ML20199H363

From kanterella
Jump to navigation Jump to search
Rev 20 to AR-401, PSA F Annunciator Response
ML20199H363
Person / Time
Site: Crystal River 
Issue date: 01/29/1998
From:
FLORIDA POWER CORP.
To:
References
AR-401, NUDOCS 9802050020
Download: ML20199H363 (187)


Text

Document Transmittal #: 86187 Date: 1/29/98 TC:

NRC (DC DESK)

MAC:- N/A Destination:

==

Description:==

Copy Copy Totals Document:~

Revision:

Comment:

INFO CNTL MSTR AR0401 20 24 1

0 0

- Instructions to the Addressee:

Pl:aso verify the docurrent(s) received agrees with the above information.

Operations department must attach old document (s) or portions of document (s) superseded by the above to this transmittal.

i The signature indicates acknowledgment of receipt of the above document (s) and that documents hav6 mU been updated. Return signed and dated transmittal to Document Control within 15 working dr.ys of UOg1

)

transmittal date to mall code:

NA1C Florida Power Corporation ll ll lllll ll l ll llll 4,,.

=.. n Document Control. NA1C ll ll lI l ll l ll ' l lll V N L..A o O Crystal RAer Energy Compkx 15760 W. Power une St.

Crystal River, FL 344284708 Signature of Addressee:

Date:

~9002C$0020 980129 PDR ADOCK 05000302 F

PDR a

s i

Rev. 20 f

l,!OS. k Effective Date r

I IN?OR,MA <.n.N a

ONLY ANNUNCIATOR RESPONSE AR-401

- FLORIDA POWER CORPORATION-CRYSTAL RIVER UNIT 3 PSA F ANNUNCIATOR RESPONSE 1

i APPROVED BY: Interpretation Contact Yid '0-0 N /)/4f-(SIGNATUREONFILEI DATE:.

Ts' /98' INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support a-e

  • + ~

3-

.m..

,-w-

=

s

.6,.s

=---------.r

--e--,==

-,mwer w

?

,A TABLE OF CONTENTS SECTION PAgg

~1.0 PURP05E.................................................................

1 2.0 REEERENCE5..............................................................

1 2.1 IMPLEMENTING REFERENCES.............................................

1 2. 2 DEVE LQEMENTAL REFERENCES........................................... 1 3.0 PE.RSONNEL INDOCTRINATION.........................,......................

1 4.0. INSTRUCTIONS............................................................

2 5. 0 FOLLQW-UP ACTI.QfiS....................................................... 2 ENCLOSURES 1

An n u n c i a t o r R e s po n s e............................................... 3 o

. 1

.fg

.y 9

,,y y)

(

\\ j.

AR-401

.Rev. 20 Page i

1.0 PURPOSE j

t-- \\,

_1.1 Establish a reference document for each Annunciator Window on the PSA-X Lampbox.

1.2 Establish operator status for valid Annunciator alarms on the PSA-X Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the PSA-X Lampbox.

2.0 REFERENCES

2.1 IMP _LEMENIMG_.EEEEEEEES 2.1.1 OP-409 - Plant Ventilation 2.1.2 OP-417 - Containment Operating Procedure 2.1.3 OP-703 - Plant Distribution System 2.1.4 AP-250 - Radiation Monitor Actuation 2.1.5 AP-513 - Toxic Gas 2.1.6 AP-880 - Fire Protection 2.1.7 OP-417A - Industrial Cooling System 2.1.8 SP-300 - Operating Daily Surveillance Log 2.1.9 PM-294 - Calibration of Robert Shaw Vibra Switches 2.2 QEVELOPMENTAL REFEREEES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 3.0 PERSONNEL INDOCTRINATIQN 3 ; 1' The Annunciator System-is powered from VBDP-5-Breaker 28.

_ -[.

N..

AR-401 Rev. 20 Page 1

?

i -

ll :

+

s 1

i

. INSTRUCTIONS' f

i 4.0=

t

+

'i F

4. li

-. Respond to alarms-on the PSA-X Lampbox'as indicated on Enclosure-1, j

Annunciator Response.

j f

l-5.0

FOLLOW-UP ACTIONS I:

I None.

i I

i i

r i

1-i 4

i 9

k u

4 a

1 i

r i:

i

?

+

i-4 t

=

L l -

eo 4

j --

4 i-(.'..

+

i-D.

i..

j -,

i:

a:

1' 1

J 2

4. '

g.o h

AR-401!

Rev. 204 Page~2 4-d'

-yr<,*~~w-,,

c

,-,v#:.+-.,----

r e..e -

r r ww = - -,+ +m e r s'-

w--t'

- +

i-=e+

- - = i r-

.. *. * - = - - - - - -, + - - - - - + - - - - - - - -

- - - - - - - - - ~ - - - - - - - ~ ~ - - - - - - -

IXCLQSURE_1 (Page-1 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 1-l l

CNTRL COMPLEX l

l-FAN l

l TRIP I

I g

I l

EVENT POINT 0466 INDICATF.D CONDITION:

o AHF-17A MOTOR IS NOT ENERGIZED WITH CONTROL llANDLE IN NORMAL AFTER START POSITION A

t V.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o-GREEN LIGHT ON WITH A RED FLAG ON CONTROL-STATION o. RADIATION HIGH RAD ALARM RM A-5 r

1 OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF TRIP o START AHF-178 o RESTORE VENTILATION PER OP-409 0 REFER--TO AP-250 DISCUSSION:

J m:

-- / J

REFERENCES:

DRAWING 208-005 SHEET AH-80 SENSING ELEMENT: CS/SC.CS/0, 42B AR-401:.

Rev. 20 Page,

b

).

ENCLOSURE 1-(Page 2 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01 F-01-01 I

I CNTRL COMPLEX l

l FAN 1.

I TRIP l

I I

-l I

I EVENT POINT 0467 INDICATED CONDITION:

o AHF-178 MOTOR IS NOT ENERGIZED WITH. CONTROL HANDLE IN NORMAL AFTER START POSITION G.Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF TRIP o-REFER TO AP-250 o. START AHF-17A o -RESTORE VENTILATION PER OP-409 DISCUSSION:

REFERENCES:

' DRAWING 208-005 SHEET AH-81

-(')

SENSING ELEMENT: CS/SC, CS/0, 42B gj

' 'AR-401 Rev. 20 Page 4

ENCLOSURE 1 (Page 3 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX I'

FAN I

TRIP t

EVENT POINT 0470

-.1 INDICATED CONDITION:

o AHF-38A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT ~ INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-18A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF TRIP o START AHF-18B o RESTORE VENTILATION PER OP-409 DISCUSSION:

REFER TO TECH SPECS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

. DRAWING-208-005 SHEET AH-82

]n-_)

SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev 20:

Page 5

ENCLOSURE 1 4j (Page 4 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01 F-01-01

'I I

CNTRL COMPLEX l

l FAN

.l TRIP l

l I

I EVENT POINT 0471 INDICATED CONDITION:

o AHF-18B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION A-'()

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-188 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF TRIP o START AHF-18A o RESTORE VENTILATION PER OP-409 DISCUSSION:

REFER TO TECH SPECS FOR ADMINISTRATIVE REQUIREMENTS REFERENCES'- DRAWING 208-005 SHEET AH-83

(,/

SENSING ELEMENT:

CS/SC, CS/0. 42B AR-401-Rev. 20 Page 6 1

e LifCLOSURE 1 (Page 5 of.183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 1

I CNTRL COMPLEX l

-l FAN-1 I

^

TRIP l

l I

I I

l EVENT POINT 0478 INDICATED CONDIT.*0N:

o -- AHF-19A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION

.(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-19A CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF-TRIP o REFER TO AP-250 o START AHF-19B o RESTORE VENTILATION PER OP-409 DISCUSSION:

REFERENCES:

- DRAWING'208-005 SHEET AH-86 ij SENSING ELEMENT': CS/SC, CS/0, 428 AR-4011 Rev. 20 Page 7

ENCLOSURE 1 (Page 6 of 183)

PSA ANNUNCIATOR RESPONSE

'PSA-X-01-01 F-01-01 1

l l

CNTRL COMPLEX -

l l

FAN-l l

TRIP I

l-I I

I I

EVENT POINT 0479 INDICATED CONDITION:

f o AHF-198 MOTOR:IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-19B CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:

o -INVESTIGATE THE CAUSE OF TRIP o START AHF-19A-o P.ESTORE VENTILATION PER OP-409 o REFER TO AP-250 DISCUSSION:

,N

REFERENCES:

DRAWING 208-005 SHEET AH-87

(

SENSING ELEMENT: : CS/SC, CS/0,- 428 AR-401 Rev. 20 Page 8

/"'N-ENCLOSURE 1

,Q (Page 7 of 183)-

PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 l

l CNTRL COMPLEX l

l FAN I

I TRIP I

I I

I I

I EVENT POINT 0482 INDICATED CONDITION:

o AHF-20A MOTOR FAST SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PUSHED IN NORMAL AFTER START POSITION

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

~

-o CREEN FAST SPEED LIGHT ON WITH A RED FLAG ON AHF-20A CONTROL STATION o' RADIATION HIGH RAD ALARM RM-A-5 o_ T0XIC GAS ACTUATIU OPERATOR ACTIONS'FOR-A \\i O ALARM:-

o : INVESTIGATE THE CAUSE OF TRIP o NOTIFY-CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED

o-REFER TO OP-409 o' REFER TO AP-250 OR AP-513 8

DISCUSSION:

1T.MAY BE POSSIBLE TO OPERATE.AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY SAMPLE HOOD VENTILATION

~

REFERENCES:

DRAWING-208-005 SHEET AH-88 y]

" )-

SENSING ELEMENT:

CS/SC, CS/0, NC/LAT, 42B iAR-401-Rev. 20 Page 9

i (O)

ENCLOSURE _l (Page 8 of_183)-

l 1

PSA ANNUNCIATOR RESPONSE-PSA-X-01 F-01-01 --

l l

CNTRL COMPLEX l

P 1

I FAN l

l l

TRIP

'l I

I I

I I

1 EVENT POINT 0483 INDICATED CONDITION:

o AHF-20A MOTOR SLOW SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PULLED OUT NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH.WILL VERIFY ALARM:

.o GREEN SLOW SPEED LIGHT ON WITH A RED FLAG ON AHF-20A CONTROL STATION OPERATOR ACTIONS FOR A VALID-ALARM:-

o INVESTIGATE THE-CAUSE OF TRIP

.o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED-4 o REFER T0 OP-409 DISCUSSION:

REFERENCES:

- DRAWING 208-005 SHEET AH qr]:

A/

SENSING ELEMENT: CS/SC.; CS/0, NC/LAT, 428

AR-401-Rev. 20 Page 10

ENCLOSURE _1

.. i (Page 9 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 l

l CNTRL COMPLEX l

l FAN I

I TRIP l

I I

I I

I EVENT POINT 0484 INDICATED CONDITION:

o AHF-20B MOTOR FAST SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PUSHED IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALAPM:

o CREEN FAST SPEED LIGHT ON WITH A RED FLAG ON AHF-208 CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 o T0XIC CAS ACTUATION OPERATOR ACTIONS FOR A VALID ALARM:

o - INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 o REFER TO AP-250 OR AP-513 DISCUSSION:

IT MAY BE POSSIBLE TO OPERATE AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY' SAMPLE HOOD VENTILATION

REFERENCES:

DRAWING 208-005 SHEET AH-89

. --(/

SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 428 ARL401 Rev. 20-Page 11

.. ~

~

s ENCLOSURE 1

(

(Page 10 of 183)-

t PSA ANNUNCIATOR RESPONSE' PSA-X-01 F-01-01 1

i 1-CNTRL-COMPLEX l

l FAN I

I TRIP l

I I

I I

I EVENT POINT 0485 INDICATED CONDITION:

o' AHF-20B MOTOR SLOW SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PULLED OUT NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN SLOW SPEED LIGHT ON WITH A RED FLAG ON AHF-20B CONTROL STATION

+

OPERATOR ACTIONS FOR A. VALID ALARM:

o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 DISCUSSION:

REFERENCES:

DRAWING 208-005 SHEET AH-89 SENSING ELEMENT:

CS/SC, CS/0, NC/LAT, 428 AR-401

Rev.-20 Page 12

ENCLOSURE 1 (Page 11 of 183)

PSA ANNUNCIATOR RESPONSE' PSA-X-01-01 F-01-01

?

I l-CNTRL COMPLEX l

l FAN

-1 I-TRIP I

I

'I I

I I

EVENT POINT 0491 INDICATED CONDITION:

o AHF-30 MOTOR-IS NOT ENERGIZED WITil THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-30 CONTROL STATION

-o T0XIC CAS ACTUATION o RADIATION HIGH RAD ALARM RM-A5 OPERATOR ACTIONS'FOR A VALID ALARM:

o INVESTICATE THE CAUSE OF TRIP o REFER TO OP-409 o REFER TO AP-250 OR AP-513 DISCUSSION:

d

REFERENCES:

DRAWING 208-005 SHEET AH-93 f)-

?

A_f SENSING ELEMENT: CS/SC, CS/0, 428

-AR-401 Rev. 20-Page 13

'~X, ENCLOSURE 1

,/

(Page 12 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOVV LOVV EVENT POINT 0308 INDICATED CONDITION:

o AIR FLOW FROM "A" BATTERY ROOM IS LOW AS SENSED BY AH-734-FS

)

REDUNDANT INDICATION WHICH kULL VERIFY ALARM:

o POSSIBLE FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION HAVE CHEMISTRY SAMPLE BATTERY ROOM FOR H, CONCENTRATIONS o

DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPERS IN THE CORRECT POSITION. THIS LOSS OF FLOW FROM THE BATTERY ROOM COULD RESULT IN A BUILD UP OF HYDROGEN INSIDE THE BATTERY ROOM.

CvNSIDERATION SHOULD BE GIVEN TO VENTILATING THE AREA TO PREVENT THE POSSIBILITY OF AN EXPLOSIVE MIXTURE DEVELOPING.

REFERENCES:

DRAWING 208-005 SHEET AH-131 SENSING ELEMENT: AH-734-FS AR-401 Rev. 20 Page 14

j ENCLOSURE 1 (Page 13 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0309 INDICATED CONDITION:

o. AIR FLOW FROM "B" BATTERY ROOM IS LOW AS SENSED BY AH-735-FS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o--INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION HAVE CHEMISTRY SAMPLE BATTERY ROOM FOR H, CONCENTRATIONS o

DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FIRE DAMNER ACTUATION, CHECK FIRE

. DAMPERS IN THE CORRECT POSITION.

THIS LOSS OF FLOW FROM THE BATTERY ROOM ~COULD RESULT IN A BUILD UP OF HYDROGEN INSIDE THE BATTERY-ROOM.

CONSIDERATION SHOULD BE GIVEN TO VENTILATING THE AREA TO PREVENT THE POSSIBILITY OF AN EXPLOSIVE MIXTURE DEVELOPING.

g.

REFERENCES:

DRAWING 208-005 SHEET AH-131 SENSING ELEMENT: -AH-735-FS AR-401 Rev. 20-Fage 15

-..--~

4 y

ENCLOSURE l l(

(Page-14 of 183)

PSA ANNUNCIATOR-RESPONSE PSA-X-01-02 F-01-02 J

CNTRL COMPLEX AIR FLOW j

i LOW EVENT POINT 0442 INDICATED CONDITION:

o AHF-16A CONTROL HANDLE IN NORMAL AFTER START, AND DIFFERENTIAL PRESSURE ACROSS AHHE-10A IS <0.063" H,0 AS SENSED BY AH-123 -DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-16A TRIPPED o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:

- o = INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION o START AHF-16B TO SUPPLY SWITCHCEAR ROOMS DISCUSSION:

THIS' CONDITION MAY. BE: THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPER POSITION.

REFERENCES:

' DRAWING 208-005 SHEET AH-058, DRAWING 308846 SENSING ELEMENT: AH-123-DPS.

AR-401-Rev. 20-Page 16l

. _. ~.-

C

-ENCLOSURE 1

(

(Page 15 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0446 INDICATED CONDITION:

o AHF-16B CONTROL HANDLE IN NORMAu AFTER START,. AND DIFFERENTIAL PRESSURE ACROSS AHHE-10B IS <0.050" H,0 AS 'cNSED BY AH-124-DPS

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-168 TRIPPED o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION o START AHF-16A TO SUPPLY SWITCHGEAR ROOMS DISCUSSION:--

THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPER POSITION.

REFERENCES:

DRAWING 208-005 SHEET AH-059, DRAWING 308846

'. ).

SENSING ELEMENT:.AH-124-DPS

AR-401 Rev. 20 Page 17-

i

{

ENCLOSURE 1

.y (Pag 16 of 183).

PSA ANNUNCIATOR RESPONSE

,PSA-X-01-02 F-01-02 4

CNTRL COMPLEX

. AIR FLOW LOW EVENT POINT 0468 INDICATED CONDITION:

I o AHF-17A, OR AHF-18A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.15" H,0 AS SENSED BY AH-34-DPS

-p)-

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW FLOW INDICATION ON AH-32-FIR o POSSIBLE FAN TRIP ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE THE CAUSE OF ALARM o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-405 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FLOW BLOCKAGE.

ALTERNATING VENTILATION EQUIPMENT SHOULD CORRECT THE CONDITION.

v.s -

REFERENCES:

DRAWING 208-005 SHEET AH-080, DRAWING 308847

, SENSING ELEMENT: AH-34-DPS

[

AR-401 Rev. 20-Page 18

p)

EELOSURE 1 (Page 17 of 183) l PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F 01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0480 INDICATED CONDITION:

o AHF-19A CONTROL HANDLE.IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.10" H,0 AS SENSED BY AH-175-DPS

.D i.]

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:

o - INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIFE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER-TO OP-409 DISCUSSION:

- THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.

IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.

l jq

REFERENCES:

- DRAWING 208-005 SHEET AH-086, DRAWING 308847

)

SENSING ELEMENT:.AH-176-DPS AR-401 Rev.'20 Page 19

.~.

ENCLOSURE 1

^

(Page 18 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW t

EVENT POINT 0486 INDICATED CONDITION:

o AHF-20A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.08" H,0_ AS SENSED BY AH-36-DPS f

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FAN TRIP ALARMS I

o FIRE DAMPER ALERTS 4

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:

.THIS CONDITION MAY BE THE RESUL1 0F A FAN TRIP, OR A FIRE DAMPER ACTUATION.

IF ALTERNATING VENTILJION EQUIPMENT DOES NOT CORRECT THE

- CONDITION THERE IS PROBABLY A FIM OAMPER TRIPPED.

THIS IS AN EXPECTED-ALARM WHEN AHF-20A IS BEING RUN IN SLOW SPEED.

REFERENCES:

DRAWING 208-005 SHEET AH-088, DRAWING 308847 SENSING ELEMENT: __AH-36-DPS lAR-401.

