbin HNI 0.95 ISC
+26.70 48 29 09/98 Bobbin HNI 1.41 11C
+14.88 09/98 Bobbin HNC 5
0.61 15C
+21.21 09/98 Bobbin HNC 7
1.19 11C
+39.64 09/98 Bobbin ODI 4
0.43 10C
+41.16 I
48 37 09/98 Bobbin HNC 2
1.46 AV1
+30.55 48 45 09/98 Bobbin HNI 0.87 15C
+31.96 09/98 Bobbin HNI 0.94 05H
+13.58 09/98 H/L Special Interest VOL 1.56 05H
+14.49 48 48 09/98 Bobbin HNI 0.35 17C
+25.64 09/98 Bobbin HNI 0.70 13C
+18.12 09/98 Bobbin NOI 0.45 13C
+36.04 48 49 09/98 Bobbin ODI 11 0.37 11C
+31.47 48 50 09/98 Bobbin NOI 0.54 12C
+41.75 48 52 09/98 Bobbin HNC 3
0.54 15C
+29.67 09/98 Bobbin HNC 29 0.28 15C
+29.41 48 53 09/98 Bobbin HNI 0.86 04H
+10.73 48 59 09/98 Bobbin HNI 0.27 17C
+5.29 48 60 09/98 Bobbin HNI 0.65 13C
+31.41 09/98 Bobbin NOI 0.32 13C
+11.57
+
48 75 09/98 Bobbin HNC 7
0.64 06H
+21.23 48 76 09/98 Bobbin HNC 2
1.32 15C
+7.04 09/98 Bobbin HNC 2
3.94 10C
+6.43 48 86 09/98 Bobbir, NOI 0.16 17C
+19.39 09/98 Bobbin HNC 2
0.88 IBC
+13.99 09/98 Bobbin HNC 10 3.78 11C
+15.50 09/98 Bobbin 3DI 16 1,41 18C
+4.67 09/98 C/L Special Interest JOL 0.96 18C
+4.67 49 31 09/98 Bobbin ADI 4.06 03H
+10.23 to
+35.38 09/98 H/L Special Interest VOL 2.20 03H
+10.23 to
+35.38 49 43 09/98 Bobbin ODI 11 0.21 19C
+7.76 49 46 09/98 Bobbin ODI 28 0.62 17C
+7.62 4 :.
30 09/98 Bobbin IINI 0.37 15C
+21.08 4y b2 09/98 Bobbin HNI 0.66 15C
+5.91 49 55 09/98 Bobbin HNI 0.47 07H
+38.49 09/98 Bobbin HNC 19 0.40 07H
+43.72 49 59 09/98 Bobbin HNC 8
1.53 11C
+35.81 09/98 Bobbin ODI 7
1.90 09C
+12.13 49 63 09/98 Bobbin ODI 21 0.53 ISC
+31.80 l
l l
~. -... --.
-~ - - - ~
-.. - - -.. -.. - ~ - ~. - - - - - - - - -..
)
l FTI TUBAN II (Version 2.3) 01/21/1999 11:27:12 Catswb2 Nuclear Station - Unit Two S/G C 09/98 RFO Cobbin,C/L Special Interest, Expansion +Pt->17&18,H/L Special Interest,H/L Tubesheet,MRPC j
l Page 16 i
ATTACHMENT'#3 - INDICATIONS OF IMPEP.FECTIONS j
INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 C/L Special Interest VOL 0.68 15C
+32.43 l
49 65 09/98 Bobbin HNI 0.33 11C
+16.34 09/98 Bobbin HNI 0.48 05H
+33.23 j
09/98-Bobbin HNC 6
0.71 05H
+35.86 2
09/98 Bobbin ODI 8
0.99 09C
+10.70 09/98 Bobbin ODI 20 0.33 19C
+4.90 49 69 09/98 Bobbin NQI 0.33 12C
+21.06 49 72 09/98 Bobbin HNI 0.53 17C
+6.99 09/98 Bobbin WAR 10 0.30 AV3
+0.00 09/98 Bobbin WAR 13 0.39 AV4
+0.00 1
49 73 09/98 Bobbin NQI 0.47 08H
+4.49
)
49 74 09/98 Bobbin NOI 0.24 09C
-0.70 49 76 09/98 Bobbin WAR 31 1.20 AV1
-0.69 09/98 UBEND SPEC. INT.
VOL 0.34 AV1
+0.00 J
49 81 09/98 Bobbin HNC 6
0.83 15C
+26.90 Total Indications Found = 990 Total Tubes Found = 562 l
l l
- -... - -.. ~ ~_ - -,,- -.. - ~.-.
. ~-
l l
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 Catawba Nuclear Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC
~
ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 1
1 09/98 Bobbin NQI 0.29 13C
+18.05 09/98 Bobbin NQI 0.31 13C
+11.87 1
3 09/98 Bobbin ADI 1.82 TSC
+4.89 1
09/98 Bobbin ODI 6
0.28 04H
+11.94 1
9 09/98 Bobbin HNI 0.97 05H
+13.93 1 30 09/98 Bobbin HNI 0.75 07H
+12.08 1 32 09/98 Bobbin HNI 1.54 13C
+21.12 09/08 Bobbin HNC 25 0.62 12C
+24.21 1 34 09/98 Bobbin HNI 2.92 03H
+29.04 1 37 09/98 Bobbin HNI 0.38 05H
+33.08 09/98 Bobbin HNI 0.67 05H
+33.90 09/98 Bobbin HNI 0.55 12C
+32.70 to
+37.01 1 58 09/98 Bobbin NQI 0.17 18C
+34.54 1 59 09/98 Bobbin HNI 0.70 12C
+18.13 1 65 09/98 H/L Tubesheet VOL 0.98 TSH
+1.30 1 66 09/98 Bobbin HNC 12 2.81 10C
+32.69 1 94 09/98 Bobbin HNI 2.38 18C
+14.16 to
+19.82 1 95 09/98 Bobbin HNC 2
1.77 18C
+3.79 1 97 09/98 H/L Tubesheet VOL 0.21 TSH
+0.07 2
2 09/98 Bobbin HNI 2.64 18C
+29.13 2
3 09/98 Bobbin HNI 0.74 05H
+31.47 09/98 Bobbin HNI 7.87 13C
+25.83 09/98 Bobbin HNC 11 1.75 03H
+26.91 09/98 C/L Special Interest VOL 1.39 13C
+25.83 09 98 H/L Special Interest VOL 1.47 03H
+26.86 2
7 09 98 Bobbin HNI 1.18 07H
+15.78 2 30 09/98 Bobbin HNC 15 0.98 12C
+7.03 09/98 C/L Special Interest VOL 0.85 12C
+7.03 2 45 09/98 Bobbin HNI 0.75 O1H
+25.51 2 51 09/98 Bobbin HNI 2.69 TSC
+6.12 2 58 09/98 Bobbin HNI 0.45 11C
+3.10 2 72 09/98 Bobbin HNI 3.68 16C
+29.38 09/98 Bobbin HNC 17 1.01 05H
+14.42 2 85 09/98 Bobbin NQI 1.78 TSH
+3.55 09/98 Bobbin ODI 20 0.41 TSH
+3.88 2 86 09/98 Bobbin NQI 1.06 TSH
+2.29 09/98 Bobbin NOI 1.38 04H
+38.23 2 90 09/98 Bobbin ADI 0.97 O1H
+9.72 2 91 09/98 Bobbin ODI 16 1.20 07H
+24.73 2 95 09/98 Bobbin HNI 1.75 18C
+1.19 to
+20.06 2 102 09/98 Bobbin ODI 23 0.43 05H
+2.47 2 109 09/98 Bobbin HNI 1.22 12C
+20.77 2 113 09/98 Bobbin HNI 1.70 16C
+32.47 2 114 09/98 Bobbin ODI 15 0.42 TSC
+3.07 09/98 C/L Special Interest VOL 1.08 TSC
+3.37 3
4 09 98 Bobbin HNC 16 0.47 07H
+35.70 3
5 09 98 Bobbin ADI 1.75 13C
+35.69 3
6 09/98 Bobbin HNI 0.70 10C
+19.29 3
9 09/98 Bobbin HNI 0.73 13C
+34.73 09/98 Bobbin HNC 3
3.61 10C
+35.74 09/98 Bobbin ODI 14 4.95 09C
-8.83 I
09/98 C/L Special Interest VOL 3.02 10C
+35.74 l
3 13 09/98 Bobbin HNC 12 2.86 17C
+12.99 09/98 C/L Special Interest VOL 1.90 17C
+14.04 3 24 09/98 Bobbin HNI 0.54 IBC
+8.46 3 29 09/98 Bobbin HNI 0.28 10C
+14.72 09/98 Bobbin HNI 1.06 12C
+36.12 l
i 09/98 Bobbin HNC 7
1.21 11C
+35.82 09/98 C/L Special Interest VOL 0.91 11C
+35.82 l
3 37 09/98 Bobbin HNI 0.38 10C
+25.94 09/98 Bobbin HNI 0.69 07H
+25.67 3 58 09/98 Bobbin HNI 0.53 16C
+12.98 3 64 09/98 Bobbin HNI 0.65 13C
+17.54 3 70 09/98 Bobbin NOI 0.43 11C
+26.28 09/98 Bobbin HNC 17 0.59 11C
+33.23 j
i
z,
_m
-__m
__.m m.. _. _. _ _, _ _ _ _. _ _ -... _ _ _.. _.._
FTI TUBAN II (Version 2.3) 01/21/1999 11:29:55 Catawba Nuclear Station - Unit Two S/G D 09/98 RPO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 3 '76 09/98 Bobbin HNC 4
1.97 10C
+16.33 4
1 09/98 Bobbin HNI 0.23 07H
-+36.33 09/98 Bobbin HNI 1.09 07H
+44.69 4
2 09/98 Bobbin HNI 0.20 07H
+23.66 09/98 Bobbin HNI 0.23 07H
+23.40 4
3 09/98 Bobbin HiiI 0.66 10c 240.85 l
09/98 Bobbin HNC 30 0.86 09C 5.49-4 4 09/98 Bobbin HNI 0.37 07H
+35.66 09/98 Bobbin ODI 11 0.34 07H
+18.20
)
4 5 09/98 Bobbin HNC 32 0.66 07H
+41.41 09/D8 Bobbin ODI 27 0.61 07H
+40.99 i
4 6 09/98 Bobbin HNI 0.38 10C
+22.13 4 -12'09/98 Bobbin HNI 0.35 07H
+25.17 4 31 09/98 Bobbin HNI 0.88 18C
+5.55 l
4-51 09/98 Bobbin HNI 0.80 16C
+5.61 1
4 53 09/98 Bobbin HNI 1.80 03H
+13.55 09/98 H/L Special Interest VOL 1.40 03H
+12.74 4 56 09/98 Bobbin NOI 0.52 13C
+5.06 09/98 Bobbin ODI 12 2.01 10C
+23.51 4 65 09/98 Bobbin HNI 2.09 15C
+8.76 to
+13.38 4 68 09/98 Bobbin HNI 0.98 02H
+3.04 4 90 09/98 Bobbin DWI 0.66 TSH
+1.66 4 94 09 98 Bobbin HNI 0.61 12C
+40.31 4 109 09 98 Bobbin HNC 19 0.65 05H
+18.04 4 113 09 98 Bobbin HNI 2.30 14C
+2.61 5
2 09/98 Bobbin HNC 3
1.30 10C
+41.55 5 11 09/98 Bobbin HNC 29 1.23 06H
+23.99 5 34 09/98 Bobbin ADI 1.61 18C
+8.08 09/98 Bobbin HNI 1.00 13C
+5.10 to
+10.22 09/98 C/L Special Interest VOL 0.50 18C
+8.08 5 35 09/98 Bobbin HNI 0.51 04H
+12.37 5 42 09/98 Bobbin ADI 1.93 13C
+32.12 09/98 Bobbin HNI 2.87 17C
+11.79 5 58 09/98 Bobbin HNC 19 0.37 14C
+16.13 5 65 09/98 Bobbin HNI 1.95 13C
+39.83 09/98 Bobbin HNI 2.56 11C
+18.75 5 88 09/98 Bobbin HNI 0.66 05H
+20.24 5 101 09/98 Bobbin ADI 1.64 O1H
+17.71 5 107 09/98 Bobbin HNC 4
1.19 03H
+16.21 6
5 09/98 Bobbin HNI 0.41 07H
+29.16 09/98 Bobbin ODI 36 0.73 07H
+38.73 6 10 09/98 Bobbin HNI 0.37 07H
+26.93 6 11 09/98 Bobbin HNC 11 0.77 10C
+30.57 6 18 09/98 Bobbin HNI 0.44 10C
+26.46 09/98 Bobbin HNI 1.05 07H
+28.90 09/98 Bobbin HNC 7
0.48 IOC
+24.57
' 6 27 09/98 Bobbin HNI 0.54 07H
+33.41 6 42 09/98 Bobbin ADI 4.15 03H
+20.01 j
09/98 Bobbin HNI 0.50 12C
+9.15
]
6 44 09/90 Bobbin ODI 13 0.96 02H
+4.26 6 47 09/98 Bobbin ADI 1.10 15C
+2.01 09 98 Bobbin ODI 13 0.92 15C
+8.68 6 59 09 93 Bobbin HNI 0.76 02H
+33.31 6 66 09/98 Bobbin HNI 1.96 02H
+10.95 09/98 Bobbin HNI 2.61 03H
+8.34 6 68 09/98 Bobbin NOI 0.19 11C
+4.89 09/98 Bobbin HNC 30 0.91 04H
+15.44 6 77 09/98 Bobbin HNI 0.45 18C
+8.76 6 82 09 98 Bobbin HNC 17 1.44 TSH
+7.91 09 98 Bobbin ODI 10 0.48 03H
+21.61 09/98 H/L Special Interest VOL 0.59 TSH
+8.03 6 91 09/98 Bobbin HNI 2.92 04H
+10.79
)
6 100 09/98 Bobbin HNI 1.64 03H
+7.55 09/98 Bobbin HNI 1.65 03H
+5.23 7
2 09/98 Bobbin NQI 0.30 07H
+29.30
-._._... _..~ _.
