"~'T Duke Power Company l

A w atow p a mp,

Mc uire Nuclear Station 12700 Hagers Ferry Rd.

Huntersville, NC 28078-9340 H. B. Barron Mce Mident, McGuire (704) 875-4800 oma Nuclear Generation Department (704) 8754809 Mx February 12, 1998 U.

S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555

Subject:

McGuire Nuclear Station Docket Nos. 50-369, 370 Emergency Response Data System (ERDS) Changes By letter dated December 11, 1997, McGuire notified the NRC of data point library changes on the Emergency Response Data System (ERDS) for Unit 2 per 10CFR50 Appendix E, Section VI.

Please find enclosed additional information requested by the NRC via conference call on January 21 1998.

Questions should be directed to Kay Crane, McGuire Licensing and Compliance, at (704) 875-4306.

Sincerely, bWd oWu/

H.

B.

Barron, Vic Presi ent McGuire Nuclear Station Attachment i

I (F Ch l

u.S 3 9802200245 980212 PDR ADOCK 05000369 m'fffitfl,f fff f l{

F PDR

_ _. ~. _ _ _. _. _ _ _. _ _ _ _ -. _ _ _ _ _ _ _. _ _ _ _ _ -. _. _ _ _.

U.S. Nuclear Regulatory Commission F'ebruary 12, 1998 Page 2 cc:

Mr.

L. A Reyes Regional Administrator, Region II U.

S. Nuclear Regulatory Commission 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323 Mr.

F. Rinaldi, Project Manager l

Office of Nuclear Reactor Regulation i

U.

S. Nuclear Regulatory Commission One White Flint North, Mail Stop 9H3 4

Washington, D.C.

20555 J.

Jolicoeur U.

S. Nuclear Regulatory Commission Mail Stop T4A43 Washington, D.C.

20555 S.

Shaeffer Senior NRC Resident Inspector McGuire Nuclear Station i

l i

9 a

i j

Attachment i

0 l

i I

i 1.

For Points Ml&2Ai124 and M1&2A0976, PZR LEVELS: Zero point is 46.75" above tank bottom and PZR Heater top is 12.7%.

2.

For Points Mi&2 Pol 80 and Mi&2 Pol 81, REAC VES LVLs,64% is Top of Core and 66.5% is j

. Centerline of Hot Legs.

3.

For Points MI&2A1004, M1&2A1005, Mi&2A0970, and M1&2A0988, SG LEVELS,0% is 9" above 4

)

tube sheet and 69.4% is at the top of the tube bundles.

4.

For the following radiation monitor detectors:

i

{

Mi&2E0174 (EMF 3611), EFF GAS RAD, MIE0307&M2E0307DI (EMF 49H), EFF LIQ RAD, Mi&2E0153 (EMF 34H), SG BD RAD, i

t the following approximatit.. correlation factors can be used:

a EMF 36H (Both Units)- 2.0E-04 pCi-ml/ cpm. based on XE-133 equivalent llllllll"::""lll:l2: '" !:" :;";:::*":" ':l"*;"l:"l*"

4 8-P i

f i

i-i 1-i

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTON UNIT: MC1 DATA FEEDER: ~U1 OAC NRC ERDS PARAMETER: PRZR LEVEL POINT ID: M1A1124 PLANT SPEC POINT DESC: U1 PZR LEVEL i GENERIC /COND DESC: PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: %

ENGR UNITS CONVERSION: 1% = 5.22" MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

Bottom REFERENCE POINT NOTES: Zero point is 46.75* above tank bottom, Htr top =12.7%.

PROC OR SENS: S i

j NUMBER OF SENSORS: 1 HOW PROCESSED: Direc' SENSOR LOCATIONS: Pressurizer Vessel Current Prodac ALARMfTRIP Hi:

Lo:-

SETPOINTS:

N1 DETECTOR POWER SUPPLY N/A t

CUT-OFF POWER LEVEL:

N1 DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

+

- INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: WET UNIOUE SYSTEM DESC.: Reverse acting D. P, transmitter supplies pressurizer level signals.

j point xref:

6.1 1

Page 1

~

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1OAC NRC ERDS PARAMETER: PRZR LEVEL POINT ID: M1A0976 PLANT SPEC POINT DESC: U1 PZR LEVEL lli GENERIC /COND DESC: PRIMARY SYSTEM PRE 55dRIZER LEVEL 4