Rev.'20 Page 20

i

}

i ENCLOSURE 1 1

(

(Page 19 of 183) 4 \\_./

i PSA ANNUNCIATOR RESPONSE PSA-X O h0h )F-01-02 t

4 CNTRL COMPLEX AIR FLOW LOW-4

.i l

EVENT POINT 1545 3

i l

TNDICATED CONDITION:

o AHF-17D, OR AHF-18B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.15" H,0 AS SENSED BY AH-546-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM o LOW FLOW INDICATION ON AH-32-FIR o POSSIBLE FAN TRIP ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE THE CAUSE OF ALARM o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409

!9

)

DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FLOW BLOCKAGE.

ALTERNATING VENTILATION EQUIPMENT SHOULD CORRECT THE CONDITION.

REFERENCES:

DRAW:NG 208-005. SHEE. AH-081, DRAWING 308847 Q

SENSING ELEMENT:- AH-546-DPS AR-401 Rev. 20 Page 21 d

['

ENCLOSURE 1 (Page 20 of 183)

PSA ANNUNCIATOR RESPONSE F'A-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW i

EVENT POINT 1546 INDICATED CONDITION:

o AHF-198 CONTROL HANDLE IN NORMAL A; iiR START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.10" H,0 AS ?ENSED BY AH-547-DPS

.O V

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:

-THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.

IF ALTERMTING VENTILATION EQUIPMENT DOES NOT CORRECT THE

. CONDITION THERE-IS PROBABLY A FIRE DAMPER TRIPPED.

REFERENCES:

DRAWING 208-005 SHEET AH-086, DRAWING 308847 4

' (,!

SENSING ELEMENT: AH-547-DPS AR-401-Rev. 20 Page 22 i

l i

i

[NCLOSURE 1 f

(Page 21 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 f

CNTRL COMPLEX AIR FLOW LOW EVENT PO!NT 1547 INDICATED CONDITION:

o AHF-208 CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.08" H,0 AS SENSED BY AH-548-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER

-ACTUATION.

IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.

YHIS IS AN EXPECTED ALARM WHEN AHF-20B IS BEING RUN IN SLOW SPEED.

REFERENCES:

DRAWING 208-005 SHEET AH-089, ORAWING 308847

()

SENSING ELEMENT: AH-548-DPS AR-401 Rev. 20-Page 23

_.. _, _. i. _ -.

. 2 :..

ENCLOSURE 1 (Page 22 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X 01-03 F-01 03 AH FLTR 4A/B PRESS HIGH EVENT POINT 0476 INDICATED CONDITION:

A HIGH DIFFERENTIAL PRESSURE EXISTS ACROSS AHFL-4A 0F >5.20" H,0 o

AS SENSED BY AH-205-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIFFERENTIAL PRESSURE INDICATOR AH-205 DPIl ON REAR OF MCB o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.

IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.

REFERENCES:

. DRAWING 208-005 SHEET AH-131, DRAWING 308847 SENSING ELEMENT: AH-205-DPS AR-401-Rev. 20 Page 24

ENCLOSURE 1 (Page 23 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-03 F-01-03 AH FLTR 4A/S PRESS HIGH EVENT POINT 0477 INDICATED CONDITION:

A HICH DIFFERENTIAL PRESSURE EXISTS ACROSS AHFL-4B 0F >5.20" H,0 o

AS SENSED BY AH-206-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DIFFERENTIAL PRESSURE INDICATOR AH-206-DPIl ON REAR OF MCb o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:-

-THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATIbN.

IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE__

CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.

REFERENCES:

-ORAWING 208-005 SHEET AH-131, DRAWING 308847 SENSING ELEMENT: AH-206-DPS AR-40'li Rev. 20 Page 25

,m.

W

-M 4-

-s 5-4m4-4 L+. + -

J.O4-J-e--.----_--A-,

..4M*--A=f -4.E--4--A.*-

.-~J-

.--a

+----4.*

.wnw-e---

+hA-N

-D--'s

---4*A+-

de+4-

--sk-ENCLOSURE 1 (Page 24 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0469 INDICATED CONDITION:

o #;!Jj.rWPERATURE OF >135'F EXISTS IN THE CONTROL COMPLEX SUPPLY DUCT AS Sc.3f! P At AH-207-TS.

1.EDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE HICH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.

IF SO A FIRE' DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-080, DRAWING 308847 7

k SENSING ELEMENT: AH-207-TS

.: AR-401 Rev. 20 Page 26

+

m

--, -,,~.... _ ~

.-..-,4 m,-J

EffCLOSURE 1

^

(Page 25 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-0.1-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0487 INDICATED CONDITION:

o HIGH TEMPERATURE OF >I35*F EXISTS IN THE DISCHAP.GE OF AHF-20A DUCT AS SENSED BY AH 258-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.

IF SO A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-088, DRAWING 308847

(

SENSING ELEMENT: --AH-258-TS AR-401 Rev. 20 Page 27

ENCLOSURE 1

. Os (Page 20 of 183) l

~

t PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 i

CNTRL COMPLEX i

DUCT TEMP HIGH EVENT PO. INT 0517 INDICATED CONDITION:

a i

o HIGH TEMPERATURE EXISTS OF >135'F IN THE DISCHARGE OF AHF-20B DUCT AS SENSED BY AH-543-TS 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o PO'.SIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS 4

OPERATOR ACTIONS FOR A VALID ALARM:

s o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o ' REFER TO AP-880 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.

IF SO A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.

f

REFERENCES:

DRAWING.208-005 SHEET AH-089 DRAWING 308847 SENSING ELEMENT: AH-543-T5 AR-401 Rev.t20 Page 28

'~.

w

.J-.

v.

E,i.-_m,,

.r-,.

_,...,,.-~,,,-#,5.,

,,.,r,.,.

ENCLOSURE l' l

O (Page 27 of 183) l PSA ANNUNCIATOR RESPONSE PSA-X 01-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0493 INDICATED CONDITION:

o HIGH TEMPERATURE OF >135T EXISTS IN THE CONTROL COMPLEX RETURN DUCT ON ELEVATION 124' AS SENSED BY AH-191-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o POSSIBLE LOW AIR FLOW ALARMS o FIRE DAMPERS FD-28, AND FD-29 ACTUATE OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 DISCUSSION:

THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.

IF SO A FIRE-DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-101, DRAWING 308847 SENSING-ELEMENT: AH-191-TS-AR-401 Rev. 20 Page'29 m.,--

i i

O ENCLOSURE 1 (Page 28 of 183)

{

PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 5

n 1

CNTRL COMPLEX.

INST AIR PRESS LOW t

EVENT POINT 1690 m

INDICATED CONDITION:

o AIR PRESSURE IN THE RECEIVER OF AHP-1A/1B AS SENSED BY AH-507-PS IS

<55 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL PRESSURE INCICATOR AH-896C-PI ON JOHNSON CONTROL PANEL 25A OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE THAT AHP-1A/1B ARE RUNNING o ' VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o_ DEENERCIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE)

ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE) o DISCUSSION:

THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION-SYSTEM "A" COMPONENTS AND A LOSS OF "A" SYSTEM AIR TO "AB" SYSTEM COMPONENTS.

g

REFERENCES:

DRAWING 208-005 SHEET AH-148 V) i SEN3ING ELEMENT: AH-507-PS

AR-401-Rev.' 20 Page 30

l ENCLOSURE 1 O

(Page 29 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-0$

t t

i CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1691 INDICATED CONDITION:

o AIR PRESSURE IN THE RECEIVER OF AHP-1C/10 AS SENSED BY AH-509-PS IS <55 PSIG O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL PRESSURE INDICATOR AH-894C-PI ON JOHNSON CONTROL PANEL 258 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE THAT AHP-1C/1D ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERG1ZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)

DISCUSSION:

Tif15 CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "B" COMPONENTS'AND A LOSS OF "B" SYSTEM AIR TO "AB" SYSTEM COMPONENTS.

REFERENCES:

DRAWING 208-005 SHEET AH-149

- Q- -

SENSING ELEMENT: AH-509-PS AR-401-Rev. 20 Page 31

1 i

LKLQ5URE 1 i

O (Page 30 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1692 INDICATED CONDITION:

o REGULATED "A" SIDE CONTROL AIR AS SENSED BY AH-512-PS IS <17 PSIG i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL PRESSURE INDICATOR AH-8968-PI ON JOHNSON C0tlTROL PANEL 25A OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE THAT AHP-1A/1B ARE RUNNING VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o

o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERCIZE AH-518-SV.(CC CONTROL. AIR SUPPLY VALVE)

DIS"SSION:

~t CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX aflLATION SYSTEM "A" COMPONENTS AND A LOSS OF "A" SYSTEM AIR TO "AB" SYSTEM COMPONENTS.

P'

REFERENCES:

DRAWING 208-005 SHEET AH-150 OQ SENSING ELEMENT: AH-512-PS AR-401

'Rev. 20-

.Page 32

i ENCLOSURE 1 (Page 31 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 4

CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1693 INDICATED CONDITION:

o AIR PRESSURE FOR DAMPER CONTROL AS SENSED BY AH-513-PS IS <17 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL PRESSURE INDICATOR AH-8958-PI ON JOHNSON CONTROL P. AEL 25AB OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE THAT AHP-1A/1B ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)

DISCUSSION:

THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR 10 CONTROL COMPLEX VENTILATION SYSTEM COMPCNENTS o

REFEF,2NCES:

DRAWING 208-005 SHEET AH-150-I N.

( ;f SENSING ELEMENT: AH-513-PS

.AR-401 Rev. 20' Page 33

~'

'~x, IliCLQiEL1

()

(Page 32 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTHL COMPLEX INST AIR PRESS LOW EVENT POINT 1694 INDICATED CONDITION:

o REGULA1ED "B" SIDE CONTROL AIR AS SENSED BY AH-514-PS IS <I7 PSIG

(,i REDUNDANT INDICATION P )1 WILL VERIFY ALARM:

o LOCAL PRESSURE INDICATOR AH-8948-PI ON JOHNSON CONTROL PANEL 258 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE THAT AHP-1C/10 ARE RUNNING VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o

o DEENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)

ENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o DISCUSSION:

THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "B" COMPONENTS AND A LOSS OF "B" SYSTEM AIR TO "AB" SYSTEM COMPONENTS,

REFERENCES:

DRAWING 208-005 SHEET AH-150 SENSING ELEMENT: AH-514-PS AR-401 Rev. 20 Page 34

f i

f O

GCLOSEL1 t

(Page 33 of 183) j PSA ANNUNCIATOR RESPONSE PSA-X-01-06 F-01 06 CNTRL COMPLEX AIR DRYER TEMP HIGH i

EVENT POINT 1695 INDICATED CONDITION o AIR TEMPERATURE ON THE OUTLET OF AHDR-1A 15 >45*F AS SENSED BY AH-510-T5 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARMt o NOTIFY MECH SUPERVISOR IN CHARGE OF HVAC TO INSPECT AHDR-1A FOR PROPER I

OPERATION DISCUSSION:

AHDR-1A 15 REFRICERATED AIR DRYER WHICH UTILIZE 5 A REFRICERANT CYCLE TO ORY CON 1ROL COMPLEX CONTROL AIR SUPPLY. HICH AIR TEMP 5 CAN BE CAUSED BY LOW REFRIGERANT CHARGE OR A DIRTY CONDEN5ER COIL.

REFERENCES:

-ORAWING 208-005-SHEET AH-150 pd SENSING ELEMENT: AH-510-T5

AR-401 Rev. 20 Page 35

i O

ENCLOSURE 1-(Page 34 of 183) i PSA ANNUNCIATOR RESPONSE PSA-X-01-06 F-01-06 i

CNTRL COMPLEX i

1 AIR DRYER TEMP HIGH l

1 4

EVENT POINT 1696 i

INDICATED CONDITION:

o AIR TEMPERATURE ON THE OllTLET OF AHDR-1B IS >45*F AS SENSED BY AH-511-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALIO ALARM:

o NOTIFY MECH SUPERVISOR IN CHARGE OF HVAC TO INSPECT AHDR-1B FOR PROPER OPERATION DISCUSSION:

r AHDR-1B-15 REFRICERATED AIR DRYER WHICH UTILIZES A REFRIGERANT CYCLE TO DRY CONTROL COMPLEX CONTROL AIR SUPPLY. HIGH AIR TEMPS CAN BE CAUSED BY LOW REFRICERANT CHARGE-OR A DIRTY CONDENSER COIL.

REFERENCES:

DRAWING 208-005 SHEET AH-150 SENSING ELEMENT: AH-511-TS AR-401 Rev. 20 Page 36

.. -- --. =.:- --

- - ~. ~.

7 b

1 l

LMCLOSURL1 1

O (Page 35 of 183)

PSA ANNUNCIATOR RESPONSE P$A-X-01-07 F-01-07 1

i CHILLED WATER l

i SYSTEM i

l TROUBLE EVENT POINT 0518 1

INDICATED CONPITION:

i o CHP-IA MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN THE NORMAL i

AFTER START POSITION 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

-o GREEN LIGHT ON WITH A RED FLAG ON THE CHP-1A CONTROL STATION i

l-o RUNNING CHILLER TRIPS ON LOW CHILLED WATER FLOW OPERATOR ACTIONS FOR A VALID ALARM:

o START CHP-1B AND CHHE-1B PER OP-409 l

DISCUSSION:

4

^

REFERENCES:

DRAWING 208-076 SHEET CH SENSING ELEMENT:.42/5CR

^

'AR-401 Rev.' 20 Page 37,

~

.e

.....u.

t i

ENCLO5URE 1 O

(Page 36 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X 01-07 F-01-07 j

CHILLED WATER SYSTEM TROUBLE EVENT POINT 0519 INDICATED CONDITION:

o CHP-1B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION

\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGH1 ON WITH A RED FLAG ON THE CHP-1B CONTROL STATION o RUNNING CHILLER TRIPPED ON LOW CHILLED WATER FLOW OPERATOR ACTIONS FOR A VALID ALARM:

o START CHP-1A AND CHHE-1A PER OP-409 W

DISCUSSION:

REFERENCES:

DRAWING 208-076 SHEET CH-04 p --

1 SENSING ELEMENT: -CS/SC, CS/0. 428 RELAY I

AR-401 Rev.'20-Page 38-

,-rae-*w.,--w,,

-4

-Ww ey-yg-g r-yp-v gr ywgwM e wy-rywww--yr-r qqw egwy-,pwp p,,9 y,g.

3y-9 w

r-we-*

--m~wv

=

)

i ENCLOSM ll 1O (Page 37 of 183) 1 PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 0520 INDICATED CONDITION o CHHE-1A BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM o GREEN LIGHT ON WITH A RED FLAG ON CHHE-3A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o SWAP CHILLERS PER OP-409 l

t DISCUSSION:

AN-ES BUS UNDERVOLTAGE CONDITION WILL CAUSE THIS CONDITION, THE BREAKER WILL NOT BE ABLE TO BE RECLOSED UNTIL THE UNDERVOLTAGE LOCK OUT HAS BEEN RESET..-

REFERENCES:

DRAWING 208-076 SHEET CH-01 SENSING ELEMENT:

CS/SC, CS/0, R/B CONTACT

.AR-401:

Rev. 20 Page 39

.a

O ENCLOSURE 1

(,)

(Page 38 of 183)

PSA ANNUNCIATOR RESPONSE PSA- 07 F-01-07 CHILLED WATER SYSTEM TROUBLE l

EVENT POINT 0521 INDICATED CONDITION:

o CHHE-IB UREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION G

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON CHHE-IB CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o SWAP CHILLERS PER OP-409 DISCUSSION:

AN ES BUS UNDERVOLTAGE CONDITION WILL CAUSE THIS CONDITION, THE BREAKER WILL NOT BE ABL5 TO BE RECLOSED UNTIL THE UNDERVOLTAGE LOCK OUT HAS BEEN RESET.

REFERENCES:

DRAWING 208-076 SHEET CH-02

\\

)

SENSING ELEMENT: CS/SC, C5/0, R/B CONTACT AR-401 Rev 20 Page 40

1 1

ENCLOSURE 1 l

)

(Page 39 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 I

l

)

I l

CHILLED WATER SYSTEM TROUBLE EVENT POINT 1526 1

INDICATED CONDITION:

P o CHT-1 LEVEL IS t 180' 2",

OR a 12" BELOW CENTER LINE OF TANK REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL LEVEL INDICATOR ON CHT-1 OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT CHEMISTRY AND REFILL CHT-1 REFER TO OP-409 DISCUSSION:

'l 8

REFERENCES:

DRAWING 208-076 SHEET CH-06

' SENSING ELEMENT:

CH-660-LSS

~

.AR-401 Rev. : 20-Page 41

t I

i i

B CLQ51E _1 j

(Page 40 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1554 INDICATED CONDITION:

o CHHE-1A BREAKER HAS NO DC CONTROL POWER 1

REDUNDANT INDICATION WH!r"' WILL VERIFY ALARMt o

NO INDICATING LIGHTS ON CHHE-1A CONTROL STATION t

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY " PULL OUT" FUSE BLOCK FOR CHHE-1A BREAKER IS INSTALLED o VERIFY DPDP-5A BREAKER 9 CLOSED DISCUSSION:-

'THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.

4 J

REFERENCES:

DRAWING 208-076 SHEET CH-01

-g s.

...G.

_ SENSING ELEMENT:

27C RELAY iAR-401-Rev. 20 Page'42 r

,y y.

,7-m,--e.6,%,my,s---w--

.w,,,7

.g.

-r-

-g-w---. + -

ENCLOSURE 1 (Page 41 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1555 INDICATED CONDITION:

o CHHE-IB BREAKER HAS NO DC CONTROL POWER j

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON CHHE-IB CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM o VERIFY PULL OUT FUSE BLOCK FOR CHHE-10 BREAKER IS INSTALLED o VERIFY DPDP-5B BREAKER 9 CLOSED DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

-THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.

REFERENCES:

DRAWING 208-076 SHEET CH-02

(_)

SENSING ELEMENT: '27C RELAY AR-401V Rev. 20.

Page 43.

L.

I i

l ENCLOSURE 1 i

, O (Page 42 of 183) l l

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 i

CHILLED WATER I

SYSTEM TROUBLE 1

EVENT POINT 1556 i

f i

INDICATED CONDITION:-

i o CHHE-IA MOTOR WINDING TEMe'ERATURE IS >105aC, OR CHHE-1A OIL TEMPERATURE IS >170'F.