I FTI TUBAN II (Varzion 2.3) 01/21/1999 11:29:55 l
Catawba Nuclear Stetion - Unit Two S/G D I
09/98 RFO f
. Kobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC
{
ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD l
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin NOI 0.39 07H
+29.01 09 98 Bobbin NQI 0.61 07H
+37.54 7
3 09 98 Bobbin HNI 1.25 10C
+28.23 7
8 09 98 Bobbin HNI 0.40 10C
+22.58 09/98 Bobbin HNI 0.40 10C
+29.05 J
09 98 Bobbin HNC 6
1.56 15C
+8.40 09 98 C/L Special Interest VOL 0.99 15C
+8.40 7 11 09 98 Bobbin HNC 5
0.63 07H
+17.76 l
09/98 Bobbin ODI 10 0.82 07H
+18.35
)
7 14 09 98 Bobbin-HNI 0.39 07H
+28.29 09 98 Bobbin HNI 1.38 12C
+3.93 1
09/98 Bobbin HNI 1.80 12C
+6.17 09/98 Bobbin HNI 3.40 15C
+1.68 09/98 Bobbin ODI 16 0.28 IOC
+5.09 f
7 36 09/98 Bobbin HNI 1.52 04H
+9.24 09/98 H/L Spezial Interest VOL 1.02 04H
+9.56 7 44 09/98 - Bobbin HNI 2.42 10C
+10.95 7 49 09/98 Bobbin NOI 0.52 O1H
+9.29 7 58 09/98 Bobbin HNI 0.78 04H
+33.71 09/98 Bobbin HNI 0.96 O1H
+6.94 7 71 09/98 Bobbin HNI 0.64 07H
+11.72 09/98 Bobbin HNI 1.65 07H
+10.59 7 84 09/98 Bobbin HNI 1.94 10C
+11.52 09/98 Bobbin HNI 2.70 10C
+10.79 7 87 05/98 Bobbin ODI 27 1.13 07H
+22.17 7 98 09/98 Bobbin HNC 16 0.60 02H
+14.14 7 99 09/98 Bobbin ODI 1
3.05 11C
+34.46 09/98 C/L Special Interest VOL 1.84 11C
+34.46 7 111 09/98 Bobbin HNI 0.86 06H
+41.14 09/98 Bobbin ODI 20 1.14 06H
+25.91 7 112 09/98 Bobbin HNC 12 1.11 11C
+31.97 8
3 09/98 Bobbin HNI 0.34 07H
+32.55 09/98 Bobbin HNI 0.35 07H
+32.98 09/98 Bobbin HNI 0.73 07H
+34.52 09/98 Bobbin HNI 0.83 07H
+34.14 8
5 09/98 Bobbin HNI 1.54 08H
+1.11 8
6 09/98 Bobbin HNI 0.27 10C
+36.83 09/98 Bobbin HNI 0.74 07H
+28.93 8
8 09/98 Bobbin HNC 23 0.74 07H
+21.79 09 98 Bobbin HNC 34 0.54 07H
+29.15 8
9 09 98 Bobbin HNC 10 0.54 10C
+35.45 09 98 Bobbin HNC 22 0.44 07H
+35.99 8 10 09 98 Bobbin HNI 0.25 07H
+19.94 8 11 09/98 Bobbin HNI 0.50 10C
+15.85 8 12 09/98 Bobbin HNI 1.36 10C
+27.57 09/98 Bobbin HNC 14 0.49 07H
+24.33 8 13 09/98 Bobbin ODI 24 0.34 07H
+31.65 09/98 Bobbin ODI 32 0.30 10C
+31.91 8 19 09/98 Bobbin HNI 1.06 05H
+16.61 8 21 09/98 Bobbin NQI 0.64 16C
+7.43 09/98 Bobbin HNC 12 1.91 02H
+7.63 09/98 Bobbin ODI 10 1.31 02H
+11.41 8 28 09/98 Bobbin HNI 1.30 09C
+1.19 8 56 09/98 Bobbin HNC 16 1.57 02H
+22.67 l
8 60 09/98 Bobbin HNI 0.70 06H
+39.86 09/98 Bobbin NOI 0.46 03H
+6.67 09/98 Bobbin HNI 0.95 02H
+8.10 to
+21.67 8 62 09/98 Bobbin NOI 0.64 04H
+19.98 8 66 09/98 Bobbin HNI 1.92 15C
+12.57 8 68 09/98 Bobbin HNI 1.69 13C
+12.93 i
8 71 09/98 Bobbin HNI 0.90 18C
+2.58 i
i 09/98 Bobbin HNI 3.92 18C
+13.02 8 84 09/98 Bobbin HNI 1.91 TSC
+2.33 8 92 09/98 Bobbin HNC 11 0.69 07H
+29.33 09/98 Bobbin HNC 14 0.93 07H
+26 11 l
- ~ - _ -. - - _. - - - -.
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 5
Cattwba Nuclear Station - Unit Two i
S/G D 09/98 RFO Eobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC t
i Page 4 ATTACHMENT #4'- INDICATIONS OF IMPERFECTIONS i
INDS OF IMPERFECTIONS - SGD I
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION t
09 98 Bobbin ODI 11 0.51 02H
+17.99 8 111 09 98 Bobbin HNC 20 0.88 02H
+15.74 l
09 98 Bobbin ODI 20 1.01 07H
+17.60 6
9 3 09 98 Bobbin ODI 18 0.24 07H
+25.77 i
9 5 09 98 Bobbin HNC 11 1.42 10C
+23.12 09 98 Bobbin ODI 7
0.80 11C
+7.44 i
09/98 Bobbin ODI 11 0.75 15C
+11.55 09/98 Bobbin ODI 13 0.40 10C
+18.04 9 10 09/98 Bobbin HNC 21 1.23 02H
+20.30 I
09 98 H/L Special Interest VOL 3.01 02H
+19.46 9 12 09 98 Bobbin HNC 17 0.55 10C
+22.61 9 20 09 98 Bobbin HNC 19 0.41 05H
+37.80 9 34 09 98 Bobbin HNI 0.76 12C
+32.25 to
+36.45 9 46 09/98 Bobbin HNI 0.38 14C
+6.78 9 47 09/98 Bobbin HNI 0.88 02H
+9.90 9 49 09/98 Bobbin HNI 2.90 03H
+2.08 to
+11.49
[
9 56 09/98 Bobbin HNC 7
1.16 13C
+18.37 9 61 09/98 Bobbin HNI 0.29 17C
+13.58 9 62 09 98 Bobbin HNC 29 0.50 O1H
+20.89 to
+23.52 9 68 09 98 Bobbin HNI 1.89 06H
+27.53 9 71 09 98 Bobbin HNC 9
0.56 02H
+3".