ANALOG / DIGITAL: A ENGR UNITS / DIG STATES:

  • /o ENGR UNITS CONVERSION:

1% = 5.22' MINIMUM INSTR RANGE: 0

~

MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

Bottom REFERENCE POINT NOTES: -[ero point is 46.75" above tank bottom, Htr top =12.7%

PROC OR SENS: S NUMBER OF SENSORS:

1 HOW PiiOCESSED: Direct SENSOR LOCATIONS: Pressurizer Vessel Current Prodec ALARM / TRIP Hi: -

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: WET UNIOUE SYSTEM DESC.:

Reverse acting D. P. transmitter supplies pressurizer level signals.

point xref:

6.3 i

Page 2

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1OAC NRC ERD $ PARAMETER: REAC VES LEV POINT ID: M1P0180 PLANT SPEC POINT DESC: U1 RVLIS TRAIN A VESSEL LEVI'.

GENERIC /COND DESC: REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL: A ENGP UNITS / DIG STATES: %

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 120 ZERO POINT

REFERENCE:

TAF REFERENCE POINT NOTES: 64bTop of Core,66.5bCenterline of Hot Leg ^

PROC OR SENS: S NUMBER OF SENSORS: 7 HOW PROCESSED: Using RVLIS SENSOP LOCATIONS: Reactor Vessel (incore & Excore)

Current Prr ec ALARM / TRIP Hi:

Lo:-

SETPOINTS:

NI DETEUTOR POWER SUPPLY N/A CUT OFF POWEH LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE I

COMFENSATION FOR DP REF. LEO: N/A UNIQUE SYSTEM DESC,: Reactor Vessel Level is derived from (RVLIS) Reactor Vessel leveling system, which interacts with numerous sensors (level, pressure, temperature) to process a lower range level (0-70%) and an upper range level (60-120%). This point is the best of the lower or upper range This is a Train A sensor _.

point xtef:

8.1 Page 3

l J

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1 OAC NRC ERDS PARAMETER: REAC VES LEV POINT 10: M1P0181 PLANT SPEC POINT DESC: U1 RVLIS TRAIN B VESSEL LEVEL GENERIC /COND DESC: REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL: 7 ENGR UNITS / DIG STATES: ' %

ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 120

~

ZERO POINT

REFERENCE:

TAF REFERENCE POINT NOTES: 64%= Top of Core,66.5bcenterline of Hot Leg PROC OR SENS: S NUMBER OF SENSORS: 7 HOW PROCESSED: Using RVLIS SENSOR LOCATIONS: Reactor Vessel (incere & Excore)

Current Prodac ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF.. LEG: N/A UNIOUE SYSTEM DESC.:

Reactor Vessel Level is derived from (RVLIS) Reactor Vessel leveling system, which Interacts with numerous sensors (level, pressure, temperature) to process a lower range level (0 70%) and an upper range level (60-120*/.). This point is the best of the lower or upper range Thqis a Train A sensne.

point xref:

8.2 N

Page 4

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1 OAC NRC ERDa PARAMETER: SG LEVEL 1/A POINT 10: M1A1004 PLANT SPEC POINT DESC: 1 A S/G WIDE RANGE LEVEL

~ITEAM GENERATOR A WATER LEVEL GENERIC /COND DESC:

E l

ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: %

ENGR UNITS CONVERSION:

1% = 6 inches of H2O MINIMUM INSTR RANGE: ~ 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

TUBSHT

.i REFERENCE POINT NOTES: 0% is 9" above tube Sheet,69.4 top of tube bundle PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED: Direct SENSOR LOCATIONS: Stm Gen A Vessel Current Prodsc ALARM / TRIP Hi:

Lo: -

SETPCsNTS:

Ni DETECTOR POWER SUPPLY N/A CUT-03F POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT F ALLURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_. LEG: Wet UNIQUE SYSTEM DESC.:

Steam Generator levelis sent to OAC via the process control cabinet. Levelis Cold Calibrated.

point xref:

14 1 4

Page 5

-_.a n

e a-.

>.a-

.. + _.