_(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "0IL/ MOTOR TEMPERATURE" OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP CHILLERS PER OP-409 l

DISCUSSION:

THIS CONDITION WILL CAUSE THE CHILLER TO TRIP THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

DRAWING 208-076 SHEET CH 05

'h SENSING' ELEMENT:' 6R, 2/A AR.4011 Rev.-20 ~

Page 44

i i

LNCLQSuall O

(Page 43 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 I

4 I

T CHILLED WATER SYSTEM TROUBLE 4

i EVENT POINT 1557 l

INDICATED CONDITION:

o CHHE-1A REFRICERANT PRESSURE IS < 11.9" HG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW PRESSURE" OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP CHILLERS PER OP-409 i

DISCUSSION:

THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL-THE RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

DRAWING 208-076 SHEET CH-05 SENSING ELEMENT:

7R 2/A AR-401-Rev. 20:

Page 45-

O ENCLOSURE 1 (Page 44 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1558 INDICATED CONDITION:

o CHHE-1A REFRIGERANY PRESSURE IS >15 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "HIGH PRESSURE"-

CPERATOR ACTIONS FOR A VALID ALARM:

i o SWAP CHILLERS PER OP-409-DISCUSSION:

THIS C0hDIT161 WILL CAUSE THE CHILLER TO TRIP, THE CONDITI0t? SEALS IN UNTIL THE. RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

DRAWING 208-076 SHEET CH-05 7yV SENSING ELEMENT: : 8R, 2/A

AR-401 Rev. 20 Page 46 i-

_ _ _._..- __..._..~. -._. _. _.-__ _ _ _

j O

ENCLOSURE 1 (Page 45 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 4

CHILLED WATER SYSTEM TROUBLE EVENT POINT 1559 INDICATED CONDITION:

o CHHE-1A OIL PRESSURE IS < 27 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW OIL PRESS" 4

OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP CHILLEKS PER OP-409 DISCUSSION:

THIS CONDITION WILL CAUSE THE. CHILLER T0 TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

DRAWING 208-076 SHEET CH-05 1

SENSING ELEMENT:

9R, 2/A AR-401'

'Rev. 20' Page 47 1

ENCLOSURE 1 i

O (Page 46 of 183)

PSA ANNUNCIATOR RESPONSE l PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE l

EVENT POINT 1560 INDICATED CONDITION:

o CHHE-1A DOES NOT HAVE ANY POWER TO THE CONTROL PANEL OR COMPRESSOR MOTOR AS SENSED BY RELAY 14/R REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AMBER " POWER FAILURE" LIGHT ON LOCAL CONTROL PANEL OPERATOR ACTIONS FOR A VALIO ALARM:

o INVESTIGATE THE CAUSE OF POWER LOSS DISCUSSION:-

1

REFERENCES:

DRAWING 208-076 SHEET CH-05 SENSING ELEMENT:

14R. 2/A AR-401-Rev. 20 Page 48

ENCLOSURF_1 I

(Page 47 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1561 INDICATED CONDITION:

o CHHE-1B MOTOR WINDING TEMPERATURE IS >IO5T, OR CHHE-18 OIL TEMPERATURE IS >I70*F.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "0IL/ MOTOR TEMP" OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP' CHILLERS PER OP-409 DISCUSSION:

-THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS _IN UNTIL THE RESE1 PUSHBUTTON IS DEPRESSED

REFERENCES:

' DRAWING 208-076 SHEET CH-06

.(

\\

-Q SENSING ELEMENT:- 6R, 2/B 4

AR-401-Rev. 20 Page 49-

~ -

f;

'f*

ENCLOSURE 1

\\

(Page 48 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07

^~

CHILLED WATER SYSTEM TROU8LE EVENT POINT 1562 INDICATED CONDITION:

o CHHE-1B REFRIGERANT PRESSURE IS <11.9" HG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW PRESSURE" OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP-CHILLERS P.IR OP-409 DISCUSSION:

THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL.THE RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

-DRAWING 208-076 SHEET CH-06

(,,) -

SENSING ELEMENT:

7R. 2/B

'AR-401 Rev. 20 Page 50

1 ENCLOSURE 1

'('

(Page 49 of-183)-

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1563 INDICATED CONDITION:

o CHHE-IB REFRICERANT PRESSURE IS >15 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "HIGH PRESSURE" OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP CHILLERS PER OP-409 DISCUSSION:

THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

DRAWING 208-076 SHEET CH-06 fm().

SENSING-ELEMENT:

BR. 2/B

-AR-401 Rev. 20 Page 51

i ENCLOSURE 1 (j.-

(rage.50 of 183) 1 PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07

)

CHILLED WATER i

~ SYSTEM

- TROUBLE EVENT POINT 1564 INDICATED CONDIT70N:

o CHHE-1B OIL PRESSURE IS < 27 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW OIL PRESS" OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP CHILLERS PER OP-409 DISCUSSION:

THIS CONDITION WILL CAUSE THE CHILLER TO TRIP,.THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED

REFERENCES:

DRAWING 208-076 SHEET CH-06 y-SENSING ELEMENT:

9R, 2/B

.AR.401 Rev. 20 Page 52

ENCLOSURE 1 (Page 51 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 I

CHILLED WATER SYSTEM TROUBLE EVENT POINT 1565 INDICATED CONDITION:

o CHHE-1B DOES NOT HAVE ANY POWER TO THE CONTROL PANEL OR COMPRESSOR MOTOR AS SENSED BY RELAY 14/R REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AMBER " POWER FAILURE" LIGHT ON LOCAL CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:

-o INVESTIGATE THE CAUSE OF POWER LOSS DISCUSSION:

REFERENCES:

DRAWING 208-076 SHEET CH-06 Ir\\

(f SENSING ELEMENT:

14R, 2/8

(

l AR-401-Rev. 20 Page 53

ENCLOSURE 1-e)s t

(Page 52 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 I

I TOXIC GAS I

I MONITOR I

I TROUBLE I

I I

I I

I EVENT POINT 0314 INDICATED CONDITION:

o ONE OR MORE OF -THE FOLLOWING MONITORS' LOCAL TROUBLE ALARM 3 HAS ACTUATED:

AH-648-CE AH-652-CE AH-649-CE AH-653-CE O

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL TROUBLE ALARMS ON AH-648-CE, AH-649-CE, AH-652-CE, OR AH-653-CE o COMPUTER POINTS S263, S297, S298, 5299 FOR T0XIC CAS CONCENTRATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF TROUBLE o NOTIFY I&C TO TROUBLE SHOOT MONITORS DISCUSSION:

REFERENCES:

DRAWINC 208-005 SHEET AH-84

).

, SENSING ELEMENT: -AH-648-CE, AH-652-CE,'AH-649-CE, AH-653-CE AR-401-Rev. 20-

-Page 54

1

-)

ENCLOSURE 1

(y],

(Page 53 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 j

l i

TOXIC GAS I

I MONITOR I

l' TROUBLE I

I I

EVENT POINT 0432 a

INDICATED CONDITION:

i o T0XIC CAS >5 PPM CL AS SENSED BY-AH-648-CE AND/0R AH-649-CE OR,

>2 PPM SO, SENSED BY AH-652-CE AND/OR AH-653-CE

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINTS 5263, 5297, 5298, OR 5299 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-513 o REFER TO SP-300 DISCUSSION:

REFERENCES:

DRAWING 208-005. SHEET AH-84 L) -

SENSING-ELEMENT: 'AH-648-CE, AH-652-CE, AH-649-CE, AH-653-CE AR-401 Rev. 20 Page 55

ENCLOSURE'1-(Page 54 of 183)

( --

i PSA ANNUNCIATOR RESPONSE.

PSA-X-02 F-02-01 l

l TOXIC GAS I

I MONITOR I

I TROUBLE I

I I

l l

l EVENT POINT 0800 INDICATED CONDITION:-

T0XIC CAS >20 PPM S0, SENSED DETECTORS AT UNITS 1&2 o

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NOTIFICATION OF A SPILL FROM UNITS I&2 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-513 1

DISCUSSION:

4

REFERENCES:

DRAWING 208-005 SHEET AH-84A

- -f

\\

(_j SENSING ELEMENT:

UNITS 1 & 2 "A" OR "B" 502 DETECTOR AR-4011 Rev. 20 Page 56

ENCLOSURE 1

(

(Page 55 of-183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-04 F-02-04 Cl SYSTEM TROUBLE EVENT POINT 1567 INDICATED CONDITION:

o THE 4160V BREAKER FOR THE REACTOR BLDG. CHILLER IS CLOSED AND AN ALARM EXISTS ON THE MICROTECH CONTROL PANEL o LOW DIFFEREKTIAL DRESSURE ACROSS CIP-1A OR CIP-1B

-G (j

REDUNDANT INDICATION WHILF WILL VERIFY ALARM:

o A FAULT IS INDICATED ON THE MICROTECH FLUORESCENT DISPLAY o CIP-1A OR CIP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o DEPRESS THE " UNIT STATUS" PUSHBUTTON IF NO VISUAL DISPLAY PRESENT o DEPRESS THE " FAULT HISTORY" PUSHBUTTON ONCE TO DETERMINE THE CURRENT FAULT, ~AND EIGHT MORE TIMES FOR THE PREVIOUS EIGHT FAULTS IF DESIRED o CORRECT SOURCE OF THE FAULT, THEN DEPRESS " CLEAR FAULT" PUSHBUTTON AND i

RESTART THE CHILLER IF DESIRED, REFER TO OP-417A o IF THE CHILLER CANNOT BE RESTARTED, THEN PLACE THE SYSTEM IN THE " FREE

COOLING MOCE OR SWAP TO SW COOLING FOR THE RB COOLING UNITS,-REFER TO OP-417A o PLACE ALTERNATE CIP IN SERVICE PER OP-417A DISCUSSION:

HIGH DISCHARGE PRESSURE, WHICH IS HIGH CONDENSER PRESSURE, TRIPS THE o

HIGH MECHANICAL PRESSURE SWITCH. FIRST THE SWITCH MUST BE RESET INSIDE MICROTECH,.THEN CLEAR ' FAULT WILL ALLOW RESTART. IF THE FAULT CANNOT BE CLEARED, THEN HVAC PERSONNEL SHOULD BE NOTIFIED FOR RESOLUTION o IF-THE CHILLER IS OPERATING WHEN A CIP TRIPS, THEN THIS WILL TRIP THE CHILLER ON LOW FLOW

\\ _)

REFERENCES:

DRAWING 208-077 SHEET CI-25 m

SENSING ELEMENT:

RL3-ALM, RL6-ALM, CI-772-DPS AR-401 Rev. 20 Page 57

-~s ENCLOSURE 1 (Page 56 of:183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-04 F-02-04 Cl SYSTEh4

-TROUBLE EVENT POINT 1FG8 INDICATED CONDITION:

o HIGH VIBRATION ON CIF-1A OR CIF-1B o LOW TOWER BASIN WATER LEVEL f

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CIF-1A OR CIF-18 HAS TRIPPED o CIP-1A OR CIP-1B MAY TRIP ON LOW DP, MAY EXHIBIT CAVITATION, OR MAY CAUSE A TRIP OF THE RB CHILLER ON LOW FLOW OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY HVAC PERSONNEL FOR TRIPPED FAN ON HIGH VIBRATION o VERIFY PROPER VALVE ALIGNMENT FOR LOW BASIN LEVEL o SECURE PUMP IF CAVITATION EXISTS AND ESTABLISH SW COOLING TO THE RB UNTIL PROBLEM IS CORRECTED o ENSURE PROPER DO TANK LEVEL DISCUSSION:

c--THE BASIN WATER LEVEL IS AUTOMATICALLY MAINTAINED WITH TWO FLOAT VALVES OPERATING IN PARALLEL TO SUPPLY EACH TOWER, THE TOWER BASINS ARE CROSSTIED'SUCH THAT EITHER VALVE WILL SUPPLY BOTH BASINS. LOW BASIN LEVEL DISABLES.THE BASIN WATER HEATERS.

o D0 SYSTEM _ SUPPLIES MAKEUP TO.THE IB ROOF AND SOUTH BERM COOLING TOWER REFERENtcS: DRAWING 208-077 CI-29 AND CI-30

,,,q

k. _,)

SENSING' ELEMENT: CI-784-SS. CI-785-SS, CI-780-LS, CI-781-LS s

AR-401 Rev. 20 Page 58

I\\

,q ENCLOSURE 1 y

(Page 57 of 183)-

PSA ANNUNCIATOR RESPONSE PSA-X-02-05 F-02-05.

Cl CIRC PP 1A/B OVERLOAD EVENT POINT 1879 INDICATED CONDITION:

o CIP-1A OR CIP-1B MOTOR CURRENT IS EXCESSIVE

- f,Q -

g REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

PUMP MAY TRIP FROM LOW DP AS A RESULT OF LOCKED ROTOR OR VERY HIGH o

FLOWRATES OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE OPERATION OF CIP-1A OR CIP-1B o SWAP RB COOLING TO SW IF REQUIRED r

DISCUSSION:

4

REFERENCES:

DRAWING 208-077 CI-27 AND CI-28

.)

SENSING ELEMENT: OVERLOAD HEATERS IN INST COMPARTMENT IN UNIT 480V SG RM

'x AR-401' Rev. 20 Page 59

- J ENCLOSURE 1 f

(Page 58 of 183).

PSA ANNUNCIATOR RESPONSE PSA-X-02-06

.F-02-06 9

~

Cl CIRC PUMP-2A/B 3A/B TRIP EVENT POINT 0524 INDICATED CONDITION:

o CIP-2A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL \\ERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON CIP-2A CONTROL STATION 4

OPERATOR ACTIONS FOR A VALID ALARM:

o START CIP-2B o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

c

-- I

REFERENCES:

_ DRAWING 208-077 SHEET CI-03 i

SENSING ELEMENT: CS/SC, CS/0, R/B

-AR-401 Rev. 20

~ Page 60 i

ENCLOSURE 1 (qj (Page 59 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 l

Cl CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0526 INDICATED CONDITION:

o. CIP-2B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION

-1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON CIP-28 CONTROL STATION OPERATOR ACTIONS FOR-A VALID ALARM:

o START CIP-2A o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

E, e s,.

REFEET*IES:

DRAWING 208-077 SHEET CI-04

'{}

SENSING ELEMENT: 'CS/SC, CS/0, R/B

<r AR-401 Rev. 20 Page 61

)

ENCLOSURE 1

'g (Page 60 of__183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 Cl CIRC PUMP 2A/8 3A/B TRIP EVENT POINT 0528 INDICATED CONDITION:

o CIP-3A CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE MOTOR NOT I

ENERGITc s O

G REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON CIP-3A CONTROL STATION l

OPERATOR AGIONS FOR A VALID ALARM:

o SWAP REAGOR CAVITY COOLING TO "B" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 c

DISCUSSION:

A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFEGS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.

t i

REFERENCES:

DRAWING 208-077 SHEET CI-18 M

\\.m/

SENSING ELEMENT:42/13CR

-AR-401 Rev. 20 Page 62

ENCLOSURE ?

{gJ; (Page 61 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 Cl CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0529 INDICATED CONDITION:

o -CIP-38 CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE MOTOR NOT ENERGIZED m

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON CIP-3B CONTROL STATION OPERATOR ACTIONS FOR A VALID, ALARM:

o SWAP REACTOR CAVITY COOLING TO "A" SIDE PER OP-417 o MONITOR REACTOR-CAVITY TEMPS ON AH-1003-TIR PER OP-409 DISCUSSION:

A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS-ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.

REFERENCES:

DRAWING-208-077 SHEET CI-19

_.;q fif

-SENSING-ELEMENT: CS/SC, CS/0, 42B

'AR-401 Rev. 20 Page 63

ENCLOSURE 1

(

_(Page 62 of 183) 1 PSA ANNUNCIATOR RESPONSE PSA-X-02-07 F-02-07 Cl CIRC PUMP 2A/B OVERLOAD EVENT POINT 0525 INDICATED CONDITION:

o CIP-2A MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH LOCAL TEMPERATURES ON PUMP AND OR MOTOR OPERATOR ACTIONS FOR A VALID ALARM:

o SHUTDOWN CIP-2A AND START CIP-2B o INVESTIGATE THE OPERATION OF THE PUMP MOTOR TO DETERMINE THE CAUSE OF THE ALARM DISCUSSION:

THIS' ALARM INDICATES THAT THE INTERNAL OVERCURRENT DEVICE HAS ACTUATED AND THAT THE MOTOR MAY TRIP AT ANY TIME.

REFERENCES:

DRAWING'208-077 SHEET CI-03

~

SENSING ELEMENT: - 49X THERAL-OVERLOADS IN MCC AR-401 Rev. 20 Page 64

c ENCLOSURE 1 (Page 63 of 183) s PSA ANNUNCIATOR RESPONSE PSA-X-02-07 F-02-07 Cl CIRC PUMP 2AIB OVERLOAD 4

EVENT POINT 0527 INDICATED CONDITION:

o CIP-2B MOTOR.\\MPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH LOCAL TIMPERATURES ON PUMP AND OR MOTOR OPERATOR ACTIONS FOR A VALID ALARM:

o SHUTDOWN CIP-28 AND START CIP-2A o INVESTIGATE THE OPERATION OF THE FUMP MOTOR TO DETERMINE THE CAUSE OF THE ALARM DISCUSSION:

THIS ALARM INDICATES THAT THE INTERNAL OVERCURRENT DEVICE HAS ACTUATED AND THAT THE MOTOR MAY TRIP AT ANY TIME.

4

~

REFERENCES:

- DRAWING 208-077 SHEET CI-04'

- /^s

- () _

SENSING ELEMENT: 49X THERMAL OVERLOADS IN MCC AR-401 Rev. 20 Page 65

ENCLOSURE 1

{

i

(. Page-64 of 183).

PSA ANNUNCIATOR RESPONSE l PSA-X-02-08 F-02-08 I

I I

i l-

-- l Cl PUMP l

I-SUCT PRESS I

I LOW I

I 222 EVENT-POINT 1702 INDICATED CONDITION:

o CIP-2A BREAKER IS CLOSED AND SUCTION PRESSURE IS < 5 PSIG AS SENSED BY CI-728-PS REDUNDANT. INDICATION WHICH WILL VERIFY ALARM:

o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-99-PI OPERATOR ACTIONS FOR A VALID-ALARM:

.o CHECK CIT-1 LEVEL o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o VERIFY PROPER OPERATION OF THE REACTOR BLDG CHILLER DISCUSSION:

THIS CONDITION COULD BE CAUSED BY A LOW' LEVEL IN THE-EXPANSION TANK, OR BY-EXCESSIVE PRESSURE DROP ACROSS CIHE-3/CIHE-4A OR THE LEAK' RATE TEST COOLER. THE LINE UP OF THE SYSTEM SHOULD BE VERIFIED.

REFERENCES:

DRAWING 208-077. SHEET CI-03

.g k

SENSING ELEMENT: CI-728-PS R/A 1

AR-40I.

_Rev. 20-Page 66

ENCLOSUEL1 (Page 65 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 I

l-

-1 I

I I

Cl PUMP l

I SUCT PRESS I

I

. Low I

I 4

2 EVENT POINT 1703 INDICATED CONDITION:

o CIP-28 BREAKER IS CLOSED AND SUCTION PRESSURE IS < ' PSIG AS SENSED BY CI-729-P!

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-101-PI

-t OPERATOR ACTIONS FOR A VALID ALARM:

o CHECK CIT-1 LEVEL o INVESTICATE THE CAUSE OF LOW SUCTION FRESSURE o VERIFY PROPER OPERATION OF THE REACTOR BLDG CHILLER DISCUSSION:

THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR BY EXCESSIVE PRESSURE DROP ACROSS CIHE-3/CIHE-4A OR THE LEAK RATE TEST COOLER. lHE LINE UP OF THE SYSTEM SHOULD BE VERIFIED.

i

REFERENCES:

DRAWING 208-077 SHEET CI-04

' ().