98 9 75 09/98 Bobbin HNC 7
1.24 O1H
+2.00 09/98 Bobbin HNC 11 1.12 02H
+11.70 09/98 Bobbin HNC 19 0.73 O1H
+15.19 i
09/98 H/L Special Interest VOL 0.94 02H
+11.62 09/9J H/L Special Interes*
VOL 1.08 O1H
+1.98 09/98 H/L Special Interest VOL 1.26 O1H
+16.14 9 88 09/98 Bobbin NOI 0.69 03H
+12.93 9 91 09/98 Bobbin HNI 0.94 13C
+28.45 10 3 09/98 Bobbin HNI 0.35 07H
+24.81 09/98 Bobbin HNI 0.71 07H
+23.05 1
10 8 09/98 Bobbin HNI 0.52 07H
+41.42 10 26 09/98 Bobbin HNI 0.25 07H
+24.81 09/98 Bobbin ODI 7 0.43 07H
+27.06 09/98 Bobbin ODI 11 0.67 07H
+26.69 09 98 Bobbin ODI 31 0.31 07H
+16.86 10 31 09 98 Bobbin HNI 0.41 10C
+14.85 09 98 Bobbin HNI 0.44 10C
+11.23 10 33 09/98 Bobbin HNI 0.28 10C
+35.52 09/98 Bobbin HNI 0.65 19C
+7.11 l-09/98 Bobbin HNI 1.21 14C
+7.57 09/98 Bobbin NQI 0.29 18C
+6.36 10 38 09/98 Bobbin HNC 15 0.77 07H
+21.22 10 51 09/98 Bobbin HNI 0.43 10C
+32.28 09/98 Bobbin NOI 0.26 10C
+26.08 10 64 09/98 Bobbin HNI 0.49 O1H
+9.60 10 76 09/98 Bobbin HNC 24 0.77 13C
+41.62
)
10 91 09/98 Bobbin HNC 12 2.23 06H
+33.74 i
10 106 09/98 Bobbin HNI 4.76 14C
+13.32 09/98 C/L Special Interest VOL 1,32 14C
+13.19 10 113 09/98 Bobbin NQI 0.34 13C
+27.74 09/98 Bobbin HNC 12 0.72 13C
+21.57 11 2 09/98 Bobbin HNC 15 0.84 10C
+38.39 l
11 4 09/98 Bobbin HNI 0.58 07H
+29.75 l
11 24 09/98 Bobbin NOI 0.54 03H
+12.01 09/98 Bobbin ODI 26 0.25 07H
+40.55 11 28 09/98 Bobbin NOI 0.25 07H
+40.24 11 37 09/98 Bobbin HNI 0.45 07H
+37.94 4
1 09/98 Bobbin HNI 0.65 10C
+5.56 09/98 Bobbin HNC 7
0.83 10C
+10.32 11 45 09/98 Bobbin HNI 0.26 02H
+32.94 11 61 09/98 Bobbin HNI 1.53 02H
+5.64 4
09/98 H/L Special Interest VOL 0.94 02H
+5.47 11 73 09/98 Bobbin HNC 2
0.65 12C
+5.15 11 83 09/98 Bobbin HNI 0.25 12C
+15.79 i
--.. _. -~. - _ _ -.... -. - _, _ _. - _ - _ _ -. -. - _. - - -. _ -
- - ~ ~. _ _
FTI TURAN II (Varsion 2.3) 01/21/1999 11:29:55
(
Catawb3 Nuclear Station - Unit Two i
S/G D r
09/98 RFO Cobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC l
ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS I
INDS OF IMPERFECTIONS - SGD ROW. COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 11 88 09 98 Bobbin HNC 15 1.50 03H
+1.91 11-93 09 98 Bobbin HNI 2.23 07H
+27.83 l
11 95 09 98 Bobbin HNI 1.65 12C
+14.82 12 3 09 98 Bobbin HNI 0.49 10C
+29.97 i
12 13 09/98 Bobbin HNC 21 2.16 13C
+41.94 12 80 09/98 Bobbin HNC 4
2.06 07H
+34.01 i
12 91 09/98 Bobbin HNI 0.61 02H
+9.88 i
13 7 09 98 Bobbin HNI 0.57 07H
+39.37 13 10 09 98 Bobbin HNC 5
1.20 12C
+25.71 13 20 09/98 Bobbin HNI 0.58 10C
+44.45 i
09/98 Bobbin ODI 10 0.26 07H
+31.83 13 28 09 98 Bobbin ODI 2
0.58 15C
+3.21 09 98 C/L Special Interest VOL 0.68 15C
+3.56 13 69 09/98 Bobbin HNI 0.92 13C
+23.98 1
09/98 Bobbin HNC 18 0.87 13C
+18.03 09/98 C/L Special Interest VOL 0.48 13C
+18.12 09/98 C/L Special Interest VOL 0.87 13C
+23.98 13 70 09 98 Bobbin HNC 19 1.23 12C
+7.62 to
+23.78 1
09 98 C/L Special Interest VOL 0.93 12C
+7.62 to
+23.78 i
l 13 84 09/98 Bobbin NQI 0.38 03H
+25.38 I
13 85 09 98 Bobbin ENI 1.65 11C
+19.00 09 98 Bobbin HNI 2.40 12C
+16.08 13 86 09 98 Bobbin HNC 8
0.33 07H-
+32.67 13 88 09 98 Bobbin HNC 24 1.15 16C
+11.66 13 90 09 98 Bobbin HNI 1.04 13C
+7.31 1
13 92 09/98 Bobbin HNC 5
2.11 12C
+21.37 1
l 09/98 Bobbin HNC 15 3.02 13C
+3.36 l
09/98 C/L Special Interest VOL 0.71 13C
+3.23 l
14 37 09/98 Bobbin HNC 19 0.64 15C
+12 71 l
14 39 09/98 Bobbin HNC 24 0.89 07H
+44.02 09/98 Bobbin ODI 36 0.24 07H
+30.00 i
14 45 09/98 Bobbin HNC 19 0.37 06H
+41.65 14 63 09/98 Bobbin HNC 17 1.24 13C
+5.01 14 69 C9/98 Bobbin HNI 1.62 15C
+6.52 14 70 09/98 Bobbin HNC 1
1.70 04H
+12.37 14 77 09/98 Bobbin HNC 18 1.30 04H
+34.89 14 82 09/98 Bobbin HNC 8
1.14 04H
+41.48 14 87 09/98 Bobbin HNC 12 1.50 13C
+23.41 14 91 09/98 Bobbin HNC 8
2.12 10C
+41.28 14 103 09/98 Bobbin HNI 0.88 07H
+4.19 15 5 09/98 Bobbin HNC 8
1.77 10C
+23.90 l
09/98 Bobbin HNC 33 0.57 10C
+23.33 15 13 09/98 Bobbin HNC 10 1.38 12C
+26.17 15 15 09/98 Bobbin ODI 4
0.79 10C
+37.85 15 36 09/98 Bobbin ADI 0.97 10C
+19.52 1
09/98 Bobbin HNI 0.62 10C
+26.61 15 49 09/98 Bobbin HNI 3.81 08H
+19.10 09/98 Bobbin HNI 3.96 AV1
+1.73 15 56 09/98 Bobbin HNC 2
1.84 11C
+30.10 15 58 09/98 Bobbin ADI 5.10 09C
+4.71 15 62 09/98 Bobbin NOI 0.52 07H
+38.69 15 87 09/98 Bobbin HNI 0.78 03H
+25.76 15 98 09/98 Bobbin HNI 0.92 10C
+11.93 15 104 09 98 Bobbin HNC 21 0.78 10C
+29.95 16 4 09 98 Bobbin HNC 22 0.29 05H
+21.30 1
16 19 09/98 Bobbin HNC 3
0.47 10C
+38.62 09/98 Bobbin HNC 4
1.45 O1H
+8.32 i
09/98 H/L Special Interest VOL 2.60 O1H
+0.52 i
16 20 09/98 Bobbin ADI 2.66 05H
+26.74 09/98 H/L Special Interest VOL 1.01 05H
+26.63 16 23 09/98 Bobbin HNC 31 0.25 07H
+24.71 16 53 09/98 Bobbin HNI 0.66 05H
+19.58 09/98 Bobbin HNI 1.09 07H
+27.89 16 72 09/98 Bobbin HNI 0.39 11C
+37.40 09/98 Bobbin HNI 0.55 11C
+37.11 i
1 l
FTI TUBAN II (Varzion 2.3) 01/21/1999 11:29:55 Catewbn Nuclcar Stetion - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 6 ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 16 88 09/98 Bobbin HNI 10.76 11C
+15.49 16 100 09/98 Bobbin HNC 8
1.60 11C
+34.15 16 101 09/98 Bobbin HNC 10 0.60 11C
+13.93 09/98 C/L Special Interest VOL 0.47 11C
+13.69 16 103 09/98 Bobbin HNC 7
1.07 02H
+28.58 16 110 09/98 Bobbin HNI 2.62 06H
+34.82 17 5 09/98 Bobbin HNC 7
1.42 07H
+25.58 09/98 Bobbin HNC 13 0.99 07H
+36.73 09/98 Bobbin HNC 15 1.15 10C
+22.22 17 8 09/98 Bobbin HNI 1.04 05H
+14.35 09/98 Bobbin HNI 1.79 11C
+24.54 17 25 09/98 Bobbin HNC 4
1.54 16C
+10.23 09/98 Bobbin ODI 12 0.29 04H
+1.54 09/98 C/L Special Interest VOL 1.52 16C
+10.38 17 34 09/98 Bobbin NQI 0.27 09C
+0.21 17 36 09/98 Bobbin HNI 0.81 06H
+12.58 17 40 09/98 Bobbin HNI 1.16 10C
+10.58 17 42 09/98 Bobbin HNI 0.99 O1H
+4.17 09/98 Bobbin HNI 1.42 06H
+0.42 OS/98 H/L Special Interest VOL 2.07 06H
+8.43 l
09/98 H/L Special Interest VOL 2.54 O1H
+4.17 17 47 09/98 Bobbin HNI 2.04 O1H
+9.05 17 50 09/98 Bobbin HNC 15 0.67 02H
+29.98 17 59 09/98 Bobbin HNI 0.60 02H
+10.21 1
09/98 Bobbin HNC 15 0.54 02H
+5.89 l
09/98 Bobbin HNI 1.96 02H
+23.41 to
+30.97 l
17 65 09/98 Bobbin HNI 1.10 12C
+9.11 l
17 87 09/98 Bobbin HNI 3.90 04H
+1.41 to
+21.32 t
09/98 Bobbin HNI 4.92 03H
+15.84 to
+22.25 l
09/98 Bobbin HNI 5.81 03H
+32.08 to
+35.58 09/98 Bobbin HNI 6.26 02H
+20.69 to
+28.19 l's 106 09/98 Bobbin NOI 0.75 07H
+28.41 18 9 09/98 Bobbin HNC 10 1.35 10C
+39.69 18 20 09/98 Bobbin ADI 3.50 16C
+1.65 l
10 22 09/98 Bobbin NOI 0.14 07H
+13.47 09/98 Bobbin NOI 0.18 07H
+26.32 j
09/98 Bobbin NOI 0.41 07H
+14.80 i
18 59 09/98 Bobbin HNI 0.29 O1H
+14.98
)
l 18 72 09/98 Bobbin HNI 2.70 18C
+14.22 l
18 73 09/98 Bobbin HNC 19 0.86 13C
+6.10 to
+17.53 1
18 86 09/98 Bobbin HNC 26 0.59 10C
+41.97 18 87 09/98 Bobbin HNI 0.97 03H
+13.17 i
18 96 09/98 Bobbin HNI 1.50 10C
+41.74 18 108 09/38 Bobbin ADI 2.67 04H
+4.54 18 110 09/98 Bobbir.