..-n..-e McGuire Nuclear Station i

Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE OATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1OAC NRC ERDS PARAMETER: ~SG LEVEL 2/B POINT ID: 1A1005 PLANT SPEC POINT DESC: 1B 3/G WIDE RANGE LEVEL GENERIC /COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: %

ENGR UNITS CONVERSION: 1% = 6 inches Of H2O MINIMUM INSTR RANGE: 0 M AXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

TUBSHT REFERENCE POINT NOTES: 0% is 9' above tube sheet,69,4% top of tube bundle J

PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED: Direct SENSOR LOCATIONS: Stm Gen B Vessel Current Prodac ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

N1 DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF LEG: Wet i

UNIQUE SYSTEM DESC.: Steam Generator level is sent to OAC via the p% 38 control cabinet. Levelis Cold Cahbrated.

point xref 14.2 Page 6

McGuire Nuclear Station Emergency Response Data System (E!1DS)Imolementation PWR DATA POINT RF' 73ENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1 OAC NRC ERDS PARAMETER: SG LEVEL 3/C

^

POINT ID: M1A0970 PLANT SPEC POINT DESC: 1C S/G WIDE RANGE LEVEL GENERIC /COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG / DIGITAL: A ENGR UNITSOIO STATES: */,

ENGR UNITS CONVERSION:

1% = 6 inches of H2O MINIMUM INSTR RANGE: 0 M AXIMUM INSTrt RANGE:

100 ZERO POINT

REFERENCE:

TUBSHT REFERENCE POINT NOTES: 0% is 9" above tube sheet,69.4btop of tube bundle PROC OR SENS: S NUMBER OF SENSORS:

1 HOV. PROCESSED:

Direct SENSOR LOCATIONS: Stm Gen C Vessel Current Prodec ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT OFF POWER LEVEL:

NI DETECTc4 POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: Wet UNIQUE SYSTEM DESC :

Steam Generator level is sent to OAC via the 6, ocess control Cabinet. Levelis Cold Calibrated.

point xref:

14.3 Page 7

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1 OAC NRC ERDS PARAMETER: 5 LEVEL 4/D POINT ID: M1A0988 PLANT UPEC POINT DESC: 1D S/C WIDE RANGE LEVEL GENERIC /COND DESC: STEAM GENERATOR D WATER LEVEL ANALOG /thGITAL: A FNGR UNITS / DIG STATES: */.

ENGR UNITS CONVERSION:

1*/o = 6 inches Of H2O MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

TUBSHT REFERENCE POINT NOTES: 0% is 9" above tube sheet,69.4*/o= top of tube bundle PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED: Direct SENSOR LOCATIONS: Stm Gen D Vessel 4

Current Prodsc ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT OFF POWER LEVEL:

N1 DETECTOR POWER SUPPLY ~N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW t

TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: Wet UNIQUE SYSTEM DESC.: Steam Generator level is sent to OAC via the process control cabinet. Level is Cold Calibrated.

point xref:

14.4 1

4 Page 8

McGuire Nuclear Station Emergency Response Data Systsm (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1OAC NRC ERDS PARAMETER: EFF GAS RAD POINT ID: M1E0174 PLANT SPEC POINT DESC: 1 EMF 36H UNIT VENT GAS HI RANGE GENERIC /COND DESC: RADIOACTIVITY OF RELEASED GAS ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: appr0X. Correlat;on factor 2.0E-04 uCi/ cpm-mi MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 1700000000 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: S l

NUMBER OF SENSORS:

1 HOW PROCESSED:

Direct SENSOR LOCATIONS: Unit 1 Vent Stack Current Prodac ALARMffRIP Hi: -

LO: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF_ LEG: N/A UNIQUE SYSTEM DESC.: None point xref:

29.1 Page 9

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1 OAC NRC ERDS PARAMETER: EFF LlO RAD POINT ID: ~M1E0307 PLANT SPEC POINT DESC: 1 EMF 49H WASTE LIQUID DISC HI RANGE GENERIC /COND DESC: RADIOACTIVITY OF RELEASED LIQUID ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: approx. correlation factor 1.0E-03 uCi/ cpm-ml MINIMUM INSTR RANGE: 0 M AXIMUM INSTR RANGE: 1700000000 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

Direct SENSOR LOCATIONS: Dn Stream Waste Monitor Tank Pump Current Prodac ALARM / TRIP Hi:

LO:

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF_ LEG: N/A UNIQUE SYSTEM DESC.:

None l

point xref:

30.1 l

l l

l Page 10 1

l

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC1 DATA FEEDER: U1 OAC NRC ERDS PARAMITER: SG BD RAD POINT ID: ~M1E0153 PLANT SPEC POINT DESC: 1 EMF 34H S/G LIQUID RAD MON HI RANGE CENERIC/COND DESC: STM GEN BLOWDOWN FiAD LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: approx. Correlation factor 1.0E-03 uCl/ Cpm-ml MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 1700000000 ZERO POINT

REFERENCE:

N/A-

~

REFERENCE POINT NOTES: Shielded, Nominal Reading = 1E1 1E7 PROC OR SENS:

S' NUMBER OF SENSORS: 1 HOW PROCESSED: Direct SENSOA LOCATIONS: Outlet Stm Gen Blow Dwois Line Current Prodac ALARM / TRIP Hi:

Lo:-

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF_ LEG: N/A UNIQUE SYSTEM DESC.:

Stm Gen Blowdown Rad levelis found through continuous blowdown of each steam gen, (A D). Upon high radiation, EMF 34 will control isolation values and shutdown, point xref:

32.1 Page 11

4 MCGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE -

DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: PRZR LEVEL POINT ID: M2A1124 PLANT SPEC POINT DESC: U2 PZR LEVEL 1 GENERIC /COND DESC: PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: %

ENGR UNITS CONVERSION: 1% = 5.22" MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

Bottom REFERENCE POINT NOTES:

0%=46.75" above tank bottom.Htr top =12.7%

PROC OR SENS: $

NUMBER OF SENSORS: 1 HOW PROCESLED: Dis eCl SENSO3 LOCATIONE: Pressurizer Vessel Current Prodec ALARM /TF/P Hi Lo:-

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CU14FF POWEGEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW

~

TEMPERATURE N

COMPENSATION FOR DP REF_ LEO: WET UNIQUE SYSTEM DESC.: ~ Reverse acting D. P. transmitter supplies pressurizer level signals.

point xref:

6.1 Page 1

~

McGuire Nuclear Station Emergency Respor se Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: PRZR LEVEL

.eOINT ID: M2A0976 PLANT SPEC POINT DESC: U2 PZR LEVEL lli

~

GENERIC /COND DESC: ~ PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG / DIGITAL: A ENGR UNITS /DIO STATES: */.

~

ENGR UNITS CONVERalON: 1 % = 5.22" MINIMUH INSTR RANGE: 0 M AXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

Bottom REFERENCE POINT NOTES: 0 46.75 above tank bottom.Htr top =12,7%

PROC OR St.NS: ~S l

NUMBER OF SEN3 ORS:

1 l

l HOW PROCESSED: Direct SENSOR LOC ATIONS: Pressurizer Vessel Current Prodac ALARM / TRIP Hi:

Lo:-

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT OFF POWER LEVEL:

N1 DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: WET UNIQUE SYSTEM DESC.:

Reverse acting D. P. transrnstter supplies pressunzer level signals, point xref:

6.3 Page 2

McGuire Nuclear Station Emerge. icy Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: _ _.U2 OAC NRC ERDS PARAMETER: REAC VES LEV i

POINT ID: M2P0180 PLANT SPEC POINT DESC: RVLIS TRAIN A VESSEL LEVEL GENERIC /COND DESC: REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES:

  • /o ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 120 ZERO POINT

REFERENCE:

TAF REFEREF ?E POINT NOTES: 64bTop of Core,66.5% = Centerline of Hot leg l

PROC OR SENS: S NUMeER OF SENSORS: 7 HOW PROCESSED: Using RVLIS SENSOR LOCATIONS: Reactor Vessel (Incore & Excore)

Current Prodec ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY -N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF_ LEG: N/A UNIOUE SYSTEM DESC.:

Reactor Vessel Level is derived from (RVLIS) Reactor Vessel leveling system, which interacts with numerous sensors (level, pressure, temperature) to process a lower range level (0-70%) and an upper range level (60-120%). This point is tr e best of the lower or upper range. 64bTop of Core. 66.5% Centerline of Hot Leg This is a Train A sensor.