. SENSING ELEMENT: CI-729-PS, R/A s_

5 AR-401E Rev. 20 Page 67 1

D ENCLOSURE 1 j

(Page 66 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 Cl PUMP SUCT PRESS LOW -

L_ _

EVENT POINT 1704 INDICATED CONDITION:

o CIP-3A CONTROL SWITCH IS IN NORMAL AFTER START, AND SUCTION PRESSURE IS

< 45 PSIG AS SENSED BY CI-730-PS r

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-732-PI OPERATOR ACTIONS FOR A VALID ALARM:

o CHECK CIT-1 LEVEL o - INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 o CHECK CIP-2A/2B DISCHARGE PRESSURE DISCUSSION:

THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THL EXPANSION TANK, OR

~BY EXCESSIVE FLOWRATE. THE LINE UP OF THE SYSTEM SHOULD BE VERIFIED.

A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.

"[ ')

REFERENCES:

DRAWING 208-077 SHEET CI-18 SENSING ELEMENT:

CI-730-PS AR-401' Rev. 20

-Page 68

a-4.

ENCLOSURE 1 (Page-67.of 183)

~

PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 I

I I

I I-l=

Cl PUMP -

1 I

SUCT PRESS I

I Low l

l EVENT POINT 1705 INDICATED CONDITION:

v-o CIP-3B CONTROL SWITCH IS IN NORMAL AFTER START, AND SUCTION-PRESSURE IS

< 45 PSIG AS SENSED BY CI-731-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-733-PI OPERATOR ACTIONS FOR A VALID ALARM:-

o CHECK CIT-1 LEVEL INVESTIGATE-THE CAUSE'0F LOW' SUCTION PRESSURE o

o'.. MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 o -CHECK CIP-2A/28 DISCHARGE PRESSURE' DISCUSSION:

[

- : THIS' CONDITI0tl COULD BE CAUSED BY A LOW LEVEL' IN THE FXPANSION' TANK, OR BY__ EXCESSIVE FLOWRATE. THE LINE UP OF THE: SYSTEM SHOULD BE VERIFIED.

A SUSTAINED-LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE L

, EFFECTFf ON THE-RELIABILITY OF THE NUCLEAR INSTRUMENTATION.

c

REFERENCES:

DRAWING 208-077 SHEET CI-19 i

~

SENSING ELEMENT: 1 CI-731-PS~

L AR-401--

Rev. 20'

_Page 69_

.i

'((~)T ENCLOSURE 1-(Page 68 of.183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 i

l l

I I

TURBINE BLDG

-I-I FIRE ALERT -

4 -

1 I

I I

-l l

EVENT POINT 0443 j

i INDICATED. CONDITION:

o TEMPERATURE > 135'F.AS SENSED BY AH-125-TS EXISTS IN THE INTAKE PLENUM FOR AHF-16A/16B REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-16A-TRIPS o -AHF-16B TRIPS OPERATOR ACTIONS FOR'A VALID ALARP:

o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO THE CR3 PRE FIRE PLAN

.o REFER TO AP-880 i

DISCUSSION:-

~ THIS CONDITION IS INDICAT <E OF A FIRE' OR A HIGH TEMPERATURE IN THE:

-INTAKE DUCT OF AHF-16A/AHF-168.

1 g

REFERENCES:

DRAWING 208-005~ SHEETS AH-058, DRAWING 308846 k.

SENSING EL5 MENT: AH-125-TS 1

..AR-401

-Rev. 20 Page 70-

.O ENCLOSURE 1 (Page 69 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 I

I I

I TURBINE BLDG I

I FIRE ALERT I

I I

I I

I EVENT POINT 0444 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-126-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-126-CE o TEMPERATURE > 135*F AS SENSED BY AH-126-TS EXISTS IN THE RETURN FR DUCT FROM 119' SWITCH CEAR ROOM

\\j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THIS ALARM WILL RESULT IN THE ACTUATION OF THE FOLLOWING FIRE DAMPERS FD-38, FD-40, FD-48, FD-49, AND FD-50 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE RETURN AIR DUCT FROM 119' SWITCH GEAR ROOM TO AHF-16A/AHF-168.

REFERENCES:

DRAWING 208-005 SHEETS AH-058, AH-060, AND DRAWING 308846 SENSING ELEMENT: AH-126-TS, AH-126-CE, 3AH-126-TS/RR-HV-V AR-401 Rev. 20 Page 71

O ENCLOSURE 1 (Page 70 of-183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 l

I I

I TURBINE BLDG I

I FIRE ALERT I

I I

I I

I EVENT POINT 0448 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION-HAVE BEEN DETECTED BY AH-127-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-127-CE o TEMPERATURE > 135*F AS SENSED BY AH-127-TS EXISTS IN THE RETURN AIR DUCT A

FROM 95' SWITCH GEAR ROOM Q

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o THIS ALARM WILL RESULT IN THE ACTUATION OF THE FOLLOWING FIRE DAMPERS FD-39 AND FD-41 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO-THE PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE RETURN AIR DUCT FROM 95' SWITCH GEAR ROOM TO AHF-16A/AHF-168.

(

F.EFERENCES:

DRAWING 208-005 SHEETS AH-059, AH-060, AND DRAWING 308846

'\\

. SENSING ELELJNT: AH-127-TS, AH-127-CE, 3AH-127-TS/RR-HV-V AR-401 Rev. 20 Page 72

l-ENCLOSURE 1 g

(Page 71 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 l

l I

I TURBINE BLDG l_

l FIRE ALERT I

I I

I EVENT POINT 0449 INDICATED CONDITION:

o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >135T AH-153-TS AH-523-TS AH-524-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o FIRE DAMPERS FD-52, FD-53, AND FD-54 TRIP o AHF-25A, AHF-258, AND AHF-25C TRIP IF OPERATING OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING SUPPLY FANS o REFER TO AP-880 DISCUSSION:

THIS ALARM INDICATES'THAT THE FIRE DAMPERS FOR AHF-25A/B/C HAVE ACTUATED AHF-25A/B/C SHOULD SHUTDOWN AUTOMATICALLY.

4

REFERENCES:

DRAWING 208-005 SHEET AH-061, AH-70,- DRAWING 308846 SENSING-ELEMENT: AH-153-TS, AH-523-TS, AH-524-TS, AND RELAY 3HBT1A AR-401 Rev. 20 Page 73

ENCLOSURE 1

(

(Page 72-of 183)-

PSA ANNUNCIATOR RESPONSE PSA-X-03 F-03-01 l

l l

1 TURBINE BLDG I

I FIRE ALERT I

I I

I I

I EVENT POINT 0450 INDICATED CONDITION:

o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >I35T AH-155-TS AH-527-TS AH-528-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-26.

AHF-268, AND AHF-26C TRIP IF OPERATING OPERATOR ACTIONS'FOR A VALID ALARM:

NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING o

-SUPPLY FANS o REFER TO AP-880 LISCUSSION:

THIS' ALARM INDICATES.THAT THE FIRE DAMPERS FOR AHF-26A/B/C HAVE f.

ACTUATED. AHF-26A/B/C SHOULD SHUTDOWN AUTOMATICALLY.

REFERENCES:

DRAWING 208-005 SHEET AH-064, AH-70, DRAWING 308846 k)

SENSING ELEMENT: AH-155-TS, AH-527-TS, AH-528-TS, AND RELAY 3HBT2 AR-401 Rev. 20 Page 74

ENCLOSURE 1

(

(Page 73 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 I

I I

I TURBINE BLDG I

I FIRE ALERT I

I I

I EVENT POINT 0451 INDICATED CONDITION:

'o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >135'F

.-AH-154-TS AH-525-TS AH-526-TS j

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-27A, AHF-278, AND AHF-27C TRIP IF OPERATING OPERATOR ACTIONS FOR A VALID ALARM:

NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING s

o SUPPLY FANS o REFER TO AP-880 DISCUSSION:

THIS ALARM INDICATES THAT THE FIRE DAMPERS FOR AHF-27A/B/C HAVE ACTUATED.'- AHF-27A/B/C SHOULD SHUTDOWN AUTOMATICAI LY.

3

REFERENCES:

DRAWING 208-005 SHEET AH-067, AH-70, DRAWING 308846 SENSING ELEMENT: AH-154-TS, AH-525-TS, AH-526-TS, AND RELAY 3HBT3 AR-401 Rev. 20 Page 75 iii.gr il

l-p-

f ENCLOSURE 1

i

-(Page 74 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03 F-03-01 l

I I

I TURBINE BLDG I

I FIRE ALERT l

l l

l l

l i

EVENT POINT 1118 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-723-CE o TROJBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-723-CE OV REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DETECTION OF PRODUCTS OF COMBUSTION WILL TRIP AHF-49 IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS..OR A FIRE IN THE-INSTRUMENT CAL LAB 145' TURBINE DECK.

REFERENCES:

DRAWING.208-005 SHEETS AH-151 AND AH-152

.g,m) :

w/

SENSING ELEMNT: AH-723-CE.

1 AR-401 Rev. 20 Page 76

{

1 1

O DiCLQiELI (Page 75 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i.

AUXBLDO FIRE ALERT i

EVENT POINT 0006 INDICATED CONDITION:

o PENETRATION COOLING DUCT TEMPE O'JRE UP5TREAM OF FD-278 IS >I65'F AS SENSED BY AH-1004-TS

()

REDUNDANT INDICATION WHICH k!LL VERIFY ALARM:

o PENETRATION COOLING FANS AHF-9A/98 TRIP ON INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHF-9A/98 ARE SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION:

THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.

CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE A')PROPRIATE ACTIONS.

AH-1004-TS IS A MANUAL RESET TEMPERATURE SWITCH LOCATED AT INT. BLDG, 95' ELEV NEXT TO THE LOCAL CONTROL STATION FOR AHF 9A AND 9B.

REFERENCES:

DRAWINC 208-005 SHEET AH-056, DRAWING 308849 O

SENSING ELEMENT: AH-1004-TS AR-401 Rev. 20 Page 77

, _ _ _ _ _ - - - - _.- - ~ - -

b ENCLOS9RE 1 O

(

(Page 76 of 183) 1 PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l

-l AUX BLDG i

FIRE ALERT I

EVENT POINT 0380 INDICATED CONDITIbas o RB PURGE SUPPLY DUCT TEMP IS >135T AS SENSED BY AH-23-TS OR PRODUCTS OF COMBUSTION HAVE BEEN SENSFD BY AH-23-CE AND/0R AH-24-CE, OR RELAY 3PSFP HAS ACTUATED o RB PURGE SUPPLY DUCT TEMP IS <70T AS SEN3ED BY AH-645-TS REDUNDANT IN91 CATION WHICH WILL VERIFY ALARM:

o PURCE SUPPLY FANS AHF-6A/6B TRIP o PURGE SUPPLY DAMPER AHV-10 CLOSES ON LOW PURCE SUPPLY FLOW OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o SECURE RB PURCE PER OP-417 IF HIGH TEMP ALARM o REFER TO AP-880. IF HIGH TEMP ALARM o CHECK CORE FLOOD TANK PRESSURE / TEMP, IF LOW TEPP ALARM DISCUSSION:

THIS IS INDICATIVE OF A FIRE IN THE PURCE SUPPLY FAN DISCHARGE DUCT THE TEMPERATURE AND PRODUCT OF COMBUS110N DETECTORS SENSE THE DISCHARGE UPSTREAM OF THE RECIRCULATION DAMPER. THE LOW TEMPERATURE ALARM HAS NO INTERLOCKS ASSOCIATED WITH IT,

REFERENCES:

-DRAWING 208-005 SHEETS AH-020, AND AH-15 DRAWING 308849 SENSING ELEMENT: AH-23-TS, AH-23-CE. AH-24-CE, AH-645-TS, AND RELAY 3PSFP

'AR-401~

Rev. 20 Page 78 L

u--

_ _._ _.._ _ _ -.._...~ _. _ _. _ _

l EfiCLQSEL_1 O,

(Page 77 of 183) 1 PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02

)

i 1

~

r AUX BLDG FIRE ALERT I

EVENT POINT 0387 INDICATED CONDITION:

o RB PURGE EXHAUST DUCT TEMP IS >135'F., SENSED BY AH-295-TS, OR PRODUCTS OF COMBUSTION HAVE PEEN S u'.D BY AH-295-CE, OR RELAY 3PEFP HAS A G UATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o PURGE EXHAUST FANS AHF-7A/78 TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o SECURE THE RB PURCE REFER TO OP-417 o REFER TO AP-880 DISCUSSION:

THIS IS INDICATIVE OF A FIRE IN THE PURGE EXHAUST DISCHARGE DUCT THE TEMPERATURE AND PRODUCT OF COMBUSTION DETECTORS SENSE THE DISCHARGE OF THE FANS-

REFERENCES:

DRAWING 2 e

'

  • SHEETS AH-020, AND AH-15 DRAWING 308849 SENSING ELEMENT: AH-295-CE, AH-295-TS, AND RELAY 3PEFP AR-401-Rev. 20 Page 79

I 1

ENCLOSURE 1 O

(Page 78 of 183) l PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 1

i s

AUX BLDG FIRE ALERT EVENT POINT 0391 i

i INDICATED CONDITION:

1 o TEMPERATURE IS >135*F IN SPENT FUEL AIR HANDLING FAN AHF-8A DISCHARGE DUCT WORK AS SENSED BY AH-314-TS h

REDUNDANTINDICATIONWHICHWILLVERhvALAh?

1 o AHF-8A TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION:

THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL COOLING UNIT DISCHARGE DUCT CONSIDERATION SHOUtD-BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP'IN DETERMINING A COURSE OF ACTION I

REFERENCES:

DRAWING 208-005 SHEETS AH-026,. DRAWING 308849 SENSING ELEMENT: AH-314-TS AR-401 Rev. 20 Page 80

ENCLOSURE 1 (Page 79 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i

AUXBLDG FIRE ALERT EVENT POINT 0394 INDICATED CONDITION:

o TEMPERATURE IS >135'F IN SPENT FUEL AIR HANDLING FAN AHF-8B DISCHARGE DUCT WORK AS SENSED BY AH-409-TS O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-8B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880

(

DISCUSSION:

i THIS IS INDICATIVE OF A' FIRE IN THE SPENT FUEL COOLING UNIT DISCHARGE-s L

DUCT CONSIDERATION SHOULD BE GIVEN TO. CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION l

REFERENCES:

DRAWING 208-005-SHEETS AH-027 DRAWING 308849 SENSING ELEMENT: AH-409-TS

~

AR-401-Rev, 20 Page 81

1 O

[RCLOSURE 1 (Page 80 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0403 INDICATED CONDITION:

o TEMPERATURE IS >135'F IN SPENT FUEL AREA AIR HANDLING FAN AHF-10 DISCHARGE DUCT WORK AS SENSED BY AH-377-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-10 TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE THE CAUSE OF THE ALARM o REFER TO AP-880 OISCUSSION:

THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL FLOOR AIR HANDLING UNIT DISCHARGE DUCT CONSIDERATION 3HOULD BE GIVEN TO CONSULTING THE FIRE PLANS:FOR ADDITIONAL HF.Lt' IN DETERMINING A COURSE OF ACTION

REFERENCES:

DRAWING 208-005 SHEETS AH-044 DRAWING 308849 k)

SENSING ELEMENT: AH-377-TS-

-AR-401-Rev. 20 Page 82

i I

i ENCLOSURE 1 O

(Page 81 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0410 INDICATED CONDITION:

o TEMPERATURE IS >135T IN AUXILIARY BUILDING SUPPLY FAN DISCHARGE DUCT r

WORK AS SENSED BY AH-318-T5 REDUNDANT INDICATION WHICH WILL \\ERIFY ALARM:

o AHF-11A/118 FANS TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION:

THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING SUPPLY FANS DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE-PLANS FOR' ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION

REFERENCES:

- DRAWING 208-005 SHCETS AH-045 DRAWING 308849 Oh SENSING ELEMENT: AH-318-TS i

AR-dO1 Rev. 20 Page 83

l O

ENCLOSURE 1 (Page 82 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX SLDG FIRE ALERT EVENT POINT 0416 INDICATED CONDITION:

o TEMPERATURE IS >I35F IN AUXILIARY BUILDING RECIRC FAN SUCTION DUCT WORK AS SENSED BY AH-375-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o - AHF-13 TRIPS 4

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION:

THIS 1 INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING RECIRC FAN

- DISCHA;;GE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL-HELP IN DETERMINING A COURSE OF ACTION

REFERENCES:

DRAWING 208-005 SHEETS AH-048 DRAWING 308849 QQ SENSING ELEMENT:.AH-375-TS

- AR-401:

Rev. 20 Page 84

~

1 l

ENCLOSURE 1 (Page 83 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0420 INDICATED CONDITION:

o TEMPERATURE IS >135'F IN AUXILIARY BUILDING EXHAUST DUCT WORK AS SENSED BY AH-354-TS

[

REDUNDANT INDICATION WHICH WILL-VERIFY ALARM:

AUXILIARY BUILDING EXHAUST FANS AHF-14A, AHF-148, AHF-14C, & AHF-14D o

TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION.

THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING EXHAUST DISCHARGE DUCT. CONSIDERATION SHOULD BE GIVEN-T0 CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION

REFERENCES:

DRAWING 208-005 SHEETS AH-001, AND AH-005, DRAWING 308849 SENSING ELEMENT: AH-354-TS LAR-401-Rev. 20--

Page 85

~

1

f' O

ENCLOSURE 1 (Page 84 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUXBLDG FIRE ALERT EVENT POINT 0431 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETEGED BY AH-156-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-156-CE o TEMPERATURE > 135'F AS SENSED BY AH-156-TS EXISTS AT THE 95' LEVEL INTERMEDIATE BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALArtM:

o HIGH TEMPERATURE WILL RESULT IN THE TRIP OF AHF-24A/B IF RUNNING o HIGH TEMPERATURE WILL RESULT IN THE ACfUATION OF FD-42, AND FD-43 OPERATOR AGIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o-REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.

REFERENCES:

DRAWING 208-005 SHEETS AH-51, AND AH-55. DRAWING 308846 SENSING ELEMENT: AH-156-CE, AH-156-TS, RELAY 3AH-156-TS/RRIA AR-401~

Rev. 20 Page 86

ENCLOS6*L_1 2

(Page 85 of 183) l PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUXBLDG FIRE ALERT EVENT POINT 0433 1

INDICATED CONDITION:

o TEMPERATURE > 135'F AS SENSED BY AH-157-TS EXISTS AT THE 95' LEVEL INTERMEDIATE BUILDING l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42, AND FD-43 o

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THE IS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE

-95' INTERMEDIATE BUILDING,

REFERENCES:

DRAWING 208-005 SHEETS AH-51, AND AH-55 DRAWING 308846

(,)

SENSING ELEMENT: AH-157-TS,

-AR-401.