HNI 1.61 13C
+12.54 to
+21.58 19 11 09/98 Bobbi; ADI 1.88 13C
+19.10 19 12 09/98 Bobbin HNI 0.23 10C
+36.14 19 13 09/98 Bobbin HNC 8
0.B5 10C
+37.24 19 15 09/98 Bobbin HNC 21 0.29 10C
+37.97 19 22 09/98 Bobbin HNI 0.89 10C
+41.79 19 23 09/98 Bcbbin HNI 0.41 15C
+16.43 4
09/98 Bobbin HNI 0.53 13C
+36.26 09/98 Bobbin HNI 0.85 13C
+17.53 09/98 Bobbin HNI 1.07 07H
+9.82 09/98 Bobbin NOI 0.32 12C
+11.62 09/98 Bobbin HNC 10 0.92 10C
+9.64 09/98 Bobbin HNC 24 1.06 11C
+33.78 09/98 Bobbin ODI 12 0.97 14C
+17.09 i
19 60 09/98 Bobbin HNI 0.59 18C
+6.03 19 61 09/98 Bobbin HNI 0.31 11C
+34.98 19 67 09/98 Bobbin HNC 11 0.39 07H
+43.93 09/98 Bobbin HNC 25 0.36 10C
+43.77 i
19 95 09/98 Bobbin HNI O.32 10C
+23.77 l
09/98 Bobbin HNI 0.38 07H
+24.59 09/98 Bobbin HNC 29 0.45 07H
+23.50
I FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 C&tcwb2 Nucle r Station - Unit Two S/G D 09/98 RPO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 7 ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS 1'
INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VQLTS LOCATION 19 99 09/98 Bobbin HNI 0.46 18C
+4.08 20 7 09/98 Bobbin ODI 14 0.56 10C
+38.98 20 8 09/98 Bobbin HNI 2.65 17C
+8.69 20 9 09/98 Bobbin ODI 14 0.52 10C
+34.05 20 18 09/98 Bobbin HNI 0.38 12C
+34.77 09/98 Bobbin HNC 28 0.89 12C
+15.29 09/98 Bobbin ODI 10 1.09 07H
+42.92 20 20 09/98 Bobbin HNC 8
1.20 AV1
+6.32 i
20 21 09/98 Bobbin ADI 3.22 09C
+6.50 20 23 09/98 Bobbin HNI 2.84 AV1
+5.89 20 30 09/98 Bobbin HNI 0.42 14C
+4.10 09/98 C/L Special Interest VOL 0.87 14C
+4.10 20 53 09/98 Bobbin HEC 5
0.56 TSH
+17.60 09/98 H/L Special Interest VOL 1.53 TSH
+17.00 20.58 09/98 Bobbin HNC 28 0.50 10C
+37.41 20 61 09/98 Bobbin HNC 6
0.98 04H
+8.72 09/98 Bobbin HNC 20 0.95 03H
+27.98 20 70 09/98 Bobbin HNC 16 0.87 18C
+11.82 20 71 09/98 Bobbin NQI 0.23 18C
+8.50 20 72 09/98 Bobbin HNC 16 0.49 18C
+8.33 20 73 09/98 Bobbin HNC 24 0.66 18C
+8.34 20 74 D9/98 Bobbin HNI 0.76 AV4
+10.38 09/98 Bobbin HNC 13 0.70 14C
+2.95 09/98 Bobbin HJC 20 0.89 04H
+38.39 09/98 Bobbin HNC 24 0.78 04H
+27.15 20 75 09/98 Bobbin HNC 24 0.47 18C
+8.52 20 78 09/98 Bobbin HNC 15 1.37 10C
+20.04 20 80 09/98 Bobbin HNC 10 2.54 10C
+7.51 20 81 09/98 Bobbin HNC 17 0.57 18C
+8.79 20 82 09/98 Bobbin HNC 10 0.47 18C
+8.11 20 83 09/98 Bobbin HNC 25 0.35 18C
+7.91 20 90 09/98 Bobbin HNC 25 0.49 18C
+5.82 l
20 91 09/98 Bobbin HNI 0.36 18C
+9.28 20 92 09/98 Bobbin HNC 22 0.01 18C
+6.82 1
20 93 09/98 Bobbin HNC 15 c.66 18C
+9.20 j
20 94 09/98 Bobbin HNC 25 0.54 18C
+9.40
~
20 96 09/98 Bobbin HNC 32 0.84 18C
+0.20 20 97 09/98 Bobbin NQI 0.25 IBC
+4.91 20 99 09/98 Bobbin HNC 1"
O.51 IBC
+9.31 20 100 09/98 Bobbin HNC 25 0.56 18C
+9.20 j
20 102 09/98 Bobbin HNI o.64 18C
+9.47 20 103 09/98 Bobbin HNC 24 0.86 18C
+9.18 20 104 09/98 Bobbin HNC 23 1.17 18C
+9.36 20 106 09/98 Bobbin HNC 1
0.93 O1H
+23.78 09/98 Bobbin HNC 13 0.62 18C
+7.86 20 108 09/98 Bobbin NQI 0.26 18C
+9.70 4
21 5 09/98 Bobbin HNI 0.79 06H
+28.94 21 13 09/98 Bobbin HNI 3.40 02H
+16.63 09/98 Bobbin NOI 0.30 10C
+32.63 09/98 H/L Special Interest VOL 0.82 02H
+16.33 21 15 09/98 Bobbin HNI 2.27 IOC
+10.07 21 20 09/98 Bobbin ADI 2.56 12C
+31.70 21 21 09/98 Bobbin HNI 2.28 16C
+13.72 21 33 09/98 Bobbin HNI 0.81 05H
+19.44 21 36 09/98 Bobbin HNI 0.37 07H
+42.44 21 47 09/98 Bobbin HNI 1.31 16C
+14.60 21 61 09/98 Bobbin HNI 0.87 18C
+11.92 l
21 62 09/98 Bobbin NOI 0.28 18C
+11.80 21 63 09/98 Bobbin HNC 19 0.58 18C
+14.41 21 65 09/98 Bobbin HNC 1
0.69 18C
+13.55 21 66 09/98 Bobbin NOI 0.46 18C
+15.39 21 68 09/98 Bobbin ADI 2.03 03H
+19.60 l
09/98 Bobbin RNC 18 1.25 18C
+11.44 21 69 09/98 Bobbin HNC 34 0.96 18C
+13.60 21 72 09/98 Bobbin HNC 1
0.62 18C
+12.05
~~. -. - _ - - - -. -
=. _ - - - _ -
. ~ -
~. - - = - - -
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 l
Catawba Nuclear Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC i
Page 8 i
ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS i
INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin ODI 3
1.82 10C
+30.51 21 73 09/98 Bobbin HNC 24 0.43 18C
+13.04
~
21 74 09/98 Bobbin HNC 33 0.97 18C
+11.39 I
21 76 09/98 Bobbin HNC 11 0.84 18C
+14.03 l
21 77 09/98 Bobbin HNC 1
0.93 07H
+25.01 1
09/98 Bobbin HNC 24 0.89 18C
+11.23 09/98 C/L Special Interest VOL 1.43 18C
+11.46 21 79 09/98 Bobbin NQI 1.33 18C
+14.07 21 80 09/98 Bobbin HNC 21 0.83 18C
+12.35 21 81 09/98 Bobbin HNC 11 1.25 18C
+12.43 21 82 09/98 Bobbin HNC 29 0.95 18C
+12.34 21 83 09/98 Bobbin HNC 10 1.94 18C
+12.34 09/98 Bobbin ODI 11 0.89 ISC
+12.17 21 84 09/98 Bobbin HNC 5
0.72 18C
+12.57 21 85 09/98 Bobbin HNC 12 1.27 18C
+12.54 21 87 09/98 Bobbin HNC 26 0.93 IBC
+12.38 21 88 09/98 Bobbin HNC 7
1.06 IBC
+12.50 21 89 09/98 Bobbin HNC 3
1.17 18C
+12.76 21 90 09 98 Bobbin NOI 0.22 10C
+13.90 09 98 Bobbin HNC 10 1.36 IBC
+12.80 21 91 09 98 Bobbin HNC 8
0.72 18C
+12.65 21 93 09/98 Bobbin HNC 8
1.25 11C
+17.35 09/98 Bobbin HNC 12 1.23 11C
+23.17 09/98 Bobbin HNC 15 0.67 18C
+12.76 09/98 Bobbin HNC 17 0.85 11C
+30.99 09/98 Bobbin HNC 17 1.04 11C
+14.06 09/98 Bobbin HNC 20 0.90 11C
+13.36 09/98 Dobbin HNC 26 0.84 11C
+20.06 21 94 09/98 Bobbin HNC 11 1.39 18C
+12.60 21 96 09/98 Bobbin HNI 0.26 18C
+8.02 09/su Bobbin HNC 8
1.29 18C
+12.95 21 99 09/98 Bobbin HNC 24 1.27 18C
+2.67 21 101 09/98 Bobbin HNC 3
1.89 18C
+3.09 21 103 09/98 Bobbin HNI 0.93 18C
+2.75 21 104 09/98 Bobbin HNC 28 0.79 18C
+3.24 21 105 09/98 Bobbin HNC 28 1.24 18C
+2.69 22 16 09/98 Bobbin NQI 0.52 10C
+44.01 09/98 Bobbin HNC 11 0.75 10C
+37.81 09/98 Bobbin ODI 21 0.36 10C
+27.94 l
09 98 Bobbin ODI 32 0.39 10C
+36.56 l
22 27 09 98 Bobbin HNI 0.84 16C
+11.06 22 70 09 98 Bobbin HNC 1
0.86 15C
+9.10 22 74 09 98 Bobbin HNC 13 1.60 10C
+4.33 22 75 09/98 Bobbin HNI 1.24 04H
+23.91 l
22 89 09/98 Bobbin NOI 0.36 07H
+43.93 09/98 Bobbin NQI 0.47 07H
+22.25 09/98 Bobbin HNC 3
1.65 05H
+34.63 09/98 Bobbin HNC 7
0.47 07H
+40.28 l
21 92 09/98 Bobbin HNC 3
0.65 O1H
+24.83 o
i 2M 102 09/98 Bobbin HNC 9
1.89 13C
+17.32 09/98 C/L Special Interest VOL 1.48 13C
+17.13 22 109 09/98 Bobbin ODI 4
0.14 18C
+5.11 23 6 09/98 Bobbin NOI 0.33 08H
+0.57 09/98 Bobbin HNC 13 0.57 10C
+37.38 23 9 09/98 Bobbin HNC 17 0.49 O1H
+21.31 23 22 09/98 Bobbin ODI 5
1.82 07H
+40.69 23 45 09/98 Bobbin HNI 0.63 07H
+37.03 09/98 Bobbin HNI 2.08 07H
+2.44 09/98 Bobbin HNI 2,20 08H
+9.34 4
09/98 Bobbin HNC 20 1.21 07H
+29.84 4
23 75 09/98 Bobbin HNC 16 1.06 04H
+10.80 09/98 H/L Special Interest VOL 2.32 04H
+10.87 23 99 09/98 Bobbin HNC 14 0.59 18C
+9.24 23 103 09/98 Bobbin HNI 0.79 IOC
+43.70 23 105 09/98 Bobbin ODI 20 0.40 18C
+9.35
1 1
FTI TUBAN II (Vareion 2.3) 01/21/1999 11:29:55 Cntswba Nuclenr Station - Unit Two 1
S/G D 1
09/98 RFO Bobbin,C/L Special Intettst, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 9 ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD R.OW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 23 106 09/98 Bobbin HNI 0.81 14C
+7.83 23 108 09/98 Bobbin HNI 0.52 11C
+12.09 24 10 09/98 Bobbin HNC 6
0.93 O1H
+4.32 24 13 09/98 Bobbin HNI 1.99 17C
+10.65 24 18 09/98 Bobbin ODI 24 0.28 14C
+10.92 24 19 09/98 Bobbin HNC 18 2.57 13C
+29.53 I
24 28 09/98 Bobbin HNI 1.08 13C
+22.44 24 47 09/98 Bobbin NOI 0.43 19C
+2.81 i
24 60 09/98 Bobbin HNI 1.27 07H
+24.37 24 61 09/98 Bobbin HNI 2.43 07H
+0.99 24 62 09/98 Bobbin HNI 0.77 11C
-0.81 24 71 09/98 Bobbin HNI 1.02 13C
+8.74 to
+14.08 24 72 09/98 Bobbin HNI 3.84 10C
+38.68 24 79 09/98 Bobbin HNC 4
1.16 17C
+12.47 24 86 09/98 Bobbin HNI 1.45 AV4
+14.84 l
09/98 Bobbin HNC 10 1.25 04H
+10.64 I
09/98 Bobbin HNC 15 1.66 10C
+39.28 09/98 C/L Special Interest VOL 2.18 10C
+39.23 24 89 09/98 Bobbin NQI 0.28 13C
+14.61 24 91 09/98 Bobbin HNC 3
1.82 17C
+7.16 09/98 Bobbin HNC 12 0.94 17C
+8.21 l
24 102 09/98 Bobbin HNC 10 1.42 11C
+28.65 l
24 104 09/98 Bobbin WAR 9
0.38 AV3
+0.00 i
09/98 Bobbin HNI 2,11 11C
+2.01 to
+28.86 09/98 UBEND SPEC. INT.