1 point xref:

8.1 i

Page 3

- - - - - - - - - - -. - ~ -

m

9 McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2

~

DATA FEEDER: U2 OAC NRC ERDS PARAMETER: ~REAC VES LEV POINT ID: M2P0181 PLANT SPEC POINT DESC: WLIS TRAIN B VESSEL LEVEL GENERIC /COND DESC: REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL: A ENGR UillTS/DIO STATES: */,

ENGR UNITS CONVERSION: N/A MIN' MUM INSTR RANGE: 0 MAXIMUM INSTR RANGEt 120 ZERO POINT

REFERENCE:

TAF REFERENCE POINT NOTES: 64bTop of Core,66.5% = Centerline of Hot leg PROC OR SENS: S NUMBER OF SENSORS: 7 HOW PROCESSED: Using RVLIS SENSOR LOCATIONS: Reactor Vessel (incore & Excore)

Current Prodec ALARM / TRIP Hi:

Lo: -

SETPOINTS.

N1 DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRU?AENT FAILURE MOch: LOW TEMPERATURE COMPENSATION FOR DP REF_ LEG: N/A UNIOUE SYSTEM DESC.: Reactor Vessel Leval is denved from (RVLIS) Reactor Vesset levelin0 system, which interacts with numerous sensors (level, pressure, temperature) to process a lower range level (0 70%) and an upper range level (60-120%). 64% Top of Core.

66.5 Centenine of He This point is the best of the lower or upper range This is a Train A sene..

point xref:

9.2 Page 4

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UMT MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: SG LEVEL 1/A POINT ID: M2A1004 PLANT SPEC POINT DESC: 2A S/G WIDE RANGE LEVEL GENERIC /COND DESC: ~ STEAM GENERATOR A WATER LEVEL ANALOG / DIGITAL: A ENGR UNITS /DIO STATES: ~%

ENGR UNITS CONVERSION:

1% = 6 O aeS of H2O MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

TUBSHT REFERENCE POINT NOTES: 0% is 9" above tube sheet,69.4%= top of tube bundle PROC OR SENS: $

NUMBER OF SENSORS:

1 HOW PROCESSED:

Direct SENSOR LOCATIONS: Stm Gen A Vessel Current Prodec ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER EUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF LEO: Wet UNIQUE SYSTEM DESC.: Steam Generator level is sent to OAC via the process control cabinet Levelis Cold Calibrated.

j I

point xref:

14.1 Page S

4 McGuire Nuclear Station Emergency Response Data Fystem (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: SG L EVEL 2/B POINT 10: M2A1005 PLANT SPEC POINT DESC: 2B S/G WIDE RANGE LEVEL GENERIC /COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: %

ENGR UNITS CONVERSION: 1% = 6 inches of H2O

~

"^

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100

~

ZERO POINT

REFERENCE:

TUBSHT REFERENCE POINT NOTES: 0% is 9" above tube Sheet,69,4btep of tube bundle PROC OR SENS: $

NUMBER OF SENSORS; 1

HOW PROCESSED: Direct SENSOR LOCATICNS: Stm Gen B Vessel

~~

Current Prodac ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPL Y N/A CUT OFF POWER LEVEL:

NI DETE:CTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: Wet UNIQUE SYSTEM DESC : Steam Generator levelis sent to OAC via the process Control Cabinet. Level is Cold Calibrated.

point xref:

14.2 Page 6

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE l

DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: SG LEVEL 3/C

~

POINT ID: M2A0970 PLANT SPEC POINT DESC: 2C S/G WIDE RANGE LEVEL

~

GENERIC /COND DESC: STEAM GENERATOR C WATER LEVtil ANALOG / DIGITAL: A ENGR UNITS / DIG STATES:

of, ENGR UNITS CONVERSION: 1% = 6 inCneS of H2O MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

TUSSHT REFERENCE POINT NOTES: 0% is 9' above tube Sheet,69.4btop of tube bundle PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED: Direct SENSOR LOCATIONS: Stm Gen C Vessel Current Prodac ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER 6UPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: Wet UNIOUE SYSTEM DESC,: Steam Generator levells sent to OAC via the process control cabinet. Level is Cold Calibrated.

point xref:

14.3 Page 7

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2

~

DATA FEEDER: U2 OAC NRC EADS PARAMETER: lG LEVEL 4/D POINT 10: M2A0988 PLANT SPEC POINT DESC: ~2D S/G WIDE RANGE LEVEL GENERIC /COND DESC: STEAM GENERATOR D WATER LEVEL

~

ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: */.