Rev. 20 Page 87 t-P T

-iA v er-y

'm-s eiw-i s=

tf97-T-t bP-teTt TW'b-w*-

'D-.'

N

-9W

'f va7-e' w

(x ENCLOSURE 1 h

(Page 86 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l

l AUX BLDG FIRE ALERT EVENT POINT 0435 INDICATED CONDITION:

o PENETRATION COOLING SUPPLY AIR DUCT TEMPERATURE UPSTREAM OF FD-32 IS

>135'F AS SENSED BY AH-737-TS. OR AH-737-TS TROUBLE CIRCUIT HAS ACTUATED

'l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o FD-32 FIRE DAMPER CLOSES o LOCAL TROUBLE ALARM ON AH-737-TS OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY FD-32 CLOSED o REFER TO AP-880 DISCUSSION:

THIS IS~ INDICATIVE OF A HICH TEMPERATURE CONDITION IN THE TURBINE BUILDING ADJACENT TO THE FAN INTAKE, OR A PROBLEM WITH THE DETECTOR, Oc

REFERENCES:

- DRAWING 208-005 SHEET AH-056, DRAWING 308849 t

SENSING ELEMENT: AH-737-TS, AH-737-TS TROUBLE CIRCUIT AR-401 Rev.-20 Page 88 M

9 gy war-ay yv rnby+-- r r vryg--e-- + - - - ~

gg-'--

=T w

y

Og ENCLOSURE _1

)

(Page 87 of 183) l 4

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT r

a EVENT POINT 0437 INDICATED CONDITION:

o PENETRATION COOLING SUPPLY AIR DUCT TEMPERATURE UPSTREAM OF FD-33 IS

>I35*F AS SENSED BY AH-738-TS. OR AH-738-TS TROUBLE CIRCUIT HAS ACTUATED l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o FD-33 FIRE DAMPER CLOSES s

o LOCAL TROUBLE ALARM ON AH-738-TS OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY.FD-33 CLOSED DISCUSSION:

'THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE OUTSIDE AIR INTAKE, OR OF A PROBLEM WITH THE DETECTOR

REFERENCES:

DRAWING'208-005 SHEET AH-057, DRAWING 308849 SENSING ELEMENT:- AH-738-TS-AND AH-38-TS TROUBLE

~AR-401L Rev. 20 Page 89.

^

~

l p

ENCLOSURE 1 (Page 88 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX 8LDG FIRE ALERT I

EVENT POINT 0439 INDICATED CONDITION:

o PENETRATION COOLING FAN DISCHARCE DUCT TEMPERATURE IS >IIO'F AS SENSED BY AH-305-TS REDUNDANT INDICATION WHIR.1 WILL VERIFY ALARM:

o LOCAL TROUBLE ALARM ON AH-305-TS OPERATOR ACTIONS FOR A VALID ALARM:

o-ENSURE CHILL WATER IS SUPPLIED TO THE OPERATING PENETRATION COOLER o INVESTIGATE THE CAUSE OF THE hICH TEMPERATURE ALARM o REFER TO AP-880

-l

.o ENSURE THAT CHV-233 THROUGH CHV-236 HAVE NOT CLOSED.

r?SCUSSION:

THIS IS INDICATIVE OF A HICH TEMPERATURE CONDITION IN THE DISCHARGE OF THE PENETRATION COOLING FANS, OR OF A PROBLEM WITH THE DETECTOR.

LOSS OF POWER, OR FAILURE OF CHV-233 THROUGH CHV-236, CAN RESULT IN THIS ALARM.

REFERENCES:

/"~N

. DRAWING 208-005-SHEET AH-056. DRAWING 308849 SENSING ELEMENT:. AH 305-TS-

'AR-401 Rev. 20 Page 90-

=. _ - -.. -

I i

i i

ENCLOSURE 1 O

(Page 89 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUXBLDG FIRE ALERT i

d EVENT POINT 0513 i

. INDICATED CONDITION:

o TEMPERATURE > 135'F AS SENSED BY AH-132-TS EXISTS IN CLEAN MACHINE SHOP AIR HANDLING UNIT AHU-2 DISCHARGE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN A TRIP OF AHU-2 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

-THIS CONDITION IS INDICATIVE OF A~ FIRE OR A HIGH TEMPERATURE IN THE DISCHARGE DUCT OF AHU-2.

REFERENCES:

DRAWING 208-005 SHEETS AH-094,' DRAWING 308846'

-h--

SENSING ELEMENT: AH-132-TS Q

-AR-401:

Rev. 20 Page 91

. _ _ = _

m.__

l ENCLOSURE 1 O

(Page 90 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-M-02 F-03-02 r

I j

AUX BLDG l

FIRE ALERT EVENT POINT 0514 i

INDICATED CONDITION:

3 o TEMPERATURE > 135'F AS SENSED BY AH-I65-TS EXISTS IN HOT MACHINE SHOP AIR HANDLING UNIT AHU-3 DISCHARGE 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN A TRIP OF AHU-3 OPERATOR ACTIONS FOR A VALID ALARM:

i o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE DISCHARGE DUCT OF AHU-3.

d

REFERENCES:

DRAW 7NG 208-005 SHEETS AH-095, DRAWING 308846 SENSING ELEMENT: AH-165-TS AR-401-Rev. 20

.Page 92 1.

... : L..

.i ENCLOSURE 1 l

O (Page 91 of 183) 1 PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l

I DlESEL ROOM i

FIRE ALERT EVENT POINT 0460 j

INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-364-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-364-CE REDUNDANT. INDICATION-WHICH WILL VERIFY ALARM:

o AN ALARM ON AH-364-CE WILL ACTUATE FD-36 AND FD-37 s

OPERATOR ACTIONS FOR A VALID ALARM:

.o DEENERGIZE AHF-28A LOCALLY OR VIA ACDP-50 BREAKER 13 o -REFER TO THE PRE FIRE PLAN o REFER TO AP-889 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE-FIRE DETECTION CIRCUITS, OR A FIRE IN THE ECDG-1A-ROOM,

REFERENCES:

DRAWING 208-005 AH-073, AH-076,- AND DRAWING 308349 SENSING ELEMENT: AH-364-CE, 3/M-364-CE/ RELAY AR-401 Rev. 20-Page 93

m..,__ - __ _ _ _- _ _ _ _

r l

Ox ENCLOSURE 1 i

(Page 92 of 183)_

PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 DIESEL ROOM FIRE ALERT '

[

EVENT POINT 0465

.1 j

INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-374-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-374-CE bQ

~

REDUNDANT INDICATION WHICH WILL VERIFY ALARM o AN ALARM ON AH-374-CE WILL ACTUATE FD-34 AND FD-35 OPERATOR ACTIONS FOR A VALID ALARM:

o DEENERGIZE AHF-288 LOCALLY OR VIA ACDP-50 BREAKER 14 o REFER TO THE,CR3: PRE FIRE PLAN o REFER TO AP-880-DISCUSSION:

.THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR' A FIRE IN THE ECDG-18 ROOM,

REFERENCES:

DRAWING 208-005. SHEETS AH-073. AH-079, AND DRAWING 308849 dj SENSING ELEMENT: AH-374-CE, 3AH-374-CE/ RELAY AR-401 Rev. 20 Page_94

ENCLOSURE 1 (Page 93 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0481 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-33-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-33-CE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AN ALARM ON AH '

CE WILL ALLOW THE CONTROL COMPLEX VENTILATION SYSTEM TO BE PLACED IN A SMOKE REMOVAL MODE OF OPERATION OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE COMMON RETURN DUCT DOWNSTREAM OF AHF-19A/B

REFERENCES:

DRAWING 208-005 SHEETS AH-090, AH-079, AND DRAWING 308847 SENSING ELEMENT: AH-33-CE. 3AH-33-CE/ RELAY AR-401

-Rev. 20 Page 95 t

(o)

MCLQiURE_l (Page 94 of 183) v PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0492 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-529-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-529-CE o TEMPERATURE > 135*F AS SENSED BY AH-529-T5 EX75TS AT THE 124' LEVEL OF em THE CONTROL COMPLEX L_j' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-13 AND FD-84 OPERATOR ACTIONS FOR A VAilD ALARM:

o REFER TO THE CR3 FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX

REFERENCES:

DRAWING 208-005 SHEETS AH-101, /H-106, AND DRAWING 308847

^

'1 SENSING ELEMENT: AH-529-T5 AH-529-CE, 3AH-529 TS/ RELAY Ad-401 Rev. 20 Page 96 l

ENCLOSURE 1 O

(Page 95 of 383)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT f

EVENT POINT 0494 i

INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-214-CE o TROUBLE HAS BEEi' DETECTED IN THE CIRCUITS FOR AH-214-CE o TEMPERATURE > 135*F AS SENSED BY AH-214-TS EXISTS AT THE 124' LEVEL OF THE CONTROL COMPLEX. ES 480V "A" SWITCHCEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HICH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-4 AND FD-16 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:-

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE -DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX

REFERENCES:

DRAWING 208-005 SHEETS AH-102, AH-107.-AND DRAWING 308847 i

SENSING ELEMENT:

'AH-214 TS AH 214 CE, 3AH-214-TS/ RELAY AR-401 Rev. 20-Page_.97

=- _

en w

~ -, -

,,n n

+, - s x

m n

e--

ENCLOSURE 1 (Page 96 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0495 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-212-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-212-CE o TEMPERATURE > 135'F AS SENSED BY AH-212-TS EXISTS AT THE 124' LEVEL OF THE CONTROL COMPLEX. ES 480V "B" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-2 AND FD-14 OPERATOR AGIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX.

REFERENCES:

DRAWING 208-005 SHEETS AH-102, AH-106, AND DRAWING 308847 N '

}ENSING ELEMENT: AH-212-TS AH-212-CE, 3AH-212-TS/ RELAY AR-401' Rev. 20 Page 98

ENCLOSURE 1 (Page 97 of 153)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 i

CNTRL COMPLEX FIRE ALERT EVENT POINT 0498 INDICATED CONDITION:

o FRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-216-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-216-CE o TEMPERATURE > 135T AS SENSED BY AH-216-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX. ES 4160V "A" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATI'N OF FD-6 AND FD-18 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF ThE CONTROL COMPLEX.

REFERENCES:

DRAWING 208-005 SHEETS AH-103, AH-107, AND DRAWING 308847 SENSING ELEMENT: AH-216-TS AH-216-CE, 3AH-216-TS/ RELAY AR-401 Rev. 20 Page.99

3 ENCLOSURE 1 (Page 98 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 i

I

(

I CNTRL COMPLEX l

FIRE ALERT i

b EVENT POINT 0499 4

I'JDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-215-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-215-CE o TEMPERATURE > 135T AS SENSED BY AH-215-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX. ES 4160V "B" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-5 AND FD-17 3

4 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO ~4E CR3 PRE FIRE PLAN o REFER TC, y /-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETICTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX.

REFERENCES:

DRAWING 208-005 SHEETS AH-103, AH-107, AND DRAWING 308847 SENSING ELEMENT: AH-215-TS AH-215-CE, 3AH-215-TS/ RELAY

'AR-401 Rev.-20 Page 100

t fELQSURE 1 O

(Page 99 of 183) k PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 l

i l

CNTRL COMPLEX FIRE ALERT 4

EVENT POINT 0500 INDICATED CONDITION:

i o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-220-CE o TROUBLE HAS BEEN DETEGED IN THE CIRCUITS FOR AH-220-CE o TEMPERATURE > 135T AS SENSED BY AH-220-TS EXISTS IN "A" BATTERY CHARCER ROOM REDUNDART INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42 AND FD-43 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 OISCUSSION:-

THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE. FIRE DETECTION

- CIRCUITS, A FIRE, OR A HIGH TEMPEPATURE IN THE ROOM.

REFERENCES:

DRAWING 208-005 SHEET AH-IO4 SENSING ELEMENT:. AH 220-TS, AH 220-CE t

AR'-401 Rev. 20:

Page 101

~

--Vue e--

m es-w w

y--,

tp mey o.v+i g-e,'

-9g r'-+-supre 5 eemayur

. - - pe -p us-w M-y

i O

ENCLOSURE 1 (Page 100 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04

{

l CNTRL COMPLEX FIRE ALERT 1

EVENT POINT 0501 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETEGED BY AH-217-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-217-CE o TEMPERATURE > 135'F AS SENSED BY AH-217-TS EXISTS IN "B" BATTERY CHARGER ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HICH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-19 OPERATOR-ACTIONS FOR A VALID kARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS,~A FIRE OR A HIGH TEMPERATURE IN THE ROOM,

REFERENCES:

.DRAWINC 208-005 SHEETS AH-103, AH-109, AND DRAWING 308847 r

SENSING ELEMENT: AH-217-TS,'AH-217-CE AR-401; Rev. 20 Page 102

.a

f O

ENCLOSURE 1 (Page 101 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 1

CNTRL COMPLCX FIRE ALERT 1-EVENT POINT 0502 i

INDICA

  • PO CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-219-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-219-CE o TEMPERATURE > 135T AS SENSED BY AH-219-TS EXISTS IN "A" BATTERY ROOM O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-9 AND FD-21 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN

o REFER TO AP-880 DISCUSSION:.

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS..A FIRE, OR A HIGH TEMPERATURE IN THE ROOM.

REFERENCES:

DRAWING 208-005 SHEETS AH-104 -AH-108, DRAWING 308847 V -

SENSING ELEMENT:

AH-219-CE, AH-219-TS r

?

AR-401:

Rev.'20-Page 103

i

)

ENCLOSURE 1 Os (Page 102 of 183)

PSA ANNUNCIATOR RESPONSE lPSA-X-03-04 F-03-04 4

CNTRL COMPLEX FIRE ALERT EVENT POINT 0503 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION H,WE BE !N DETECTED BY AH-218-CE o TROUBLE HAS BEEN DETEC1ED IN THE CIRCUITS FOR AH-218-CE o TEMPERATURE > 135'F AS SENSED BY AH-218-TS EXISTS IN THE "B" BATTERY ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-220 AND FD-222 OPERATOR ACTIONS FOR A VALID ALARM:

4 o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS-CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION

. CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.

REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-005 SHEETS AH-103, AH-108 AND DRAWING 308847 f)

Lj SENSING ELEMENT: AH-218-CE, AH-218-TS AR-401 Rev. 20 Page 104

l l

, ~ ~

ENCLOSURE 1 (x)

(Fage 103 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04

)

i

)

CNTRL COMPLEX FIRE ALERT t

EVENT POINT 0504 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-222-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-222-CE o TEMPERATURE > 135*F AS SENSED BY AH-222-TS EXISTS IN THE "A" INVERTER

/

)

ROOM w)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-12 AND FD-24 OPERATOR ACTIONS FOR A VALID ALAR 9:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDI';10N IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.

REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCEE:

DRAWING 208-005 SHEETS AH-104, AH-109 AND DRAWING 308847

)

SENSING ELEMEWT: AH-222-CE. AH-222-TS j-AR-401 Rev. 20 Page 105

f ENCLOSURE 1 N

(Page 104 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0505 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-221-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-221-CE o TEMPERATURE > 135'F AS SENSED BY AH-221-TS EXISTS IN THE "B" INVERTER REDUNDANT INDICATION WHICH HELL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-11 AND FD-23 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS,"A FIRE OR:A HIGH TEMPERATURE IN THE ROOM, REFER TO THE CR3 FIRE PROTECTION -PLAN FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-005 SHEETS AH-104, AH-109 AND DRAWING 308847 SENSING ELEMENT: AH-221-CE, AH-221-TS

( f AR-401

_Rev.'20 Page 106

_1_______

Q ERCLOSURE 1 h

(Page 105 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPl.EX ClRE ALERT l

EVENT POINT 0506 INDICATED CONDITION:

k o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-235-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-235-CE o TEMPERATURE > 135'F AS SENSED BY AH-235-TS EXISTS IN THE CONTROL COMPLEX STAIR WELL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-25 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE id3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

e THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FVE OR A HIGH TEMPERATURE IN THE ROOM.

REFER TO THL

_M FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS..

REFERENCES:

DRAWING 208-005 SHEETS AH-105, AH-109 AND DRAWING 308847

. A.

['vl SENSli,J. ELEMENT: AH-235-CE, AH-z35-TS AR-401 Rev. 20 Page 107

ENCLOSURE _1 (Page 106 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 I

CNTRL COMPLEX FIRE ALERT

- EVENT POINT 0507 INDICATED CONDITION:

-o PRODUCTS OF-COMBl'STION HAVE-BEEN DETECTED BY AH-236-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCl ~; FOR AH-236-CE o TEMPERATURE > 135'F AS-SENSED BY AH-236-TS FXISTS AT THE 108' LEVEL OF Q

THE CONTROL COMPLEX u

4 REDUNDANT INDICATION WHICH WILL VERIFY-ALARM:

o HICH TEMPERATURE WILL RESULT-IN THE ACTUATION OF FD-26 AND FD-27 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN

.c REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE. FIRE DETECTION CIRCUITS, OR' A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX

REFERENCES:

- DRAWING 208-005 SHEETS AH-105, AH-109, AND DRAWING 308847 SENSING EL MENT: AH-236-TS AH-236-CE, 3AH-236-TS/ RELAY-

AR-401 Rev. 20 Page 108

O.

ENCLOSURE 1 (rage 107 of 183) l PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 1532 INDICATED CONDITION:

o TEMPERATURE > 135'F AS SENSED BY AH-534-TS EXISTS IN THE CONTROL COMPLEX MAIN AIR HANDLING SUPPLY DUCT AT 145' ELEVATION O

REDUNDANT INDICATION WhICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-56 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF A FIRE IN THE MAIN SUPPLY DUCT OF THE CONTROL COMPLEX.

REFERENCES:

' DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-534-TS, 3AH-534-TS/RR-HV-AU AR-401 Rev. 20 Page 109

O ENCLGSURE 1 (Page 108 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 1533 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-531-CE o TROUBLE HAS BEEN DETEGED IN THE CIRCUITS FOR AH-531-CE O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:-

o PRODUGS OF '.0MBUSTION DETEGION WILL RESULT IN THE ACTUATION OF FD-51 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER T0'THE CR3 PRE FIRr N

o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR~A FIRE-IN THE OUTSIDE-AIR INTAKE OF THE CONTROL COMPLEX.

REFERENCES:

DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 k.

SENSING ELEMENT: AH-531-CE

AR-401' Rev. 20 Page 110

ENCLOSURE 1 V

(Page 109 of 183)

PSA ANNUNCIATOR-RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT i

EVENT POINT 1534 INDICATED CONDITION:

o PRODUCT 5 OF COMBUSTION HAVE BEEN DETECTED BY AH-535-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-535-CE o TEMPERATURE > 135'F AS SENSED BY AH-535-TS EXISTS IN THE CONTROL COMPLEX MAIN SUPPLY DUCT 95' ELEVATION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-55 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 a

DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE MAIN SUPPLY DUCT OF THE CONTROL COMPLEX.