VOL 0.48 AV3
-0.15 25 8 09/98 Bobbin HNI 0.42 10C
+25.52 l
09/98 Bobbin HNI 0.44 10C
+25.17 1
l 09/98 Bobbin HNI 0.60 10C
+36.67 1
25 14 09/98 Bobbin NOI 0.43 07H
+18.60 09/98 Bobbin NOI 0.58 07H
+30.08 09/98 Bobbin NQI 1.13 07H
+27.21 09/98 Bobbin NOI 1.21 07H
+26.13 25 15 09/98 Bobbin ODI 38 0.34 10C
+34.93 25 16 09/98 Bobbin HNI 0.96 10C
+32.81 25 21 09/98 Bobbin IINC 29 2.14 AV4
+15.77 I
l 25 23 09/98 Bobbin HNC 6
1.00 10C
+39.30 1
25 24 09/98 Bobbin HNI 0.45 10C
+44.12 l
25 31 09/98 Bobbin ADI 0.75 04H
+9.63 09/98 Bobbin ADI 0.84 08H
+17.72 25 34 09/98 Bobbin HNC 16 0.54 06H
+36.74 1
09/98 H/L Special Interest VOL 0.84 07H
-6.32 j
09/98 H/L Special Interest VOL 1.08 06H
+36.45 25 42 09/98 Bobbin NOI 0.28 10C
+37.38 25 45 09/98 Bobbin HNC 33 0.56 13C
+18.46 25 (7 09/98 Bobbin ODI 12 0.64 19C
+3.93 i
25 50 09/98 Bobbin HNI 0.85 06H
+40.47
)
'25 51 09/98 Bobbin HNC 2
1.20 06H
+4.42 25 56 09/98 Bobbin HNI 0.34 12C
+6.17 09/98 Bobbin HNI 1.37 11C
+35.54 25 62 09/98 Bobbin HNC 4
1.83 04H
+31.91 09/98 Bobbin HNC 21 1.39 02H
+13.32 25 63 09/98 Bobbia HNI 4.84 AV4
+10.14 25 80 09/98 Bobbin HNI 2.05 05H
+28.00 25 91 09/98 Bobbin HNC 16 1.65 12C
+1.28 25 103 09/98 Bobbin HNI 3.48 O1H
+25.04 25 105 09/98 Bobbin HNI 1.02 18C
+15.24 25 107 09/98 Bobbin WAR B
0.30 AV3
+0.17 09/98 Bobbin WAR 21 0.97 AV2
+0.00 26 9 09/98 Bobbin HNI 0.49 10C
+15.89 09/98 Bobbin HNI 0.72 12C
+17.47 09/98 Bobbin ODI 3
0.36 08H
-0.46 09/98 C/L Special Interest VOL 1.04 12C
+17.47 26 13 05/98 Bobbin NOI 0.28 20C
+32.75 09/98 Bobbin ODI 17 0.32 07H
+34.86 26 18 09/98 Bobbin HNI 0.44 14C
+8.16 1
1
FTI TUBAN II (Varzion 2.3) 01/21/1999 11:29:55 Cattwba Nuclcar Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #4 INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 09/98 Bobbin HNI 0.45 13C
+36.43 09/98 Bobbin HNI 0.46 12C
+30.71 26 19 09/98 Bobbin HNI 1.12 03H
+29.14 l
09/98 Bobbin HNI 1.43 03H
+33.08 09/98 Bobbin ODI 19 0.81 04H
+4.96 09 98 H/L Special Interest VOL 0.41 04H
-3.06 1
09 98 H/L Special Interest VOL 1.56 03H
+33.08 26 27 09 98 Bobbin HNI 1.22 04H
+12.25 26 36 09 98 Bobbin HNI 0.36 10C
+37.21 26 37 09/98 Bobbin ODI 12 1.57 10C
+39.27 26 39 09/98 Bobbin HNI 2.25 05H
+8.64 09/98 Bobbin NQI 0.40 10C
+31.48 09/98 Bobbin HNC 12 0.96 07H
+40.50 09/98 Bobbin ODI 16 0.42 07H
+35.02 09/98 H/L Special Interest VOL 2.02 05H
+8.64 26 42 09/98 Bobbin HNI 0.63 15C
+12.94 09/98 Bobbin HNC 20 0.41 05H
+15.62
~
26 56 09/98 Bobbin HNI 4.49 10C
+18.52 09/98 Bobbin HNC 15 2.32 03H
+20.87 09/98 C/L Special Interest VOL 1.55 10C
+18.52 26 70 09/98 Bobbin HNI 1.31 10C
+4.83 09/98 Bobbin HNI 1.41 11C
+36.23 l
09/98 Bobbin HNC 16 1.19 13C
+36.33 i
26 72 09/98 Bobbin HNI 6.99 10C
+27.63 26 75 09/98 Bobbin HNC 4
0.83 02H
+12.11 26 76 09/98 Bobbin HNI 0.38 12C
+35.57 I
09/98 Bobbin HNI 1.36 12C
+22.72 09/98 Bobbin HNC 2
0.36 12C
+27.50 26 77 09/98 Bobbin HNI 0.60 OBH
+15.20 26 82 09/98 Bobbin NOI 0.30 15C
+2.43 26 95 09/98 Bobbin HNI 3.68 11C
+25.98 l
26 99 09/98 Bobbin ODI 20 0.65 17C
+1.34 27 12 09/98 Bobbin HNI 1,46 18C
+10.87 09/98 Bobbin HNC 16 0.82 12C
+33.95 09/98 C/L Special Interest VOL 0.78 18C
+10.87 27 19 09/98 Bobbin HNC 27 0.34 11C
+25.95 27 22 09/98 Bobbin HNI 0.66 IOC
+43.09 27 25 09/98 Bobbin HNI 0.68 10C
+41.57 27 30 09/98 Bobbin HNC 25 0.47 11C
+33.82 i
l 09/98 Bobbin ODI 22 0.46 05H
+39.57 27 31 09/98 Bobbin HNC 13 0.41 07H
+42.63 27 36 05/98 Bobbin NOI 0.41 16C
+8.23 27 39 09/98 Bobbin HNC 15 0.68 10C
+43.85 27 43 09/98 Bobbin HNC 18 0.80 14C
+11.12 l
27 56 09/98 Bobbin NQI 0.93 09C
+1.40 27 67 09/98 Bobbin HNC 4
0.97 13C
+13.93 09/98 C/L Special Interest VOL 0.59 13C
+14.52 27 73 09/98 Bobbin NQI 0.23 18C
+13.05 27 88 09/98 Bobbin ODI 23 0.45 12C
+20.41 27 97 09/98 Bobbin HNI 2.65 12C
+28.77 09/98 Bobbin HNI 3.31 13C
+38.28 09/98 Bobbin HNI 4.44 12C
+10.61 09/98 Bobbin HNI 4.90 02H
+9.01 09/98 Bobbin HNC 16 1.06 13C
+39.85 27 104 09/98 Bobbin HNI 1.48 AV1
+3.46 09/98 Bobbin ODI 13 0.49 18C
+1.92 09/98 Bobbin WAR 9
0.35 AV2
-0.02 2* 105 09/98 Bobbin HNI 0.67 07H
+43.59 09/98 Bobbin
- HNL, 1.31 07H
+44.51 27 106 09/98 Bobbin HNI 0.52 06H
+41.68 27 107 09/98 Bobbin WAR 14 0.57 AV2
-0.10 09/98 UBEND SPEC. INT.
VOL 0.46 AV2
+0.00 28 12 09/S8 Bobbin HNI 1.03 10C
+26.67 09/98 Bobbin HNC 15 0.37 07H
+34.96 09/98 Bobbin ODI 4
0.70 15C
+3.38
m.
