Text
_ - _ _ _ - _ _ _ _ _ _ _ _ _ - _ _ _
p* *to%
fo k
UNITED STATES j
NUCLEAR REGULATORY COMMISSION 2
WASHINGTON, D.C. 30665 0001 COMMONWEALTH EDISON COMPANY DOCKET NOXVJ LASALLE COUNTY STATION. UNIT 1 AMENOMENT TO FACILITY OPERATING LICENSE Amendment No 122 License No. NPF 11 1.
Tl o duelear Regulatory Commission (the Commission) has found that:
A.
The application for smendment filed by the Commonwealth Edison Company (the licensee) dated August 12,1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth in 10 CFR Chapter I; l
B.
The facility will operate in conformity with the application, the provisions of the Act, and the regulations of the Commission; I
C.
There is reasonable assurance: (i) that the activities authorized by ti;is amendment can be conducted w'thout endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the co.nmon defense and security or to tre health and safety of the puDlic; and E.
The issuance of this amendment is in acccrdanca with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the enclosure to this license amendment and paragraph 2.C.(2) of the Facility Operating License No. NPF 11 is hereby amended to read as follows:
9902180147 900123 PDR ADOCK 05000373 p
2 (2)
Technical Boecifications and Environmental Protection Plan The Tesnical Specifications contained in Appendix A, as revised through Amendment No. 122, and the Environmental Protection Plan contained in Appendix B, are hereby incorporated in the license. The licensee shall operats the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendr(eent is effective as of the date of its issuance and shall be implemented prior to restart from L1F35.
FOR THE NUCLEAR REGULATORY COM's.4. SION
/ cod '7Y f Donna M. Sksy, Project Manager Project Directorate 1112 Division of Reactor Projects. Ill/IV Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of issuance:
J.snuary 23, 1998 f
5 4
--m, w
ATTACHMENT TO UCENSE AMENDMENT No.122 FACILITY OPERATING LICENSE NO. NPF 11 DOCKET NO. 50-373 Replace the following page of the Appendix 'A" Technical Specifications with the enclosed page.
The revised page is identified by an amendment number and contains a vertical line indicating the area of change. The page identified by an asterisk is provided for convenience cMv, REMOVE INSERT 3/4 7 3 3/4 7 3
'3/474
- W474 l
PLdNTSYSTEMS ULTIMATE HEAT SINK LIMITIPG CONDITION FOR OPERATION 3.7.1.3 The CSCS pond shall be OPERAELE.
APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, 3, 4, 5, and *.
AC110N: With the CSCS pond incperable, restore the pond to OPERABLE status within 90 days or:
a.
In OPERATIONAL CONDITION 1, 2, or 3, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b.
In OPERATIONAL CONDITION 4, 5, or *, declare the RHRSW system and the diesel generator cooling water system inoperable and take the ACTION required by Specifications 3.7.1.1 and 3.7.1.2.
SURVEILLANCE REQUIREMENTS 4.7.1.3 The CSCS pond shall be determined OPERABLE at least once per 18 months by determining that:
a.
No sediment deposition in excess of 1.5 foot has occurred in the l
intake fiume or in the CECS pond as determined by a teries of sounding cross sections compared to as-built soundings, b.
The pond bottom elevation is less than or equal to 686.5 feet.
- When hanJ11ng irradiated fuel in the secondary containment.
LA SALLE - UNIT 1 3/4 7-3 Amendment No.122
i PLANT SYSTEMS 3/4.7.3 CONTPOL R00N AND AUXILIARY ELECTRIC E001PMENT ROOM EMERGENCY 1
FILTRA'IDM 5Y3ItM LIMITING CON 0! TION NR OPERATION 1
1 3.7.2 Two independent control room and auxiliary electric equipment room l
emergency filtration system trains shall be OPERABLE.8 1
(
APPLICABILITY: All 0PERATIONAL CONDITIONS and *.
ACTION:
With one emergency filtration system train inoperahle, restore the
~
a.
looperable train to OPERABLE status within 7 days or:
1.
In OPERATIONAL CONDITIONS 1, 2, 3, be in at least HOT SHUTDOWh within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
2.
In OPERATIONAL CONDITION 4, 5 or
- initiate and maintain operation of the OPERABLE emergency, filtration system in the i
pressurization mode of operation.
b.
With both emergency filtration system trains inoperable, in OPERATIONAL CONDITION 4, 5 or *, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment and operations with a potential for draining the reactor vessel.
c.
The provisions of Specification 3.0.3 are not applicable in Operational Condition *.
SURVEILLANCE REQUIRENENTS 4.7.2 Each control room and auxiliary electric equiment room emergency i
filtration system train shall be demonstrated OPERAB.E:
At least once per 31 days on a STAGGERED TEST BASIS by initiating, a.
from the control room,. flow through the HEPA filters and charcoal adsorbers and verifying that the train operates for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters OPERABLE.
"When irradtated fuel is being handled in the secondary containment.