REFERENCES:

DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-535-TS AH-535-CE, 3AH-535-TS/ RELAY AR-401-Rev. 20 Page 111

l O-ENCLOSURE 1 (Page 110 of_183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 s

CNTRL COMPLEX FIRE ALERT EVENT POINT 1535 INDICATED CONDITION:

S e ' *ERATURE > 135'F AS SENSED BY AH-533-TS EXISTS IN THE CONTROL COMPLEX

/,IN RETURN AIR DUCT AT 145' ELEVATION OG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-57 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:

THIS CONDITION IS INDICATIVE OF A FIRE IN.THE RETURN AIR DUCT OF THE CONTROL COMPLEX.

REFERENCES:

DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWINO 308847 SENSING ELEMENT: AH-533-TS. 3AH-533-TS/RR-HV-AT AR-401 Rev. 20 Page 112

ENCLOSURE 1

)

(Page 111 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 1536 INDICATED CONDITION:

o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-211-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-211-CE o TEMPERATURE > 135'F AS SENSED BY AH-211-TS EXISTS AT THE 134' LEVEL OF THE CONTROL COMPLEX REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF THE FOLLOWING:

FD-45, FD-46, FD-47 FD-81, FD-82, AND FD-83 OPERATOR ACTIONS FOR A VALID ALARM:

. o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 4

DISCUSSION:

THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION-CIRCUITS, OR A FIRE IN THE 134' ELEVATION OF THE CONTROL COMPLEX IN THE

' CABLE-SPREADING ROOM.

REFERENCES:

DRAWING 208-005 SHEETS AH-105, AH-107, AND DRAWING 308847 l

v SENSING ELEMENT: AH-211-TS AH-211-CE, 3AH-211-TS/ RELAY AR-401 Rev. 20 Page 113 l

O ENCLOSURE 1.

-(Page 112 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-05

-F-03-05 RUSTY BLDG FIRE ALERT EVENT POINT 0427

. INDICATED' CONDITION:.

o DUCT -TEMPERATURE AT DISCHARGE'0F AHF-46 IS > 125'F AS SENSED BY AH-667-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-46 TRIPS DUE TO INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHF-46 IS SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION:

THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.

' CONSIDERATION SHOULD BE GIVtN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS.

'AHF-46 IS THE RUSTY BUILDING'RECIRC FAN.

V['

\\~

REFERENCES:

DRAWING 208-005 SHEET'AH-142 SENSING ELEMENT: AH-667-TS

'AR-401-Rev. 20 Page 114-

O<

-ENCLOSURE 1 (Page 113 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-05 F-03-05 RUSTY BLDG

,RE ALERT EVENT POINT 0512 INDICATED CONDITION:

o DUCT TEMPERATURE AT DISCHARGE OF AHU-7 IS > I25*F AS SENSED BY AH-670-TS REDUNDANT INDICATION WHICn WILL VERIFY ALARM:

o AHU-7 TRIPS DUE TO INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHU-7 IS SHUTDOWN o INVESTIGATE CAUSE OF ALARM i

DISCUSSION:

THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.

CONSIDERATION SHOULD BE CIVEN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS.

AHU-7 IS THE RUSTY BUILDING AIR CONDITIONING UNIT.

f

REFERENCES:

DRAWING 208-005 SHEET AH-144 SENSING ELEMENT: -AH-670-TS AR-401L Rev.'20 Page 115

f" ENCLOSURE 1

(Page 114 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-03-06 F-03-06 I

FIRE PUMP HOUSE FIRE ALERT EVENT POINT 0455 INDICATED CONDITION:

o PRODUCTS OF-COMBUSTION HAVE BEEN DETECTED BY AH-386-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUIT'. FOR AH-386-CE t

-\\ d REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i OPERATOR ACTIONS FOR A VALIO ALARM:

o NOTIFY TURBINE BUILDING OPERATOR TO INVESTICATE THE FIRE-PUMP HOUSE.

DISCUSSION:

7-

REFERENCES:

DRAWING 208-005' SHEET AH-072-C.

SENSING ELEMENT: AH-386-CE

.AR-401 Rev. 20 Page.116

t

[-

ENCLOSUEE_1 v-(Page-115 of-183)-

PSA ANNUNCIATOR RESPONSE =

PSA-X-03-07 F-03-07 l

- FIRE SYSTEM TROUBLE EVENT POINT 0197 INDICATED CONDITION:

1 o FIRE SERVICE PANEL IN THE CONTROL ROOM HAS AN UNACKNOWLEDGED OR UNRESET ALARM i

i\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

~

o ALARM ON THE FIRE SERVICE PANEL OR ONE OF THE PYROTRONICS PANELS OPERATOR ACTIONS FOR A VALID ALARM:

o IMMEDIATE INVESTIGATION OF ALARM CAUSE SHOULD BE INITIATED DISCUSSION:

' REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.

-N REFERENCESi -DRAWING 208-031 SHEET FS-21

)--

'V'-

SENSING ELEMENT:

4 AR-401' Rev.~ 20-Page-117

I l

O ENCLOSURE 1 (Page 116 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-01 F-04-01 I

I REACTOR BLDG I

l PURGE FAN TRIP I

I I

I EVENT POINT 0384 INDICATED CONDITION:

o AHF-7A MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION O

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-7A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE RB PURGE o REFER TO OP-417 DISCUSSION:

TH7.5 CONDITION MAY BE CAUSED BY ACTUATION OF A FIRE ALERT IN THE DUCT INDICATED BY EVENT POINT 0387, OR AN FSV-114 DELUGE VALVE ACTUATION

REFERENCES:

DRAWING 208-005 SHEETS AH-022, AH-015

' \\M SENSING ELEMENT: CS/SC, CS/0, 42/49B RELAY

'AR-401.

Rev. 20 Page 118

I

{

ENCLOSURE 1 (Page 117 of 183)-

PSA ANNUNCIATOR RESPONSE PSA-X-04-01 F-04-01 l

l REACTOR BLDG I

I PURGE FAN I

TRIP I

I I

I EVENT POINT 0385 INDICATED CONDITION:

o AHF-78 MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-78 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE RB PURCE o REFER TO OP-417

' DISCUSSION:

THIS CONDITION MAY BE CAUSED BY ACTUATION OF A FIRE ALERT IN THE DUCT INDICATED'BY EVENT POINT 0387, OR AN FSV-114 DELUGE VALVE ACTUATION

REFERENCES:

DRAWINC 208-005 SHEETS AH-023, AH-015

'M SENSING ELEMENT: CS/SC, CS/0, 42/498 RELAY AR-401 Rev. 20 Page 119 m

f ENCLOSURE 1 (Page 118 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-02 F-04-02

^

I' d

AH FLTR 1 A/B DIFF PRESS HIGH EVENT POINT 0497 INDICATED CONDITION:

o DIFFERENTIAL PRESS ACROSS AHFL-1A/IB IS > 5.2 "H20AS SENSED BY AH-586A-DPS, OR AH-5868-DPS AU REDUNDANr INDICATION WHICH WILL VERIFY ALARM:-

o HIGH FLOW INDICATED O'. e u FIR o LOCAL DIFFERENTIAL Fih -

INDICATIONS ON AH-586-DPI, LOCALLY NORTH / SOUTH END (AHFL A, FILTERS D, E, & F) (AHFL B FILTERS A, B & C)

OPERATOR ACTIONS FOR A VALID ALARM:

o REDUCE RB PURCE FLOW RATE o REFER TO OP-417 o VERIFY ROUGHING FILTER OP < 0.9" H,0 LOCALLY (FILTERS A/F) o VERIFY HEPA FILTER DP < 3.0" H,0 LOCALLY (FILTERS B/E)

DISCUSSION:

.THIS CONDITION'IS INDICATIVE OF EXCESSIVE FLOW THROUGH THE PURGE EXHAUST FILTERS OR A DIRTY FILTER CONDITION

REFERENCES:

. DRAWING 308848

' SENSING ELEMENT: AH-586A-DPS, AH-5868-DPS AR-401-Rev. 20 Page 120

l

(

f~k ENCLOSURE 1 (f

(Page 119 of-183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP q

EVENT POINT 0360 INDICATED CONDITION:

o AHF-2A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION

~t n

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O GREEN LIGHT ON WITH A RED FLAG ON AHF-2A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP REACTOR CAVITY COOLING TO "B" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 i

DISCUSSION:

A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFEGS ON THE RELIABILITY 0F THE NUCLEAR INSTRUMENTATION.

f]

REFERENCES:

DRAWINGS 208-005-AH-031, 308848 SENSING ELEMENT: CS/SC, CS/0, 428 RELAY

' AR'-401' Rev. 20 Page 121 1

-C-.

ENCLOSURE 1 (Page 120 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04 F-04-03 REACTOR BLDG MISC CLG FANS TRIP t

EVENT POINT 0362 INDICATED CONDITION:

o AHF-2B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION O

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-28 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP REACTOR CAVITY COOLING TO "A" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 i

DISCUSSION:

A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION, p

REFERENCES:

DRAWINGS 208-005-AH-033, 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY AR-401 Rev. 20 Page 122

. _.. ~

ENCLOSURE 1 O

(Page 121 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 e

R%CTOR BLDG MISC CLG FANS TRIP -

EVENT POINT 0365 INDICATED CONDITION:

o AHF-3A MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START

~

-POSITION bV REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAC ON AHF-3A CONTROL STATION OPERATOR ACTIONS FOR A VALID-ALARM:

o ENSURE AHF-3B IS OPERATING DISCUSSION: IF AHF-3A TRIPS, THERE IS NO IMPACT ON RMA-6

REFERENCES:

DRAWINGS 208-005-All-036, 308848 tO:.

SENSING ELEMENT: CS/SC, CS/0, 42B RELAY AR-401 Rev. 20 Page 123

ENCLOSURE 1 (Page 122 of 183)

PSA ANNUNCIATOR RESPONSE lPSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP I

EVENT POINT 0368 INDICATED CONDITION:

o AHF-3B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION

,O -

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-38 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHF-3A IS OPERATING o TRANSFER RMA-6 SUCTION TO RB ATMOSPHERE, REFER TO OP-417 DISCUSSION:

RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE VIA EITHER THE DUCT OF

-_AHF-38.QB THE R.B. ATMOSPHERE. THE TRANSFER OF THE SAMPLE POINT PER OP-417 IS A MANUAL OPERATION. REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

(

REFERENCES:

DRAWINGS 208-005-AH-037 SENSING ELEMENT:

428 RELAY AR-401 Rev. 20 Page 124

g 1

('s ENCLOSURE 1

-()

(Page 123 of 183)-

PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP EVENT POINT 0371 INDICATED CONDITION:

o AHF-4A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-4A CONTROL STATION N-OPER4 TOR ACTIONS FOR A VALID ALARM:

o START AHF-4B o REFER TO OP-417 DISCUSSION:

f]:

REFERENCES:

DRAWINGS 208-005-AH-038, 308848 SENSING ELEMENT: CS/SC, CS/0,-42B RELAY AR-401 Rev. 20 Page 125

~

p ENCLOSURE 1 g

(Page 124 of 183)

~PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03

~

REACTOR BLDG MISC CLG FANS TRIP EVENT POINT 0373 INDICATED CONDITION:

o AHF-4B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-4B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-4A o REFER TO OP-417 DISCUSSION:

/'N-

REFERENCES:

DRAWINGS 208-005-AH-040, 308848 i-

d SENSING-ELEMENT: CS/SC CS/0. 428 RELAY AR-401 Rev. 20 Page 126-

'(

O ENCLC JRE_.1 (Page 125 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP EVENT POINT 0378 INDICATED CONDITION:

o AHF-6A MOTOR IS NOT ENERCIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDlCATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-6A CONTROL STATION o LOSS OF P.B PURGE FLOW AS READ ON AH-32-FIR OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-6B o REESTABLISH RB PURGE IF REQUIRED

- o REFER TO OP-417 DISCUSSION:

ONLY ONE PURGE SUPPLY FAN IS REQUIRED FOR ESTABLISHING AN RB PURGE, SOME 0F THE THINGS THAT WILL CAUSE THE PURGE SUPPLY FAN TO TRIP ARE A LOSS OF EITHER OF THE PURGE EXHAUST FANS AHF-7A/AHF-78, ACTUATION OF FIRE ALERT EVENT. POINT'0380

REFERENCES:

DRAWINGS 208-005 SHEETS AH-015, AH-20, DRAWING 308848 Y

. SENSING ELEMENT: CS/SC, CS/0, 428 RELAY

\\,f AR-401

-Rev. 20 Page 127

i' l

ENCLOSURE 1 i

(Page 126 of 183)

PSA-ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLCG 4

MISC CLG FANS TRIP EVENT POINT 0379 INDICATED CONDITION:

o AHF-6B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-6B CONTROL STATION o LOSS OF RB PURGE FLOW AS READ ON AH-32-FIR OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-6A o REESTABLISH RB PURGE IF REQUIRED-o REFER TO OP-417 DISCUSSION:

ONLY ONE PURGE SUPPLY FAN IS REQUIRED FOR ESTABLISHING AN RB PURGE, SOME OF THE THINGS THAT WILL CAUSE THE PURGE SUPPLY FAN TO TRIP ARE A LOSS OF EITHER OF THE PURGE EXHAUST FANS AHF-7A/AHF-78, ACTUATION OF FIRE ALERT EVENT POINT 0380

REFERENCES:

DRAWINGS 208-005 SHEETS AH-015, AH-21, DRAWING 308848 D-SENSING ELEMENT: CS/SC, C5/0, 42B RELAY

[O.

AR-401 Rev. 20 Page 128

O, ENCLOSURE 1 (Page 127 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 REACTOR BLDG MISC AIR FLOW LOW f

EVENT POINT 0364 INDICATED CONDITION:

o AHF-2A AND/OR AHF-28 CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFF.

PRESS. <0.20" H,0 EXISTS AS SENSED BY AH-10-DPS AND/OR AH-532-DPS REDUNDJ,NT INDICATION WHICH WILL VERIFY ALARM:

o CLOSED INDICATION OF AHD-IA o CLOSED INDICATION ON AND-1B OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP REACTOR CAVITY COOLING PER OP-417 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 4

DISCUSSION:

.h A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY COULD HAVE ADVERSE

~

EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.

IF FLOW CANNOT BE RESTORED THEN CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE~ PLANT.

REFERENCES:

DRAWINGS 208-005 SHEET AH-031, DRAWING 308848 p);

8 l SENSING ELEMENT: CS/SC,'CS/0, 42B RELAY, AH-10-DPS, AH-532-DPS AR-401' Rev. 20 Page 129'

O ENCLOSURE 1 Q

(Page 128 of 183)

I PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 i

l REACTOR BLDG MISC AIR FLOW LOW EVENT POINT 0366 INDICATED CONDITION:

o AHF-3A CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <0.25" H,0 EXISTS AS SENSED BY AH-13-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INCREASING RB TEMPERATURES OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AHF-3B IS OPERATING o REFER TO OP-417 o MONITOR RB TEMPS DISCUSSION:

LOSS OF.THIS AIR SUPPLY FAN WILL CAUSE RB TEMPERATURES TO INCREASE IN PLACES DUE TO A LACK OF MIXING FLOW.

REFERENCES:

DRAWINGS 208-005 SHEET AH-036, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 428 RELAY, AH-13-DPS s _..

AR-401 Rev. 20 Page 130

D ENCLOSURE 1

(

(Page 129 of 183)-

PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 REACTOR BLDG MISC AIR FLOW-LOW EVENT POINT 0369 INDICATED CONDITION:-

o AHF-3B CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <0.25" H,0 EXISTS AS SENSED BY AH-15-DPS f

U REDUNCANT INDICATION WHICH WILL VERIFY ALARM:

o INCREASING RB TEMPERATURES OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-3A o TRANSFER RMA-6 SUCTION TO RB ATMOSPHERE, REFER TO OP-41, DISCUSSION:

-RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE VIA EITHER THE DUCT OF AHF-3B DE THE RB ATMOSPHERE. THE TRANSFER OF THE SAMPLE POINT PER OP-417 IS A MANUAL OPERATION. REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWINGS 208-005 SHEET AH-037, DRAWING 308848 y)

SENSING ELEMENT: LCS/SC, CS/0, 428 RELAY, AH-15-DPS AR-401

.Rev. 20 Page 131

k E".' CLOSURE 1 (Page 130 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 REACTOR BLDG MISC AIR FLOW LOW EVENT POINT 0375 INDICATED CONDITION:

o AHF-4A OR AHF-4B CONTROL HANDLE IN NORMAL AFTER START' AND A LOW DIFFERENTIAL PRESSURE < 0.19" H,0 EXISTS AS SENSED BY AH-7-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INCREASING RB TEMPERATURES OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-4A OR 48 AS REQUIRED o REFER TO OP-417

-o MONITOR RB TEMPS DISCUSSION:

LOSS OF THE SG COOLING FANS WILL CAUSE SOME AREAS OF THE RB TO INCREASE DUE TO LACK OF MIXING FLOW.

REFERENCES:

DRAWINGS. 208-005 SHEET AH-038, DRAWING 308848-

--U SENSING ELEMENT: CS/SC, CS/0, 42B RELAY, AH-7-DPS AR-401 Rev. 20 Page 132

m O

ENCLOSURE 1 (Page 131 of 183)

PSA ANNUNr..'ATOR RESPONSE PSA-X-04-05 F-04-05 f

4 REACTOR BLDO

{

FAN VIBRATION l

i HIGH EVENT POINT 0361 1

INDICATED CONDITION:

o AH-11-ME HAS ACTUATED DUE TO AHF-2A VIBRATION IN EXCESS OF SETPOINT AS DETERMINE 9 BY PM-294 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-2A o SWAP REACTOR CAVITY COOLING TO "B" SIDE PER OP-417 o MONTTOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:

THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING THEREFORE IT WILL REQUIRE A REACTOR 3UILDING ENTRY TO i.

INVESTIGATE / REPAIR THE PROBLEM.

A SUSTAINED LOSS OF COOLING TO THE REACTOR CWITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAF ~NSTRUMENTATION.

REFERENCES:

DRAWING 208-005 SHEET AH-133 SENSING ELEMENT: AH-11-ME AR-401 Rev. 20 Page-133

}

ENCLOSURE 1 (Page 132 of 183)

PSA ANNUi'CIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VlBRATION HIGH i

l EVENT POINT 0363 INDICATED CONDITION:

o AH-12-ME HAS ACTUATED DUE TO AHF-28 VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY f%294 O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o NONE I

i OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-28 o SWAP REACTOR CAVITY COOLING TO "A" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:-

THIS CONDITION INDICATES THAT A '. BRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED.

THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSfDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR 'JILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.