. _.. ~
m FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 Catawb3 Nuclear Station - Unit Two S/G D 09/98 RFO Botbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 28 13 09/98 Bobbin HNI 0.16 10C
+28.62 09/98 Bobbin HNI 0.19 05H
+37.87 28 14 09/98 Bobbin NOI 0.63 08H
+1.21 28 16 09 98 Bobbin HNI 1.70 12C
+12.59 09 98 Bobbin NOI 0.48 10C
+25.27 09/98 Bobbin NQI 0.62 10C
+26.51 28 18 09/98 Bobbin HNI 1.01 11C
+25.19 28 19 09/98 Bobbin HNI 0.35 07H
+32.28 09/98 Bobbin HNI 0.46 09C
-0.30 09/98 Bobbin HNI 0.93 IOC
+44.27 09/98 Bobbin HNI 1.04 09C
+1.05 09/98 Bobbin HNI 1.05 08H
-1.74 09/98 Bobbin HNI 1.29 07H
+40.52 09/98 Bobbin NOI 1.66 10C
+34.56 to
+47.46 28 25 09/98 Bobbin HNC 17 0.43 07H
+42.88 28 27 09 98 Bobbin HNI 0.47 16C
+0.33 09 98 Bobbin HNI 0.60 06H
+24.71 28 31 09 90' Bobbin ODI 10 0.47 10C
+35.59 28 32 09/98 Bobbin NQI 0.47 16C
+9.00 28 33 09/98 Bobbin HNC 16 1.10 19C
+2.83 09/98 Bobbin HNC 23 0.61 12C
+5.33 28 36 09/98 Bobbin ODI 32 0.43 10C
+43.15 28 40 09/98 Bobbin NQI 0.20 10C
+35.64 09/98 Bobbin NQI 0.36 10C
+31.55 28 45 09/98 Bobbin NQI 0.26 14C
+7.58 28 63 09/98 Bobbin HNC 20 0.73 10C
+43.59 09/98 Bobbin ODI 6
0.54 10C
+28.63 09/98 Bobbin ODI 9
0.52 07H
+26.20 09/98 Bobbin ODI 13 0.32 10C
+39.83 28 64 09/98 Bobbin HNC 6
1.03 16C
+16.21 28 68 09/98 Bobbin HNC 14 0.66 16C
+13.61 09/98 Bobbin HNC 29 1.01 04H
+23.91 28 71 09/98 Bobbin HNI 1.30 AV2
+0.62 28 72 09/98 Bobbin HNI 0.30 16C
+10.55 09/98 Bobbin ODI 5
0.61 01H
+6.09 09/98 Bobbin ODI 21 0.52 11C
+37.04 09/98 H/L Special Interest VOL 1.05 O1H
+5.91 28 73 09 98 Bobbin HNI 0.48 03H
+3.54 28 83 09 98 Bobbin HNI 0.58 07H
+44.64 28 84 09/98 Bobbin ODI 11 0.27 10C
+23.69 28 91 09 98 Bobbin HNI 0.83 14C
+3.03 28 94 09 98 Bobbin HNI 2.39 17C
+2.00 28 102 09 98 Bobbin HNI 0.55 07H
+42.29 28 104 09/98 Bobbin HNI 0.96 11C
+24.73 09/98 Bobbin HNI 1.64 11C
+30.10 28 105 09/98 Bobbin WAR 18 0.79 AV2
-0.14 28 106 09/98 Bobbin HNI 2.12 12C
+10.94 29 11 09/98 Bobbin HNI 0.88 05H
+19.19 09/98 Bobbin NQI 0.59 10C
+42.11 09/98 H/L Special Interest VOL 0.89 05H
+18.49 29 33 09/98 Bobbin HNC 9
1.90 10C
+1.05 1
29 36 09/98 Bobbin HNC 23 0.67 05H
+6.02 29 37 09/98 Bobbin HNI 0.44 03H
+13.40 09/98 Bobbin NOI 0.30 03H
+15.54 09/98 Bobbin NQI 0.32 07H
+34.76 09/98 Bobbin NOI 0.35 07H
+31.43 09/98 Bobbin HNC 8
2.35 10C
+13.72 29 39 09/98 Bobbin HNC 11 0.42 10C
+42.39 1
29 42 09/98 Bobbin NOI 0.35 10C
+40.53 l
29 43 09/98 Bobbin HNC 11 0.68 17C
+6.64 l
29 50 09/98 Bobbin HNI 0.81 02H
+13.57 29 59 09/98 Bobbin NOI 0.75 09C
+0.75 09/98 Bobbin HNI 1.36 IBC
+12.14 to
+16.64 29 63 09/98 Bobbin HNI 0.95 TSC v1.92 29 66 09/98 Bobbin HNC 11 1.25 14C
+6.32
I i
l l
FTI TUBAN II (Varzion 2.3) 01/21/1999 11:29:55 I
C2tcWh3 Nuclcar Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRFC l
l Page 12 ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION l
09/98 Bobbin HNC 11 1.85 15C
+7.30 29 71 09/98 Bobbin NOI 0.19 10C
+27.41 29 95 09/98 Bobbin NOI 0.50 O1H
+9.42
{
30 20 09/98 Bobbin HNC 13 4.99 O1H
+23.48 i
30 22 09/98 Bobbin HNI 0.53 07H
+32.19 l
09/98 Bobbin (DI 22 0.37 10C
+42.62 j
30 31 09/98 Bobbin h TI 0.43 11C
+22.99 30 33 09/98 Bobbin HNC 19 0.64 100
+28.52
{
30 36 09/98 Bobbin HNI 1.00 02H
+25.43 30 37 09/98 Bobbin HNC 27 0.30 09C
+0.00 30 38 09/98 Bobbin HNC 13 0.73 07H
+35.31 30 39 09/98 Bobbin NOI 0.55 10C
+44.38 30 40 09/98 Bobbin HNC 30 0.34 02H
+23.02 09/98 H/L Special Interest VOL 0.20 02H
+22.84 30 41 09/98 Bobbin HNC 23 3.02 14C
+1.47 30 46 09/98 Bobbin HNC 11 0.95 10C
+31.75 09/98 Bobbin HNC 12 0.67 10C
+35.59 09/98 Bobbin ODI 13 0.36 11C
+11.03 30 47 09/98 Bobbin HNI 0.91 04H
+20.30 30 50 09/98 Bobbin HNC 12 0.29 08H
-0.17 30 54 09/98 Bobbin HNI 2.21 13C
+15.28 09/98 C/L Special Interest VOL 0.84 12C
+6.39 30 77 09/98 Bobbin HNI 0.96 17C
+9.00 09/98 Bobbin HNC 13 1.28 13C
+16.13 09/98 C/L Special Interest VOL 0.90 13C
+16.92 30 79 09/98 Bobbin HNI 2.18 16C
+1.02 l
30 86 09/98 Bobbin HNC 3
0.73 16C
+11.22 1
30 102 09/98 Bobbin WAR 18 0.75 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 0.67 AV3
+0.00 31 15 09/98 Bobbin HNI 0.28 TSC
+6.31 31 16 09/98 Bobbin HNI 0.28 10C
+29.12 09/98 Bobbin HNI 0.40 10C
+41.64 09/98 Bobbin HNI 0.61 10C
+30.26 09/90 Bobbin KNI 0.88 10C
+43.72 09/98 Bobbin HNI 0.91 10C
+44.08 09/98 Bobbin ODI 5
0.47 07H
+24.01 31 22 09/98 Bobbin NQI 0.33 14C
+6.12 31 23 09/98 Bobbin NQI 0.79 13C
+8.54 1
09/98 C/L Special Interest VOL 1.41 13C
+8.15 t
31 24 09/98 Bobbin HNI 0.27 15C
+9.73 09 98 Bobbin HNI 0.42 03H
+30.22 j
31 37 09 98 Bobbin HNI 0.54 13C
+27.37 i
09 98 Bobbin HNI 1.21 07H
+32.36 09/98 Bobbin HNI 2.24 12C
+31.51 31 38 09/98 Bobbin HNC 5
0.61 19C
+1.67 31 39 09/98 Bobbin HNC 29 1.98 11C
+12.74 31 44 09/9d Bobbin HNI 0.96 16C
+6.07 31 47 09/98 Bobbin NOI 0.27 11C
+24.90 09/98 Bobbin HNC 25 0.35 14C
+12.20 09/98 Bobbin HNC 26 0.61 14C
+13.20 31 48 09/98 Bobbin HNI 0.54 07H
+37.75 31 59 09/98 Bobbin HNC 15 0.86 10C
+43.06 09/98 Bobbin HNC 20 0.66 10C
+41.78 31 63 09/98 Bobbin HNI 0.59 12C
+27.48 09/98 Bobbin HNI 0.63 12C
+18.99 09/98 Bobbin HNI 1.58 12C
+22.52 l
09/98 Bobbin HNI 1.59 12C
+24.55 31 67 09/98 Bobbin HNC 6
1.42 13C 438.35 l
31 68 09/98 Bobbin HNC 15 1.17 07H
+24.53 09/98 H/L Special Interest VOL 1.25 07H
+24.62 l
31 77 09/98 Bobbin ADI 1.60 07H
+16.20 l
09/98 Bobbin HNI 0.72 11C
+40.11 l
31 78 09/98 Bobbin HNI 0.77 13C
+39.30 31 82 09/98 Bobbin HNI 0.42 07H
+25.78 31 86 09/98 Bobbin HNI 0.49 11C
+10.24
.... ~. ~. -. ~.
'FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 Catawba Nuclear Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&18,H/L Special Interest,H/L Tubesheet,MRPC I
ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 31 92 09/98 Bobbin HNC 10 2.16 15C
+12.12 31 93 09/98 Bobbin NOI 0.34 12C
+30.89 32 12 09/98 Bobbin NOI 0.13 10C
+39.41 09/98 Bobbin NOI 0.37 07H
+20.81 09/98 Bobbin ODI 23 0.24 07H
+28.06 32 29 09/98 Bobbin HNC 3
1.26 03H
+23.30 09/98 Bobbin HNC 5
0.93 03H
+24.43 09/98 Bobbin HNC 17 0.96 03H
+15.39 09/98 Bobbin HNC 29 0.96 03H
+26.18 1
32 41 09/98 Bobbin NOI 0.25 10C
+40.59 09/98 Bobbin HNC 3
0.59 10C
+41.80 32 64 09 98 Bobbin HNI 0.33 07H
+32.84 j
l 09 98 Bobbin HNC 13 0.89 10C
+8.68 l-09/98 Bobbin HNC 19 0.56 10C
+17.57 32 46 09/98 Bobbin HNC 19 0.66 19C
+6.27 09/98 Bobbin ODI 31 0.30 10C
+37.41 32 47 09/98 Bobbin HNI 0.75 02H
+27.39 l
32 48 09/98 Bobbin HNI 0.61 13C
+23.21 32 62 09/98 Bobbin HNC 15 0.63 11C
+33.05 09/98 C/L Special Interest VOL 12.95 10C
-10.80 32 65 09/98 Bobbin HNC 13 2.84 13C
+25.80 32 66 09/98 Bobbin HNC 9
0.58 10C
+37.66 32 71 09/98 Bobbin HNC 19 0.32 07H
+40.40 32 76 09/98 Bobbin HNC 6
4.45 08H
+16.87 09/98 UBEND SPEC. INT, VOL 1.85 08H
+16.40 32 79 09/98 Bobbin ODI 17 0.46 10C
+29.38 09/98 Bobbin ODI 24 0.39 10C
+32.53 32 82 09/98 Bobbin HNC 28 0.42 07H
+24.08 l
09/98 Bobbin ODI 10 0.50 07H
+39.07 32 85 09/98 Bobbin ADI 4.08 AV2
+10.45 32 86 09/98 Bobbin HNI 2.43 AV4
+13.60 09/98 Bobbin HNC 12 4.42 12C
+29.22 32 101 09/98 Bobbin HNI 3.55 09C
+15.70 32 103 09/98 Bobbin HNI 2.34 10C
+43.41 33 13 09/98 Bobbin WAR 16 0.58 AV3
+0.00 09 98 Bobbin WAR 25 1.08 AV2
+0.00 33 16 09 98 Bobbin ODI 12 0.53 07H
-0.10 j,
09 98 H/L Special Interest VOL 0.45 07H
+0.28 33 17 09/98 Bobbin HNI 0.58 10C
+40.29 33 26 09/98 Bobbin HNI 0.49 12C
+37.73 33 34 09/98 Bobbin HNI 0.95 13C
+16.22 i
09/98 Bobbin NQI 0.55 04H
+2.38 33 35 09/98 Bobbin HNC 20 0.51 07H
+29.43 33 40 09/98 Bobbin ODI 3
0.32 14C
+9.72 33 41 09/98 Bobbin HNI 1.38 03H
+26.62 33 46 09/98 Bobbin HNI 0.40 10C
+15.16 33 55 09/98 Bobbin NOI 0.28 14C
+7.67 09/98 Bobbin HNC 25 1.24 07H
+21.93 33 64 09/98 Bobbin HNI 2.99 10C
+25.15 33 75 09/98 Bobbin HNC 20 0.50 ? dC
+11.88 33 77 09/98 Bobbin ODI 10 0.95 O1H
+10.86 i
33 82 09/98 Bobbin HNC 5
0.54 10C
+27.12 33 103 09/98 Bobbin HNI 0.42 07H
+40.68 34 14 09/98 Bobbin ADI 1.98 05H
+6.27 i
34 16 09/98 Bobbin HNI 0.47 13C
+6.76 09/98 Bobbin HNI 0.73 12C
+27.09 09/98 Bobbin HNI 2.82 16C
+3.49 i'
34 17 09/98 Bobbin HNI 0.60 07H
+21.97 09/98 Bobbin NOI 0.48 07H
+39.95 09/98 Bobbin NQI 0.48 07H
+42.33 34 32 09/98 Bobbin HN1 4.40 10C
+32.24 34 35 09/98 Bobbin HNC 25 1.01 10C
+39.07 i
34 36 09/98 Bobbin HNC 9
0.72 11C
+25.45 34 69 09/98 Bobbin NOI 0.27 08H
-0.52 i
09/98 Bobbin HNC 11 0.85 07H
+40.27
,m
E i
FTI TUBAN II (Varcion 2.3) 01/21/1999 11:29:55 Catawba Nuclear Station - Unit Two S/G D 09/98 RFO l
Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #4 INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IUD %TW VOLTS LOCATION 34 79 09/98 Bobbin HNC 4
1.07 18C
+8.05 34 81 09/98 Bobbin NQI 1.30 04H
+18.14 34 82 09/98 Bobbin HNI 0.40 07H
+24.11 to
+28.84 34 88 09/98 Bobbin HNC 11 2.41 13C
+20.58 34 90 09/98 Bobbin HNI 1.76 13C
+4.60 34 98 09/98 Bobbin WAR 17 0.72 AV2
-0.05 l
34 99 09/98 Bobbin WAR 15 0.60 AV2
-0.07 1
09/98 UBEND SPEC. INT.