ThenormaloremergencypowersourcemaybeinoperableinOPERATIONAL CONDITION 4, 5 or t
LA SALLE - UNIT 1 3/4 7-4 i
,m-
. g u.g l
k po UNITED STATES
'g NUCLEAR RECULATCRY C2MMISSIEN o
WASHINGTON, o.C. 30646 4 001
%.....d COMMONWEALTH EDISON COMPANY DOCKET NO. 50 374 LASALLE COUNTY STATION. UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.107 Ucense Ho, NPF 18 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The appCcation for amendment filed b the Commonwealth Edison Company
/
(the licensee) dated August 12,1997, complies with the standards and 4
requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth in 10 CFR Chapter I; I
B.
The facility will operate in conformity with the application, the provisions of the Act, and the regulations of the Commission; C.
There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without eredangering the health and safety of the public, and (ii) that r,uch activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the enclosure to this licenbe amendment and pe ~,iph 2.C.(2) of the Facility Operating License No. NPF 18 is hereby amended to read as follows:
s 1
t t
2-(2)
Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No.107, and the Environmental Protection Plan contained in Appendix B, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of the date of its issuence and shall be implemented prior to restart from L2RO7.
FOR THE NUCLEAR REGULATORY COMMISSION s
9 l -.U'? Y h Donna M. Skay, Project Manager Project Directorate 1112 Division of Reactor Projects lil/IV Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of issuance:
January 23, 1998
ATTACHMENT TO LICENSE AMENDMENT NO.107 FACILITY OPERATING LICFjiSE NO. NPJ_dA DOCKET NO. 5.Q E(
Replace the following prge of the Appendix %" Technical Specifications with the enclosed page.
The revised page is identified by an amendment number and contains a vertical line indicating the area of change, The page identified by an ?.sterisk is provided for convenience only.
REMOVE INSERI l
3/4 7 3 3/4 7 3 l
'3/47-4
'3/47-4 i
l
PLUTSYSTEMS ULTIMATE HEAT SINK LIMITING CONDITION FOR OPERATION 3.7.1.3 The CSCS pond shall be OPERABLE.
APPLICABILITY: OPERATIONAL CONDITIONS 1, 2. 3, 4, 5, and *.
ACTION: With the CSCS pond inoperable, restore the pond to OPERABLE status within 90 days or:
a.
In OPERATIONAL CONDITION 1, 2 or 3 be in at least HOT SHUTDOWN withinthenext12hoursandInCOLDSHUTDOWNwithinthefollowing 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b.
In OPERATIONAL C0NDIT10N 4, 5, or *, declare the RHRSW system and the diesel generator cooling water system inoperable and take the ACTION required by Specifications 3.7.1.1 and 3.7.1.2.
SURVEILLANCE REOUIREMENTS 4.7.1.3 The CSCS pond shall be determined OPERABLE at least once per 18 months by determining that:
1 I
a.
No sediment deposition in excess of 1.5 foot has occurred in the intake flume or in the CSCS pond as determined by a series of sounding cross-sections compared to as-built soundings, b.
The pond bottom elevation is less than or equal to 686.5 feet.
- When handling irradiated fuel in the secondary containment.
l LA SALLE - UNIT 2 3/4 7-3 Amendment No.107 L
PLANT SYSTEMS b^
3/4.7.2 ~ CONTROL R0CN AND AUXILIARY ELECTRIC EQUIPMENT ROOM EMERGENCY FILTRATION SY5 TEM LINITING CONDITION FOR OPERATION I
3.7.2 Two independent control room and auxiliary electric equipment roon emergency filtration system trains shall be OPERA 8LE.#
APPLICA8ILITY: All 0PERATIONAL CONDITIONS and *.
ACTION:
. With one emergency filtration system train inoperable, restore the a.
inoperable train to OPERABLE status within 7 days or:
j 1.
In OPERATIONAL CONDITIONS 1, 2, 3, be in at least HOT SHUTDOWN i
- within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
2.
- In OPERATIONAL CONDITION 4, 5 or *, initiate and maintain operation of the OPERABLE emergency filtration system in the pressurization mode of operation.
. b.
With both emergency filtration system trains inoperabu, in I
OPERATIONAL CONDITION 4, 5 or *, suspend CORE ALTERATIONS, handling of irradiated fuel in the secondary containment and operations with a potential for draining the reactor vessel.
c.
The provisions of Specification 3.0.3 are not applicable in Operational Condition *.
1 1
SURVE!LLANCE REQUIREMENTS 4.7.2 ; Each control room and auxiliary electric equipment room emergency filtration system train shall be demonstrated OPERABLE:-
a.
At least once per 31 dayslon a STAGGERED TEST P/s S by initiating, i
from the control room. flow through the HEPA fs " tars and charcoal adsorbers and verifying that the train operates for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters OPERABLE.
"When.1rradiated fuel is being handled in the secondary containment.
- The~ normal or em?c CON 0! TION 4,5or!encypowersourcemaybe-inoperableinOPERATIONAL h
h LA SALLE - UNIT 2 3/4 7-4 F
i
-,----.--1,
.c.e-y--..e-,
-..,.--.rs-.--,,,y-,--.e,
-.-,w-,,,.wm,x,-
m r-w-yy-,.,,. - -.-.--,
--,---,-,wm-.----,n.v.*
. -