A SUSTAINED LOSS OF CO3 LING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.

p-

REFERENCES:

DRAWING 208-005 SHEET AM-133 "Ll '

SENSING ELEMENT: AHs12-ME

.l AR-401 Rev. 20 Page 134

l ENCLOSURE 1 O

(." age 133 of 183) 4 PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 1

i.

i l

REACTOR BLDG FAN VlBRATION HIGH EVENT POINT 0367 INDICATED CONDITION:

i o AH-14-ME :lAS ACTUATED DUE TO AHF-3A VIBRATIOP

XCESS OF SETPOINT AS DETERMINED BY PM-294 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR AGIONS FOR A VALID ALARM:

o SECURE AHF-3A i

o ENSURE AHF-3B IS IN OPERATION e

e DISCUSSION:-

.THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETEGED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE -

REACTOR BUILDING, THEREFORE IT WILL P.EQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR'THE PROBLEM.

4

REFERENCES:

MAWING 208-005 SHEET AH-133 1

SENSING ELEMENT: AH-14-ME AR-401 Rev. 20 Page 135

=

cm-'e y

am >

y+-mm.

v-r e9f i-tgir.

y w

e=g--e-g.

ai

,.ev~i---

m e

e-o g-e w.-us-

,. -=m


r--m---

ENCLOSUR( 1 (Page 134 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDO FAN VlBRATION HIGH EVENT POINT 0370 INDICATED CONDITION:

o AH-16-ME HAS AGUATED DUE TO AHF-38 VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHIC!i WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALIO ALARM:

o SECURE AHF-3B o START AHF-3A o TRANSFER RMA-6 SUCTION TO RB ATMOSPHERE, REFER TO OP-417 DISCUSSION:

THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 C HAS BEEN DETECTED, -THERF. IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REAGOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATF./ REPAIR THE PROBLEM,

REFERENCES:

DRAWING 208-005 SHEET AH-134 SENSING ELEMENT: _AH-16-ME AR-401 Rev. 20 Page 136

.~

ee-e -

,r t----

w

.ee+p-

O ENCLOSURE 1 (Page 135 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F 04-05 REACTOR BLDG FAN VlBRATION HIGH EVENT POINT 0372 INDICATED CONDITION:

o AH-8-ME HAS ACTUATED DUE TO AHF-4A VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTisNS FOR A VALID ALARM:

o SECURE AHF-4A o START AHF-4B DISCUSSION:

THIS CONDITION INDICATES THAT A VIBRATION Ih EXCESS OF 1.0 G HAS BEEN O

DETECTED. THERE IS NO WAY TO MONITOR THE VIORATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE-IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.

REFERENCES:

DRAWING 208-005 SHEET AH-134 SENSING ELEMENT:

O

- AH-8-ME AR-401 Rev. 20 Page.137 m

w

O h.dE _1 (Page 136 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-0$

F-04-05 REACTOR BLDG FAN VIBRATION HlGH I

i EVENT POINT 0374 l

4 INDICATED CONDITION:

o AH-9 ME HAS ACTUATED DUE TO AHF-48 VIBRATION IN EXCESS OF SETPOINT AS-DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR AGIONS FOR A VALID ALARM:

o SECURE AHF-4B o START AHF-4A DISCUSSION:

THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS-BEEN DETECTED. -THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE

' REACTOR BUILDING, <THEREFORE IT WILL REQUIRE A REAGOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.

REFERENCES:

~ DRAWING 208-005-SHEET AH-134 SENSING ELEMENT: AH-9-ME

MCLOSURE 1 (Page 137 of 183)

I PSA ANNUNCIATOR RESPONSE PSA-X-04-07 F-04-07

=

l I

REACTOR BLDG PURGE AIR FLOW LOW T

EVENT POINT 0381 INDICATED CONDITION:

o DIFFERENTIAL PRESSURE ACROSS AH-1-DPS IS < 0.048" H 0 WITH AHF-6A AND/OR AHF-68 CONTROL HANDLE IN NORMAL AFTER START h0SITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHV-1D CLOSES OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE THE CAUSE FOR THE LOW PURCE SUPPLY FLOW, AND ADJUST THE RECIRC FLOW DAMPER CONTROL TO REESTABLISH FLOW THROUGH THE DUCT DISCUSSION:

J

REFERENCES:

DRAWING 208-005 SHEET 20, AND DRAWING 308848

')N>

SENSING ELEMENT: AHF-6A' CS/SC, CS/0, AHF-6B CS/SC, CS/0, AH-1-DPS AR-401 Rev. 20 Page 139

5 EELOSURE 1

/

(Page 138 of 103)

PSA ANNUNCIATOR RESPONSE PSA-X 04-07 F-04-07 j

REACTOR BLDG PURGE AIR FLOW-LOW EVENT POINT 0386 INDICATED CONDITION:

o DIFFERENTIAL PRESSURE ACROSS AH-296-DPS IS < 0.29' H,0 WITH AHF-7A AND/OR AHF-78 CONTROL HANDLE IN NORMAL AFTER START POSITION 3

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW FLOW INDICATidN ON AH-32-FIR POINT NUMBER 4 OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE THE CAUSE FOR THE LOW PURGE EXHAUST FLOW, AND CORRECT IF POSSIBLE DISCUSSION:

THIS CONDITION IS' INDICATIVE OF A LOSS OF INTEGRITY IN THE DUCT WORK AND SHOULD BE INVESTIGATED AS 500N AS POSSIBLE.

THIS IS AN EXPECTED ALARM DURING RB MINI-PURGE.

IF BOTH FANS OPERATING, ENSURE MINIMUM FLOW (20,000 Cf M EACH) IS OBTAINED

REFERENCES:

DRAWING 208-005 SHEET 22, AND DRAWING 308848 h

SENSING ELEMENT: AHF-7A CS/SC, CS/0, AHF-78 CS/SC.. CS/0, AH 296-DPS O-AR-401 Rev. 20--

~Page 140

4 O

ENCLOSURE 1 (Page 139 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04,

I I

I I

l l

CRDM SHROUD 4

I I

COOLING FANS I

I TRIP l

I zz +

x l

EVENT POINT 1224 1

INDICATED CONDITION:

1 o BREAKER IN UNIT-3D OF VENT MCC 3B IS OPEN o 42/12CR RELAY FOR THIS CIRCUIT IS DE-ENERCIZED o AHF-51B, AHF-51F, AND AHF-51) ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

4 o CREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 3D o LOCAL BREAKER POSITION i

OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE DISCUSSION:

THIS ALARM IS INDICATIVE 0F AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER. -ELECTRICAL MAINTENANCE WILL DETERM THE-FAN (S) THAT ARE SHORTED TO CNABLE THE REMAINING FANS TO BE

RUN, W.

REFERENCES:

DRAWING 208-005 SHEET AH-159 SENSING ELEMENT:

42/12CR RELAY AR-401 Rev. 20 Page 141

I l

ENCLOSURE 1 i

O (Page 140 of 183) i PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 l

l l

l c

I I

CRDM SHROUD l

l l

COOLING FANS '

I I

TRIP l

- t EVENT POINT-1225 INDICATED CONDITION:

o BREAKER IN UNIT 8A 0F VENT MCC 3B IS OPEN o 42/34CR RELAY. FOR THIS CIRCUIT IS DE-ENERGIZED o AHF-51C, AHF-510, AND AHF-51K ARE NOT RUNNING

[

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 8A o LOCAL BREAKER POSITION t

OPERATOR ACTIONS FOR A VALID ALARM:-

e o MONITOR CRDM STATOR TEMPS

.o NOTIFY ELECTRICAL MAINTENANCE i.

]

DISCUSSION:

-THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED ~FROM THIS BREAKER.. ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) -THAT ARE SHORTED TO ENABLE THE REMAINING FANS -TO BE RUN-

REFERENCES:

DRAWING 208-005-SHEET AH-160

~

SENSING ELEMENT:L 42/34CR RELAY AR-401'-

Rev. 2'O..

Page'142

.,.y.r[,

es,r,,

u-7.w.--y

=we..= g e 4 y

--q y

y.

<,%y-,y y,w,.s,.

,-,#,rupm.-,..q-wnive--,+

,vwr--y+g.wy

_.. _ - - - - -. ~. - - -. -.. -. - - - - - -. -.

ENCLOSURE 1 O

(Page 141 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-08

-F-04-08 i

l I

I CRDM SHROUD l

i COOLING FANS I

I TRIP I

I EVENT POINT 1226 INDICATED CONDITION:

o BREAKER IN UNIT 100 0F VENT MCC 3B IS OPEN o 42/42CR RELAY FOR THIS CIRCUIT IS DE-ENERGIZED o AHF-510, AHF-51H, AND AHF-51L ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 10D o LOCAL BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR CRDM STATOR TEMFS o NOTIFY ELECTRICAL MAINTENANCE DISCUSSION:

THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS-POWERED FROM THIS BREAKER.

ELECTRICAL MAINTENANCE WILL

- DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINDER TO BE RUN.

~

REFERENCES:

DRAWING 208-005 SHEET AH-161 SENSING ELEMENT:- 42/42CR' RELAY

-401:

AR Rev. 20 Page-143

.,---,y-y yi,-,,-r-r---'

"wr im'

~v m-s-

,~

I l

r O

ENCLOSURE 1 (Page 142 of 183)

PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 1

CRDM SHROUD v?qLING FANS TRIP EVENT POINT 1229 INDICATED CONDITION:

o BkEAKER iN UNIT 8A 0" VENT MCC 3A IS OPEN o 42/32CR.ELAY FOR THIS CIRCUIT IS DE-ENERGIZED o AHF-51A, AHF-$1E, AND AHF-51I ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN INDICATOR LIGHT ON VENT MCC 3A CUBICLE 8A

. o LOCAL BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR CRDr4 STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE DISCUSSION:

THIS ALARM IS INDICA':IVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER.

ELECTRICAL MAINTENANCE WILL DETERM THE FAN (5) THAT ARE SHORTED TO ENABLE THE REMAINDER TO BE RUN.

f3 fg REFE7ENCES:- DRAWING 208-005 SHEET AH-158 SENSING ELEMENT:

42/32 CR RELAY AR_'31 Rev. 20 Page 144

h ENCLOSURE 1 l

O (Page 143 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 i

l I

AUX BLDG l

I EXHAUST FAN I

I TRIP l

I I

I I

I EVENT POINT 0417 INDICATED CONDITION:

o AHF-14A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-14A CONTROL STATION o AHF-10, AHF-11A, AHF-11B TRIP, IF RUNNING e

OPERATOR ACTIONS FOR A VALIO ALARM:

o SECURE AHF-14C, START AHF-14B AND AHF-14D PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:

AUX BLOG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-112 WILL TRIP THIS FAN. THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL,

-WASTE CAS DECAY TANK OUTLET VALVES WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS,

~

REFERENCES:

DRAWING 208-005 SHEET AH-01 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS AR-401 Rev. 20 Page 145

~

r'3

[HCLOSURE_1

()

(Page 144 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 AUX BLDG EXHAUST FAN l

TFilP 4

EVENT POINT 0419 INDICATED CONDITION:

o AHF-14B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION (D

\\_/

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-14B CONTROL STATION o AHF-10, AHF-11A, AHF-11B TRIP, IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-140, START AHF-14A AND AHF-14C PER OP-409 o INVESTICATE CAUSE OF FAN TRIP DISCUSSION:

AUX BLOG EXHAUST FILTER DELUCE VALVE ACTUATION, FSV-110 WILL TRIP THIS FAN. WASTE GA5 DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.

THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.

)

REFERENCES:

DRAWING 208-005 SHEET AH-02 SENSING ELEMENT:

CONTROL STATION AND BREAKER CONTACTS

(

AR-401 Rev. 20 Page 146

ENCLOSURE 1 O

(Phoe 145 of 183) l PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 l

l l

AJX BLDG l

EXHAUST FAN l

TRIP

[

l I

EVENT POINT 0421 INDICATED CONDITION:

o AHF-14C BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REOUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GPEEN LIGHT WITH A RED FLAG ON AHF-14C CONTROL STATION o AHF-11A, AHF-11d, AHF-10 TRIP, IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-14A, START AHF-14B AND AHF-14D o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:

AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-116 WILL TRIP THIS FAN

'THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUFPLY INDICATION ON THE HVAC PANEL.

WASTE CAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.

REFERENCES:

DRAWING.208-005 SHEET AH-03 SENSING ELEMENT:

CONTROL STATION AND BREAKER CONTACTS

-AR-401-Rev. 20~

Page 147

ENCLOSURE 1 O

(Page 146 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05 l 1

-T I

I AUX BLDG I

I EXHAUST FAN i

l l

TRIP l

I I

I I

I EVENT POINT 0423 INDICATED CONDITION:

o AHF-14D BREAKFR OPEN WITH CONTROL HANDLE IN THE NORWL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VEIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-14D CONTROL STATION o AHF-10, AHF-11A, AHF-11B TRIP, IF RUNNING OPERATOR AGIONS FOR A VALID ALARM:

SECURE AHF-148, START AHF-14A AND AHF-14C

, INVESTIGATE CAUSE OF FAN TRIP i-DISCUSSION:

AUX BLDG EXHAUST FILTER DELUCE VALVE ACTUATION, FSV-118 WILL TRIP THIS FAN THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ~ARE DIFFiRENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL, WASTE CAS DECAY TANK OUTLET VALVES WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.

REFERENCES:

DRAWING 208-005 SHEET AH-04 SENSING. ELEMENT:

CONTROL STATION AND-BREAKER CONTAGS-AR-401 Rev. 20 Page 148

1

[HCLOSURE 1 (Page 147 of 183)

J PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 1

i; AUX BLDG j

EXHAUST FAN OVERLOAD L

j_

EVENT POINT 0418 INDICATED CONDITION:

o AHF 14A MOTOR AMPS >115% RATED LOAD i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-14A TRIPS o AHF-14/ HIGH MOTOR AMPS INDICATED ON HVAC PANEL l

OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-14A AND AHF-14C, START AHF-14B AND AHF-14 ) AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP d

DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOU5 OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVFRCURRENT PROTECTIVE RELAY ACTUATION WILL-TRIP THE BREAKER.

REFERENCES:

. DRAWING 208-005 SHEET AH-01 SENSING ELEMENT:

74-AHF-14A'

AR-401.

Rev. 201

_Page 149 4-

+tei+

.i.-,,,s.w.,4 gg-

<-Wai

-w v..'.-.mm+5wp-m-eg tr *st T-ikfev bT1 dw-in" W-ra't-s<-

N+-*wWWTT-56=-TTM7-+W ma N 'P e? *-*- W f f ed"'TF*

W T-

-W--

$ TtyT T 7 '+= T T

ENCLOSURE 1 (Page 148 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 AUX BLDG EXHAUST FAN OVERLOAD EVENT POINT 0420 INDICATED CONDITION:

o AHF 14B MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-148 TRIPS o AHF-14B HIGH MOTOR AMPS INDICATED ON HVAC PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-148 AND AHF-140, START AHF-14A AND AHF-14C AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTICATE CAUSE OF FAN TRIP DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER,

REFERENCES:

DRAWING 208-005 SHEET AH-02 SENSING ELEMENT:

74-AHF-14B AR-401 Rev. 20 Page 150

_....._.m

-__.-_w_

c J

h ENCLOSURE 1 (Page 149 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 i

i AUX BLDG EXHAUST FAN OVERLOAD i

L EVENT POINT 0422 INDICATED CONDITION:

3 o AHF-14C MOTOR AMPS >115% RATED LOAD l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-14C TRIPS o AHF-14C HIGH MOTOR AMPS INDIrATED ON HVAC PANEL OPERATOR ACTIONS FOR A VALID ALARM:

i o SECURE AHF-14A AND AHF-14C, START AHF-148 AND AHF-14D AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTICATE CAUSE OF FAN TRIP DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT Ph0TECTIVE DEVICES HAVE ACTUATED.

INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

REFERENCES:

DRAWING 208-005 SHEET AH-03 Q

SENSING ELEMENT:- 74-AHF-14C'

.AR-401

_Re'r. 20 Page 151

I ENCLOSURE 1 O

(Page 150 of 183)

PSA-F ANNUNCIATOR RESPONSE P5A-X-05-02 F-05-02 i

1 AUXBLDG EXHAUST FAN OVERLOAD 4

4 EVENT POINT 0424 INDICATED CONDITION:

o AHF-14D MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-140 TRIPS o AHF-14D HIGH MOTOR AMP 5 INDICATED ON HVAC PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE AHF-14B AND AHF-14D, START AHF-14A AND AHF-14C AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:

.THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOU5= 0VERCURRENT PROTECTIVE RELAY ACTUATION WILL. TRIP THE BREAKER.

Ri WNCES:

DRAWING 208-005 SHEET AH-04 SEh.'4NG ELEMENT:

74-AHF-14D

'AR-401 Rev. 20 Page 152

O ENCLOSURE 1 (Page 151 of 183)

PSA-F ANNUNCIATOR RESDONSE PSA-X-05-03 F-05-03 AB FLTR 2A/B/C/D AP HIGH I

EVENT POINT 1552 INDICATED CONDITION:

o AUX BUILDING EXHAUST FILTER, AHFL-2A, FLOW IS >5.2" H,0 AS SENSED BY AH-601-DPS 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHFL-2A LOCAL DIFFERENTIAL PRESSURE INDICATOR 4

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY HVAC TO INSPECT FILTER DISCUSSION:

OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.

s,

REFERENCES:

DRAWING 208-005 SHEET AH-131

'd-SENSING ELEMENT:

AH-601-DPS AR-401 Rev. 20 Page 153-e

,-w

- - +

me-e

,w

.w-

---~-s.

w rrum y

O ENCLOSURE 1 (Page 152 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 AB FLTR 2AIB/C/D AP HIGH n=

I.

EVENT POINT 1553 INDICATED CONDITION:

o AUX BUILDING EXHAUST FILTER, AHFL-2B, FLOW IS >5.2" H,0 AS SENSED BY AH-602-DPS O-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHFL-28 LOCAL DIFFERENTIAL PRESSURE INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY HVAC TO INSPECT FILTER DISCUSSION:

OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.

-h.

REFERENCES:

DRAWING 208-005-SHEET AH-131 SENSING ELEMENI AH-602-DPS AR-401-R'ev. 20 Page 154

i r

1 4

i ENCLOSURE 1 O

(Page 153 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 l

1 M

NN_

N

)

,j A8 FLTR 2A/B/C/D AP HIGH a

EVENT POINT 1688 l

INDICATED CONDITION:

o AUX BUILDING EXHAUST FILTER, AHFL-2C, FLOW IS >5.2" H,0 AS SENSED BY AH-603-DPS a

\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHFL-2C LOCAL DIFFERENTIAL PRESSURE INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY HVAC TO INSPECT FILTER.

DISCUSSION:

OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.

REFERENCES:

DRAWING 208-005 5HEET AH-131 SENSING ELEMEE AH-603-DPS AR-401-Rev. 20 Page 155

.-p 9

e m..e

+.c n-Hw--

wr m

ENCLOSURE 1 (Page 154 of 183)

PSA.F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 i

AB FLTR PA/BICID t

AP HIGH i

EVENT POINT 1689 INDICATED CONDITION:

o AUX BUILDING EXHAUST FILTER, AHFL-20, FLOW IS >5.2" AS SENSED BY AH-604-DPS-REDL'NDANT INDICATION WHICH WILL VERIFY ALARM:

o AHFL-2D LOCAL DIFFERENTIAL PRESSURE INDICATOR 1

OPERATOR ACTIONS FOR A VALID ALARM:

-o NOTIFY HVAC ?O INSPECT FILTER DISCUSSION:

OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.