VOL 0.72 AV2
-0.08 34 100 09/98 Bobbin WAR 12 0.46 AV3
+0.00 35 14 09 98 Bobbin WAR 36 2.12 AV2
+0.00 09 98 UBEND SPEC. INT.
VOL 1.06 AV2
-0.00 1
35 17 09/98 Bobbin HNI 0.51 10C
+21.62 35 32 09/98 Bobbin HNI 2.40 02H
+11.62 l
09/98 Bobbin ODI 16 1.21 02H
+17.30 09/98 Bobbin ODI 20 0.49 02H
+25.21 1
09/98 H/L Special Interest VOL 0.41 02H
+25.16 j
09/98 H/L Special Interest VOL 0.49 02H
+11.73 09/98 H/L Special Interest VOL 0.72 02H
+17.66 35 41 09/98 Bobbin HJI 3.08 06H
+17.91 35 52 09/98 Bobbin NOI 0.29 03H
+20.71 35 66 09/98 Bobbin HNI 1.45 17C
-0.55 35 79 09/98 Bobbin HNC 23 0.44 07H
+38.50 35 94 09/98 Bobbin HNC 11 1.52 03H
+16.29 35 101 09/98 Bobbin HNC 10 2.45 O1H
+11.88 36 15 09/98 Bobbin HNI 0.29 10C
+43.30 36 16 09/98 Bobbin NOI 0.65 11C
+30.76 09/98 Bobbin WAR 14 0.39 AV1
+0.00 09/98 Bobbin WAR 15 0.40 AV3
+0.19 09/98 Bobbin WAR 36 2.12 AV2
-0.05 09/98 UBEND SPEC. INT.
VOL 0.22 AV1
+0,00 09/98 UBEND SPEC. INT.
VOL 0.36 AV3
+0.00 09/98 UBEND SPEC. INT.
VOL 1.14 AV2
+0.00 36 18 09/98 Bobbin HNI 0.69 10C
+43.55 36 22 09/98 Bobbin HNI 1.38 14C
+8.06 09/98 Bobbin ODI 9
0.87 17C
+12.00 09/98 Bobbin ODI 10 0.63 16C
+11.34 09/90 Bobbin ODI 11 0.30 17C
+14.04 36 24 09/98 Bobbin HNI 1.55 AV1
+19.64 i
36 27 09/98 Bobbin HNC 7
1.01 05H
+19.02 l
36 32 09/98 Bobbin HNI 0.67 18C
+3.46 36 35 09/98 Bobbin HNI 2.03 14C
+13.61 36 65 09/98 Bobbin HNI 1.70 AV3
+0.81 j
36 75 09/98 Bobbin ODI 21 0.22 11C
+38.50 36 76 09/98 Bobbin NOI 0.34 02H
+31.94 36 91 09/98 Bobbin HNI 0.68 10C
+44.88 36 93 09/98 Bobbin WAR 14 0.57 AV2
-0.07
~
36 94 09/98 Bobbin WAR 7
0.27 AV1
-0.10 09/98 Bobbin WAR 13 0.53 AV2
+0.00 09/98 UBEND SPEC. INT, VOL 0.39 AV2
-0.00 09/98 UBEND SPEC. INT.
VOL 0.43 AV1
+0.20 36 95 09/98 Bobbin HNI 4.96 11C
+0.85 36 96 09/98 Bobbin WAR 14 0.57 AV2
+0.00 09/98 UBEND SPEC. INT.
VOL 0.38 AV1
+0.06 09/98 UBEND SPEC. INT.
VOL 0.59 AV2
+0.00 36 98 09/98 Bobbin WAR 14 0.56 AV3
+0.00 36 99 09/98 Bobbin HNI 1.32 AV4
+8.68 37 17 09/98 Bobbin WAR 16 0.55 AV4
+0.00 09/98 Bobbin WAR 17 0.60 AV2
+0.00 37 22 09/98 Bobbin HNI 0.52 11C
+6.55 t
09/98 Bobbin HNC 13 1.66 12C
+2.44 37 30 09/98 Bobbin HNI 1.88 02H
+31.11 37 37 09/98 Bobbin HNI 0.49 17C
+9.65 j
09/98 Bobbin NOI 0.81 17C
+4.39 09/98 Bobbin HNC 13 0.97 17C
+0.36 37 60 09/98 Bobbin HNI 1.75 04H
+33.34
. -.~ - --- - - ~
'FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29':55 Catawbn Nuclear Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC I
ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 37 61 09/98 Bobbin HNI 0.69 13C
+18.41 09/98 C/L Special Interest VOL 0.89 13C
+18.51 37 83 09/98 Bobbin HNI 0.95 O1H
+12.95 i
38 18 09/98 Bobbin WAR 23 0.92 AV4
+0.00 09/98 Bobbin WAR 23 0.96 AV2
+0.00 38 21 09/98 Bobbin HNI 0.38 04H
+7.91 38 25 09/98 Bobbin HNI 1.15 04H
+38.01 38 34 09/98 Bobbin HNI 0.66 02H
+16.76 09/98 Bobbin HNC 25 0.~88 11C
+28.02 38 39 09/98 Bobbin HNC 8
0.41 10C
+44.75 38 41 09/98 Bobbin NOI 0.24 10C
+17.62 l
38 49 09/98 Bobbin HNC 14 5.28 10C
+7.10 09/98 C/L Special Interest VOL 1.98 IOC
+6.69 38 64 09/98 Bobbin WAR 17 0.50 AV2
+0.00 38 68 09/98 Bobbin HNI 0.78 10C
+11.10 38 70 09/98 Bobbin HNI 0.43 10C
+12.06 l
38 71 09/98 Bobbin HNI 1.93 06H
+31.34 09/98 H/L Special Interest VOL 1.78 06H
+31.94 38 73 09/98 Bobbin HNC 7
3.58 06H
+32.85 38 77 09/98 Bobbin HNI 0.81 O1H
+16.23 38 80 09/98 Bobbin HNI 0.91 AV3
+6.85 09/98 Bobbin HNC 12 1.01 07H
+18.46 38 89 09 98 Bobbin HNI 0.44 07H
+39.30 38 93 09 98 Bobbin WAR 14 0.59 AV3
+0.00 l
09/98-Bobbin WAR 24 1.18 AV2
+0.00 39 19 09/98 Bobbin HNI 1.76 14C
+2.60 39 21 09/98 Bobbin HNI 0.70 09C
+0.93 39 23 09/98 Bobbin HNI 0.80 11C
+10.28 39 29 09/98 Bobbin ADI 2.17 13C
+1.64 09/98 Bobbin HNI 2.03 07H
+32.26 39 44 09/98 Bobbin ODI 23 0.57 16C
+12.32 39 55 09/98 Bobbin HNC 15 0.75 06H
+35.62 39 60 09/98 Bobbin ODI 15 0.46 10C
+27.16 39 62 09/98 Bobbin HNC 24 1.37 15C
+6.38 09/98 C/L Special Interest VOL 1.22 15C
+6.58 39
'70 09/98 Bobbin HNC 11 1.69 03H
+21.98 09/98 H/L Special Interest VOL 2.18 03H
+21.98 39 78 09/98 Bobbin NOI 0.41 05H
+37.84 09/98 Bobbin NQI 0.43 05H
+7.57 39 90 09/98 Bobbin HNI 0.61 07H
+44.23 39 96 09/98 Bobbin WAR 15 0.64 AV3
+0.00 39 98 09/98 Bobbin WAR 10 0.38 AV1
+0.00 40 24 09/98 Bobbin NOI 0.83 04H
+17.29 09/98 Bobbin NOI 1.28 04H
+9.59 09/98 Bobbin ODI 20 1.54 17C
+1.66 09/98 C/L Special Interest VOL 1.11 17C
+1.68 1
40 25 09/98 Bobbin HNI 0.40 15C
+5.05 09/98 Bobbin HNI 1.25 13C
+17.25 i
09/98 Bobbin HNI 1.74 15C
+3.27 40 28 09 98 Bobbin HNI 1.73 08H
+3.65 40 31 09 98 Bobbin HNC 19 0.88 10C
+5.89 40 37 09/98 Bobbin HNI 0.29 10C
+41.50 09/98 Bobbin HNI 0.46 10C
+37.60 i
{
09/98 Bobbin HNI 1.11 10C
+38.85 40 43 09/98 Bobbin NQI 0.23 14C
+14.78
?
40 44 09/98 Bobbin HNC 5
0.42 15C
+9.86 1
09/98 Bobbin HNC 15 0.74 07H
+35.40 40 56 09/98 Bobbin HNC 6
1.02 14C
+11.74 s
09/98 Bobbin HNC 12 1.35 11C
+28.49 40 63 09/98 Bobbin NOI 0.31 08H
-0.56 40 64 09/98 Bobbin HNI 8.16 AV3
+11.82 40 84 09/98 Bobbin HNI 0.30 07H
+35.91 j
09/98 Bobbin HNI 1.09 AV1
+1.07 40 89 09/98 Bobbin HNI 0.62 08H
+1.75 09/98 Bobbin ODI 17 0.52 07H
+42.47 4
j 1
l FTI TUBAN II (Version 2.3) 01/21/1999 11:29:55 Catcwbs Nuclear Station - Unit Two S/G D l
09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubesheet,MRPC Page 16 ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION l
40 93 09/98 Bobbin WAR 14 0.58 AV2
+0.00 1
40 94 09/98 Bobbin WAR 21 0.97 AV2
-0.05 l
09/98 Bobbin WAR 22 1.04 AV3
+0.05 40 97 09/98 Bobbin HNC 11 1.17 10C
+1.46 09/98 Bobbin HNC 13 0.67 03H
+29.55 09/98 Bobbin HNC 15 0.49 13C
+20.16 09/98 Bobbin HNC 18 0.23 13C
+11.21 09 98 Bobbin ODI 13 0.22 13C
+11.54 09 98 Bobbin ODI 24 0.30 12C
+19.22 09 98 Bobbin WAR 10 0.34 AV1
+0.00 09/98 UBEND SPEC. INT.