ENGR UNITS CONVERSION:

1% = 6 inches of H2O MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

TUBSHT REFERENCE POINT NOTES. 0% is 9' above tube sheet,69.4btop of tube bundie PROC OR SENS: 'S NUMBER OF set: SORS:

1 HOW PROCESSED: Direct SENSOR LOC ATIONS: Stm Gen D Vessel Curren Prodec ALARM / TRIP Hi:

Lo:-

SETPOINTS:

Nie 7ECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

Hi DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTF1UMENT FAILURE MOPE: LOW TEMPERATURE N

COMPENSATION FOR DP REF_ LEG: Wet UNIOUE SYSTEM DESC.: Steam Generator level is sont to OAC via the proaess control cabinet Levelis Cold Calibrated.

point xref:

14.4 Page 8

i 4

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: ~U2 OAC NRC ERDS PARAMETER: EFF GAS RAD POINT ID: M2E0174 plt.NT SPEC POINT DESC: 2 EMF 36(H) UNIT VENT GAS (HI RANGE)

GENERIC /COND DESC: RADIOACTIVITY OF RELEASED GAS ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: appr0X. Correlation factor 2.0E-04 uCi/ cpm-mi MINIMUM ' INSTR RANGE: 0 MAXIMUM INSTR RANGE: 1700000000 ZERO POINT

REFERENCE:

3 REFERENCE POINT NOTES: N/A PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCE9 SED:

Direct SENSOR LOCATIONS: Unit 1 Vent Stack Current Prodec ALARM / TRIP Hi:

Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LF. VEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP 4

REF. LEG: N/A UNIQUE SYSTEM DESC.: None point xref:

29.1 Page 9

4 McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: EFF LIO RAD POINT ID: M2E0307D1 PLANT SPEC POINT DE: 0: 1 EMF 49H WASTE LIQUID DISC (HI RANGE)

GENERIC /COND DESC: RADIOACTIVITY OF RELEASED LIQUID ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: approx. Correlation f actor 1.0E-03 uCi/ cpm-mi MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: I700000000 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: S l

NUMBER OF SENSORS:

1 HOW PROCESSED:

Direct SENSOR LOCATIGNS: Dn Stream Waste Monitor Tank Pump Cu.'nt Prodec ALARM / TRIP Hi:

LO:

SETPOINTS:

NI DETECTOR POWER SUPPLY N/A CUT OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY 3A TURNON 'OWER LEVEL:

INSTRUMENT Fad 'JRE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF. LEG: N/A UNIOUE SYSTEM DESC.:

Data datalt <ed from Unit 1 computer point xref:

30.1 Page 10

4

+

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 2/11/98 REACTOR UNIT MC2 DATA FEEDER: U2 OAC WRC ERDS PARAMETER: SG BD RAD POINT ID: M2E0153 PLANT SPEC POINT DESC: 2 EMF 34(H) S/G SAMPLE (HI RANGE)

GENERIC /COND DESC: STM GEN BLOWDOWN R AD LEVEL ANALOG / DIGITAL: A ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVERSION: approx. correlation f actor 1.0E-O'3 uCi/ cpm-ml MINtMUM INSTR RANGE: 0 M AXIMUM INSTR RANGE: 1700000000 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: Shielded, Nominal Reading = 1E1 - 1E7 PROC OR SENS: S NUMBER OF SENSORS:

1 HOW PROCESSED:

Direct SENSOR LOCATIONS: Outlet Stm Gen Blow Dwon Line Current Prodac ALARM / TRIP Hi:

Lo: -

SETPOINTS:

N1 DETECTOR POWER SUPPLY N/A CUT OFF POWER LEVEL:

N1 DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP REF_ LEG: N/A UNIOUE SYSTEM DESC.:

Stm Gen Blowdown Rad levelis found through continuous blowdown of each steam

_ en. (A D). Upon high radiation. EMF 34 will controlisolation values and shutdown, g

point xref:

32.1 1

Page 11 l

l