VOL 0.53 AV1
+0.05 41 22 09/98 Bobbin HNI 1.19 09C
+2.07 41 33 09/98 Bobbin HNI 0.61 02H
+8.55 41 37 09/98 Bobbin ODI 5
0.77 13C
+28.58 41 63 09/98 Bobbin HNI 0.47 13C
+0.72 09/98 Bobbin HNI 2.14 AV1
+10.68 09/98 Bobbin HNI 2.99 17C
+B.32 41 68 09/98 Bobbin HNI 0.70 06H
+37.98 41 69 09/98 Bobbin HNI 1.11 O1H
+25.60 41 77 09/98 Bobbin WAR 17 0.70 AV3
+0.00 l
09/98 Bobbin WAR 18 0.78 AV2
+0.00 41 83 09/98 Bobbin NOI 0.29 12C
+33.11 41 87 09/98 Bobbin HNI 0.74 O1H
+18.21 41 88 09/98 Bobbin HNC 16 2.09 06H
+6.43 41 90 09/98 Bobbin HNI 1 68 08H
+2.24 41 93 09/98 Bobbin HNI 1,22 07H
+39.90 41 95 09/98 Bobbin ODI 10 0.64 07H
+4.52 42 23 09/98 Bobbin WAR 19 0.72 AV2
+0.00 42 26 09/98 Bobbin HNI 0.57 11C
+28.90 42 37 09/98 Eobbin HNI 0.50 12C
+32.78 42 61 09/98 Bobbin HNC 1
0.52 11C
+18.84 42 64 09/98 Bobbin WAR 13 1.62 13C
+0.00 42 69 09/98 Bobbin NQI 0.26 10C
+5.95 42 77 09/98 Bobbin HNC 24 0.47 15C
+14.08 42 93 09/98 Bobbin HNC 13 0.37 07H
+42.76 43 22 09/98 Bobbin WAR 22 0.04 AV4
+0.00 09/98 Bobbin WAR 30 1.43 AV3
+0.00 43 70 09/98 Bobbin HNC 10 0.77 07H
+16.48 09/98 Bobbin HNC 15 0.44 06H
+40.67 43 73 09/98 Bobbin HNI 0.70 O1H
+23.22 09/98 Bobbin HNC 21 1.07 08H
+10.81 43 74 09/98 Bobbin HNI 1.28 04H
+14.07 43 78 09/98 Bobbin WAR 27 1.04 AV2
+0.00 09/98 Bobbin WAR 34 1.77 AV3
+0.00 09/98 UBEND SPEC. INT.
V
O.65 AV2
-0.01 09/98 UBEND SPEC. INT.
t;_
1.00 AV3
+0.00 43 81 09/98 Bobbin WAR 19 0.85 AV4
+0.05 09/98 Bobbin WAR 23 1.09 AV2
-0.02 09/98 Bobbin WAR 33 2.10 AV3
-0.02 43 91 09/98 Bobbin NOI 0.50 AV1
+16.87 09/98 Bobbin ODI 6
1.68 AV4
+22.51 44 24 09/98 Bobbin NQI 1.07 04H
+27.18 09/98 Bobbin WAR 15 0.41 AV3
+0.13 09/98 UBEND SPEC INT.
VOL 0.25 AV3
+0.00 44 46 09/98 Bobbin WAR 16 0.51 AV3
-0.05 44 91 09/98 Bobbin ADI 2.12 12C
+10.99 45 24 09/98 Bobbin HNI 2.11 15C
+25.69 09/98 C/L Special Interest VOL 1.21 15C
+25.72 45 35 09/98 Bobbin HNC 24 0.55 07H
+25.24 45 38 09/98 Bobbin ODI 16 0.45 100
+9.45 45 52 09/98 Bobbin HNI 2.20 10C
+1.47 09/98 Bobbin HNC 16 0.35 17C
+8.34 09/98 Bobbin HNC 32 0.65 11C
+16.96 i
45 67 09/98 Bobbin HNC 10 0.69 10C
+28.67 45 73 09/98 Bobbin HNC 9
2,09 13C
+27.85 l
l l
l l
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 C tcwba Nuclear Station - Unit Two S/G D 09/98 RFO Bobbin,C/L Special Interest, Expansion +Pt->17&l8,H/L Special Interest,H/L Tubecheet,MRPC ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 45 78 09/98 Bobbin HNI 0.44 13C
+5.30 45 79 09/98 Bobbin HNC 28 0.92 09C
+13.46 45 91 09/98 Bobbin WAR 13 0.52 AV4
-0.07 46 26 09/98 Bobbin HNI 4.23 12C
+0.68 46 27 09/98 Bobbin ADI 1.78 15C
+13.42 46 35 09/98 Bobbin NOI 0.36 09C
+0.21 46 48 09/98 Bobbin HNI 1.30 AV3
+12.19 09/98 Bobbin HNI 2.42 AV1
+31.57 09/98 Bobbin HNI 2.68 AV3
+1.00 09 98 Bobbin HNC 1
2.67 AV2
+9.99 09 98 Bobbin HNC 9
1.22 AV1
+22.99 09/98 UBEND SPEC. INT.
VOL 1.28 AV1
+22.70 09/98 UBEND SPEC. INT.
VOL 1.41 AV3
+12.35 1
09/98 UBEND SPEC. INT.
VOL 1.47 AV3
+1.14 1
09/98 UBEND SPEC. INT.
VOL 1.92 AV1
+31.17 09/98 UBEND SPEC. INT.
VOL 2.81 AV2
+9.97 46 51 09/98 Bobbin HNC 21 0.73 12C
+6.55 46 61 09/98 Bobbin HNC 15 0.70 11C
+41.17 46 63 09/98 Bobbin HNC 1
3.89 AV2
+8.37 09/98 UBEND SPEC. INT, VOL 2.56 AV2
+0.37 46 67 09/98 Bobbin NOI 0.25 07H F40.90 46 82 09/98 Bobbin NOI 0.40 10C
+38.83 46 87 09/98 Bobbin HNI 0.64 12C
+21.21 46 88 09/98 Bobbin ODI 21 0.93 02H
+19.93 09/98 H/L Special Interest VOL 2.40 02H
+20.40 47 27 09/98 Bobbin HNC 4
1.02 06H
+7.80 47 31 09/98 Bobbin HNI 1.63 10C
+35.90 47 33 09/98 Bobbin HNI 5.23 10C
+37.97 47 34 09/98 Bobbin HNC 2
1.19 AV1
+18.11 09/98 Bobbin HNC 9
1.13 AV1
+9.94 47 38 09/98 Bobbin HNI 0.69 09C
-0.66 47 46 09/98 Bobbin HNC 5
0.59 10C
+44.65 47 53 09/98 Bobbin HNI 2.63 07H
+20.09 47 67 09/98 Bobbin HNI 0.56 07H
+38.46 47 68 09/98 Bobbin HNI 0.58 07H
+32.65 09/98 Bobbin ODI 19 0.31 10C
+33.85 i
47 76 09/98 Bobbin ODI 17 0.37 10C
+28,68 47 81 09/98 Bobbin HNI 2.09 AV2
+5.42 09/98 UBEND SPEC. INT.
VOL 2.10 AV2
+4.96 47 83 09/98 Bobbin HNI 0.59 17C
+24.23 47 84 09/98 Bobbin ODI 19 0.42 10C
+22.96 48 32 09/98 Bobbin HNI 2.17 17C
+12.27 48 34 09/98 Bobbin NOI 0.65 08H
+3.08 48 41 09/98 Bobbin HNC 21 0.73 07H
+24.23 48 42 09/98 Bobbin NOI 0.28 10C
+13.45 40 43 09/98 Bobbin NQI 0.28 12C
+31.68 48 44 09/98 Bobbin HNI 0.74 11C
+1.84 09/98 Bobbin HNI 0.95 11C
+24.11 09/98 Bobbin HNI 1.16 15C
+26.54 09/98 Bobbin ODI 16 1.65 09C
+27.61 48 47 09/98 Bobbin HNC 14 0.62 10C
+16.89 09/98 Bobbin ODI 24 0.28 10C
+23.65 09/98 C/L Special Interest VOL 0.55 10C
+16.88 48 51 09/98 Bobbin HNC 8
1.28 11C
+14.12 09/98 Bobbin WAR 9
1.21 13C
+0.41 09/98 C/L Special Interest VOL 0.79 11C
+14.12 48 55 09/98 Bobbin WAR 13 1.55 13C
+0.00 09/98 C/L Special Interest VOL 1.69 13C
-0.00 48 60 09/98 Bobbin WAR 14 1.79 13C
+0.16 l
48 62 09/98 Bobbin HNI 0.58 10C
+31.44 09/98 Bobbin ODI 30 0.19 10C
+11.82 l
48 68 09/98 Bobbin HNI 3.42 AV1
+28.37 09/98 UBEND SPEC. INT.
VOL 3.28 AV1
+28.37 48 70 09/98 Bobbin HNC 14 0.84 07H
+29.54 48 72 09/98 Bobbin ODI 26 0.29 06H
+34.95
FTI TUBAN II (Varsion 2.3) 01/21/1999 11:29:55 Catawba Nuclear Station - Unit Two S/G D l
09/98 RFO l
Bobbin,C/L Special Interest, Expansion +Pt->17&18,H/L Special Interest,H/L Tubesheet,MRPC ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 48 75 09/98 H/L Tubesheet VOL 0.42 TSH
-0.00 l
48 76 09/98 Bobbin ODI 12 0.53 07H
+43.20 I
48 77 09/98 Bobbin HNI 1.59 O1H
+15.31 48 81 09/98 Bobbin ODI 3
0.69 03H
+4.65 48 82 09/98 Bobbin NQI 0.65 09C
+2.54 09/98 Bobbin ODI 9
0.43 10C
+24.26 49 33 09/98 Bobbin HNC 18 1.75 13C
+5.96 49 37 09/98 Bobbin HNC 12 1.31..t2C
+25.28 l
09/98 Bobbin ODI 9
0.58 10C
+30.43 49 48 09/98 Bobbin HNC 16 1.10 0'JH
+3.27 49 51 09/98 Bobbin HNC 12 0.50 15C
+19.88 09/98 Bobbin HNC 25 0.48 11C
+17.89 49 52 09/98 Bobbin WAR 19 2,45 13C
+0.00 49 53 09/98 Bobbin WAR 26 4.06 13C
+0.46 09/98 C/L Special Interest VOL 3.17 13C
+0.25 49 36 09/98 Bobbin WAR 11 1.26 13C
+0,49 i
j 49 59 09 98 Bobbin HNI 0.47 07H
+26.18 j
49 70 09 98 Bobbin HNC 26 0.92 OBH
+3.39 f
49 74 09 98 Bobbin NOI 0.37 10C
+26.61 l
49 83 09/98 Bobbin HNI 0.57 04H
+3.52 Total Indications Found = 1125 Total Tubes Found = 717 I
l
o******
FTI TURAN II (Version 2.3) 01/21/1999 11:00:26 ooooo**
Catawba Nuclear Station - Unit Two occoo**
S/G A ocooo**
09/98 RFO ocooo**
43 68 Total Data Items Found = 1 Total Tubes Found = 1 l
l l
I i
1 l
FTI TUBAN II (Version 2.3) 01/21/1999 10:59:32 Catawba Nuclear Station - Unit Two a*ece**
S/G B 09/98 RFO Page 1 - Tubes Plugged 9/98 RFO COUNT ROW COL 1.
1 61 i
2.
20 104 3.
35 41 4..
46 54 5.
48 39 Total Data Items Found = 5 Total Tubes Found = 5 1
\\
l l
t l
l l
l
FTI TUBAN II (Version 2.3) 01/21/1999 10:58:34 l
Catawba Nuclear Station - Unit Two I
eeoo***
S/G C oo*****
09/98 RFO ocoo***
i
. - Tubes Plugged 9/98 RFO l
COUNT ROW COL 1.
32 12 l
Total Data Items Found = 1 Total Tubes Found = 1 l
l i
i i
I l
l l
i r
l l
1 FTI TUBAN II (Version 2.3) 01/21/1999 10:57:28 Catawba Nuclear Station - Unit Two S/G D 09/98 RFO
. - Tubes Plugged 9/98 RFO COUNT ROW COL 1
1.
33 16 j
2.
48 75 Total Data Items Found = 2 Total Tubes Found = 2 1