REFERENCES:

ORAWING 208-005 SHEET AH-131 qO SENSING ELEMENT:- AH 604-DPS AR-403 Rev. 20 Page-156 9

g g v-&4+7T vg we l y-yjar =

we T

"O'+Vr-W'**"'"C

    • 'T" NTF"""V"7'TT'"M'
  • 9'N'

--"""""#^'""*"'"*~7~^*

WCLQSURE 1 (Page 155 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-04 F-05 04 PENETRATION AIR FLOW 4

TROUBLE EVENT POINT 0438 4

INDICATED CONDITION:

l o PENETRATION COOLING AIR FLOW IS <0.015" H 0 AS SENSED BY AH-30-DPS WITH EITHERAHF-9AORAHF-98CONTROLSTATIONIbNORMALAFTERSTART REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL DIFFERENTIAL FLOW INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o START BACKUP PENETRATION COOLING FAN o REFER TO OP-417 DISCUSSION:

REFERENCES:

DRAWING 208-005 SHEET AH-56 d-SENSING ELEMENT: AH-30-DPS AR-_401 Rev. 20 Page~157-

i ENCLOSURE 1 O

(Page 156 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 i

FIRE PP HOUSE -

FAN TROUBLE EVENT POINT 0454

. INDICATED CONDITION:

l o FIRE PUMP HOUSE VENTILATION AIR FLOW IS <0.18" H 0 AS SENSED BY EITHER AH-168-DPS AND AHF-33A IS RUNNING OR BY AH-173-Dh5 AND AHF-33B RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALAR":

o LOCAL DIFFERENTIAL FLOW INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o STARf BACKUP FIRE PUMP HOUSE FAN o CHECK FIRE PUMP HOUSE INLET FILTERS AND OUTLET REGISTERS FOR PROPER OPERATION DISCUSSION:

FIRE PUMP HOUSE FANS ARE.USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL' FIRE PUMPS.

REFERENCES:

- DRAWING 208-005 SHEET AH-71 SENSING ELEMENT:. ' AH-173-DPS, 'AH-168-DPS AND CONTROL STATION CONTACTS AR-40{

Rev. 20 Page 158

LNCLOSURE 1 O

(Page 157 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 i

e 2

FIRE PP HOUSE FAN TROUBLE EVENT POINT 1537 INDICATED CONDITION!

o AHF-33A BREAKER CLOSED AND CONTROL HANDLE IN THE NORMAL AFTER STOP l

POSITION REDUNDANT INDICATION WHICH WILL VERIFY 4LARM:

o RED LIGHT ON WITH A GREEN FLAG ON AHF-33A CONTROL STATION o TEMPERATURE IN FIRE PUMP HOUSE >85* F.

o ANY FIRE PUMP RUNNING 4

OPERATOR ACTIONS FOR A VALIO ALARM:

o INVESTICATE CAUSE OF AUTO START DISCUSSION:

FIRE PUMP HOUSE FANS ARE USED FOR F79E PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERAEION-ANY-TIME A FIRE PUMP IS IN OPERATION, b

REFERENCES:

DRAWING 208-005 SHEET AH-71 SENSING ELEMENT:. CONTROL STATION AND BREAKER CONTACTS

%f EAR-401_

Rev. 20~

Page 159

. ~..

- _ _ = - -. _ - -

p ENCLOSURE 1

(

(Page 158 of 183)

PSA-F ANNUNCIA OR RESPONSE PSA-X-05-05 F-05-05 j

i i

FIRE PP HOUSE FAN TROUBLE EVENT POINT 1538 INDICATED CONDITION:

o AHF-338 BREAKER CLOSED AND CONTROL HANDI E IN THE NORMAL AFTER STOP POSITION 0

1V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON AHF-338 CONTROL STATION o TEMPERATURE IN FIRE PUMP HOUSE >85* F.

o ANY FIRE PUMP RUNNING OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF AUTO START DISCUSSION:

-FIRE PUMP HOUSE FANS ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY. TIME A FIRE PUMP IS IN OPERATION,

REFERENCES:

. DRAWING 208-005 SHEET AH-72

.}

SENSING ELEMENT:

CONTROL STATION AND BREAKER CONTACTS AR-401 Rev. 20 Page 160

}

}

ENCLOSURE 1

. /

(Page 159 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 045G INDICATED CONDITION:

o AHF-22A BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-22A CONTROL STATION OPERATOR' ACTIONS FOR A VALID ALARM:

o IF EGDG-1A IS RUNNING ENSURE AHF-22B IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <810 RPM AS SENSED BY EG-19-SS.

SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.

~

REFERENCES:

DRAWING 208-005 SHEET AH-75 SENSING ELEMENT: CONTROL SWITCH' CONTACTS

.AR-401:

Rev. 20 Page 161

'O ENCLOSURE,,1 (Page 160 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 0457 INDICATED CONDITION:

o AHF-22B BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START O'

\\

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-22B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o IF ECDG-1A IS RUNNING ENSURE AHF-22A IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <810 RPM AS SENSED BY EG-19-SS.

SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-74

\\l SENSING ELEMENT:

CONTROL SWITCH CONTACTS I

t

'AR-401 Rev. 20 Page 162 L.

ENCLOSURE 1 O

(,Page 161 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 i

DIESEL GEN RM FAN TROUBLE I

EVENT POINT 0458 I

INDICATED CONDITION:

l o-DIESEL GENERATOR "A" ROOM DUCT AIR FLOW <0.033" "H 0" AS SENSED BY AH-3598-DPS WITH AHF-22B OR AH-359A-DPS WITH AHF-2bA ON f*%

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL FLOW INDICATION ON JOHNSON CONTROL PANEL r-OPERATOR ACTIONS FOR A VALID ALARM:

o IF EGDG-1A IS RUNNING SWAP OPERATING AHF-22 FANS o NOTIFY AUX BLDG OPERATOR TO ENSURE INLET FILTERS ARE CLEAR OF DEBRIS AND OBSTRUCTIONS TO AIR FLOW o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

J 4

REFERENCES:

DRAWING 200-005 SHEET AH-74 SENSING ELEMENT: AH-3598-DPS, AW359A-DPS AR-401-Rev. 20 Page 363

q ENCLOSURE 1 Q

(Page 162 of 183)

PSA r ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03

=

DIESEL GEN RM FAN TROUBLE I

EVENT POINT 0459 INDICATED CONDITION:

o DIESEL GENERATOR "A" CONTROL ROOM TEMPERATU. E IS >I18' F AS SENSED BY AH-540-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH AMBIENT TEMPERATURE CONDITIONS IN THE "A" DIESEL GENERATOR CONTROL ROOM OPERATOR ACTIONS FOR A VALID ALARM:

o INSPECT "A" DIESEL CENERATOR CONTROL ROOM FOR ANY SIGNS OF A FIRE o LOWER TEMPERATURE BY Sl ARTING AHF-22A OR 228 o ENSURE AHF-28A IS RUNNING DISCUSSION:

HIGH AMBIENT TEMPERATURES IN THE CONTROL ROOM CAN ADVERSELY IMPACT THE OPERABILITY'0F THE EMERGENCY DIESEL CENERATORS f~

REFERENCES:

DRAWING 208-005 SHEET AH-76

(

SENSING ELEMENT: AH-540-TS

\\.

AR-401 Rev. 20 Page 164

4 ENCLOSURE 1 y

(Page 163 of-183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 l F 46,

14 DIESEL GEN RM FAN TROUBLE i

i EVENT PQlNT 0461 INDICATED CONDITION:

o AHF-22C BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER. START O

i D

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

~

o GREEN LIGHT ON WITH A RED FLAG ON AHF-22C CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o IF ECDG-18 IS RUNNING ENSURE AHF-22D IS RUNNING o INVESTIGATE 'CAUSE OF FAN TRIP o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS 4

DISCUSSION:

DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <810 RPM AS SENSED BY EG-20-SS.

SECURING THE-FAN LOCALLY WILL ACTUATE THIS ALARM.

~s

REFERENCES:

DRAWINC 208-005 SHEET AH-77 P

- t i

il-

_ SENSING ELEMENT: CONTROL SWITCH CONTACTS AR-401 Rev. 20 Page 165

O ENCLOSURE 1 (Page 164 of 183)

- PSA-F ANNUNCIATOR RESPONSE PSA-X-0G-03 F-06-03 DIESEL GEN RM FAN TROUBLE 4

EVENT PQiNT 0462 A

INDICATED CONDITION:

1 o AHF-220 BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START h

~

V RELUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-22D CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o IF ECDG-18 IS RUNNING ENSURE AHF-22C IS RUNNI.NG o INVESTIGATE CAUSE OF FAN TRIP o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS'<810 RPM AS SENSED BY EG-20-SS.

SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.

<- s

REFERENCES:

DRAWING 208-005 SHEET AH-78 SENSING ELEMENT: CONTROL SWITCH CONTACTS

.AR-401 Rev.~20 Page 166

O ENCLOSURE 1 (Page 165 of 183)

PSA-F ANNUNCIATOR RESPONSE-PSA-X-06-03 F-06-03 q

e DIESEL GEN RM FAN TROUBLE i

EVENT POINT 0463 INDICATED CONDITION:

l o DIESEL GENERATOR "B" ROOM DUCT AIR FLOW <0.033" "H,0" AS SENSED BY AH-369B-DPS WITH AHF-22D OR AH-369A-DPS WITH AHF-22C ON O

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL FLOW INDICATION ON JOHNSON CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o IF ECDG-1B IS RUNNING SWAP OPERATING AHF-22 FANS o NOTIFY AUX BLDG OPERATOR TO ENSURE INLET FILTERS ARE CLEAR OF DEBRIS AND OBSTRUCTIONS TO AIR FLOW o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

REFERENCES:

DRAWING 208-005 SHEET AH-77

, vI SENSING ELEMENT:- AH-369B-DPS, AH-369A-DPS AR-401 Rev. 20 Page 167

ENCLOSURE 1 (Page 166 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 Z

ZZ CIESEL GEN RM FAN TROUBLE EVENT POINT 0464-INDICATED CONDITION:

o DIESEL GENERATOR "B" CONTROL ROOM TEMPERATURE IS >118' F AS SENSED BY AH-541-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH AMBIENT TEMPERATURE CONDITIONS IN THE DIESEL GENERATOR CONTROL ROOM OPERATOR ACTIONS FOR A VALID ALARM:

o INSPECT "B" DIESEL GENERATOR CONTROL ROOM FOR ANY SIGNS OF A FIRE o LOWER TEMPERATURE BY STARTING AHF-22C OR 22D o ENSURE AHF-28B IS RUNNING DISCUSSION:

o HIGH AMBIENT TEMPERATURES IN THE CONTROL ROOM CAN ADVERSELY IMPACT THE

' OPERABILITY OF THE EMERGENCY DIESEL GENERATORS A

REFERENCES:

DRAWING 208-005 SHEET AH-79 SENSING ELEMENT: AH-541-TS AR-401L Rev. 20 Page 168-

p ENCLOSURE 1

-- ( )

(Page 167 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE I

I EVENT POINT 1539 5

INDICATED CONDITION:

o AHF-22A BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON AHF-22A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN AUTO S1 ART o

PLACE CONTROL HANDLE FOR AHF-22A TO NORMAL AFTER START POSITION TO MATCH FLAGS THAT WILL ENABLE THE LOW FLOW ALARM DISCUSSION:

DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >S10 RPM AS SENSED BY EG-19-SS.

STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-74 SENSING ELEMENT:

CONTROL SWITCH CONTACTS AR-401 Rev. 20 Page 169

.-x--___--___________-______-___-__-_______-

?-

p-ENCLOSURE 1 (Page 168 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 1540 INDICATED CONDITION:

o ECDG-1A SPEED IS >810 RPM AS SENSED BY EG-19-SS AND AHF-22A AND AHF-228 ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EGDG-1A READY OR RUN LIGHT ON AND AHF-22A AND AHF-22B GREEN INDICATORS ON OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-22A AND/OR AHF-22B o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

' DIESEL GENERATOR FANS PROVIDE COOLING FOR THE DIESEL GENERATOR ROOM.

OPERATION OF THE EMERGENCY DIESEL GENERATOR WITH NO COOLING FANS RUNNING MUST BE CLOSELY MONITORED 50 AS TO NOT EXCEED 120F ENGINE ROOM TEMPERATURE.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-005 SHEET AH-74

\\

SENSING ELEMENT: -3 ERA AND BREAKER CONTACTS AR-401 Rev. 20 Page 170

1 O

ENCLOSURE 1 (Page 169 of 163)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 i

i l

l DIESEL GEN RM FAN TROUBLE EVENT POINT 1541 INDICATED CONDITION:

o AHF-228 BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON AHF-22R CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN AUTO START o PLACE-CONTROL HANDLE'FOR AHF-228 TO NORMAL AFTER START POSITION TO MATCH FLAGS THAT WILL ENABLE THE LOW FLOW ALARM l

DISCUSSION:

DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >810 RPM AS

-SENSED BY EG-19-SS.

STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-75 Ii SENSING ELEMENT: CONTROL SWITCH CONTACTS AR-401.

Rev.-20' Page 171

O ENCLOSURE 1 (Page 170-of-183)~

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN HM FAN TROUBLE EVENT PC"JT 1542 INDICATED CONDITION:

o AHF-22C BREAKER CLOSED WITH THE CONTR0! HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON AHF-22C CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN AUTO START o

PLACE CONTROL' HANDLE FOR AHF-22C TO NORMAL AFTER START POSITION TO MATCH FLAGS THAT WILL ENABLE THE LOW FLOW ALARM DISCUSSION:

DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >810 RPM AS SENSED BY EG-20-SS.

STARTING'THE FAN LOCALLY WILL-ACTUATE THIS ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-77 1-.-

SENSING CLEMENT: CONTROL SWITCH CONTACTS AR-401 Rev. 20 Page 172

O ENCLOSURE 1 (Page 171 of 183)

PSA-F /.NNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE I

EVENT POINT 1543 INDICATED CONDITION:

o EGDG-1B SPEED IS >810 RPM AS SENSED BY EG-20-SS AND AHF-22C AND AHF-220

-ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EGDG-1B READY OR RUN LIGHT ON AND AHF-22C AND AHF-22D GREEN INDICATORS ON OPERATOR ACTIONS FOR A VALID ALARM:

o START AHF-22C AND/OR AHF-220 o REFER TO ITS 3.8.1 & 3.8.2 AND CONTACT NPTS DISCUSSION:

DIESEL GENERATOR FANS PROVIDE COOLING FOR THE DIESEL GENERATOR ROOM.

OPERATION OF THE EMERGENCY DIESEL GENERATOR WITH NO COOLING FANS RUNNING MUST BE CLOSELY MONITORED 50 AS NOT TO EXCEED 120F ENGINE ROOM TEMPERATURE.

REFEP. TO 15 FOR ADMINISTRATIVE R5QUIREMENTS.

REFERENCES:

ORAWING 208-005 SHEET AH-77 O

SENSING ELENENT:

3 ERB AND BREAKER CONTACTS AR-401 Pev. 20 Page 173

[

ENCLOSURE 1 (Page 172 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE l

EVENT POINT 1544 INDICATED CONDITION:

o AHF-22D BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED. LIGHT ON WITH A GREEN FLAG ON AHF-22D CONTROL STATION OPERATOR ACTIONS FCR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN AUTO START o.

PLACE CONTROL HANDLE FOR AHF-22D TO NORMAL AFTER START POSITION TO MATCH FLAGS THAT WILL ENABLE THE LOW FLOW ALARM DISCUSSION:

DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >8I0 RPM AS

. SENSED BY EG-20-SS.

STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.

REFERENCES:

DRAWING 208-005 SHEET AH-78

?

SENSING ELEMENT:

CONTROL SWITCH CONTACTS 1

AR-401 Rev. 20 Page 174

ENCLOSURE 1 p:

Q-(Page 173 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 l

SAMPLING ROOM FAN TROUBLE EVENT POINT 0508 INDICATED CONDITION:

o AHF-44A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-44A CONTROL STATION o T0XIC CAS ACTUATION o RADIATION H!GH RAD ALARM RM-A5 OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN TRIP o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION o REFER TO AP-250 OR AP-513 DISCJSSION:

DUCTWORK TEMPERATURE >135' AS SENSED BY AH-402-TS WILL TRIP THIS FAN.

AHF-20A'MUST BE RUNNING IN EITHER FAST OR SLOW FOR-THIS FAN TO RUN.

REFERENCES:

DRAWING 208-005 SHEET AH-98 SENSING ELEMENT: CONTROL STATION CONTACTS AR-401 Rev. 20 Page 175

_ p-

. ENCLOSURE 1 (Page 174 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 4

SAMPLING ROOM FAN TROUBLE EVENT POINT 0509

. INDICATED CONDITION:

o AHF-448 BREAKER OPEN WITH COWROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY. ALARM:

o GREEN LIGHT-ON WITH A RED FLAG ON AHF-44L CONTROL STATION o T0XIC CAS ACTUATION o RADIATION HIGH RAD ALARM RM-A5 OPERATOR AC INS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN TRIP o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION o REFER T0 AP-250 OR AP-513 DISCUSSION:

DUCTWORK TEMPERATURE >135' AS = SENSED BY AH-545-TS WILL TRIP THIS FAN.

AHF-208 MUST.BE RUNNING IN EITHER FAST OR SLOW FOR THIS FAN TO RUN.

,g

REFERENCES:

DRAWING 208-005 SHEET AH-99

~

SENSING ELEMENT: CONTROL 5TATION CONTACTS AR-401 Rev. 20 Page 176 v.-

w c-w

f-O ENCLOSURE 1 (Page 175 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM FAN TROUBLE EVENT POINT 0510 INDICATED CONDITION:

o AHF-44A DUCTWORK TEMPERATURE >135'F AS SENSED BY AH-402-TS L

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-44A TRIPS o WHITE " TEMP NORM" LIGHT IS OUT FOR AHF-44A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HICH TEMP o IF FIRE CONDITIONS EXIST REFER TO AP-880 o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:

REFERENCES:

DRAWING 208-005 SLEET AH-98

>~d -

SENSING ELEMENT: AH-402-TS-AR-401' Rev. 20 Page 177

i ENCLOSURE 1 (Page 176 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06 l 5

SAMPLING ROOM FAN TROUBLE EVENT POINT 0511 INDICATED CONDITION:

o AHF-44A EX;lAUST FLOW <0.10" H,0 AS SENSED BY AH-403-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW FLOW ON LOCAL INDICATION FOR AHF-44A OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW FLOW

-o CONSIDERATION SHOULD BE GIVEN TO SWAPPIt'G TO "B" SIDE CONTROL COMPLEX VENTILATION o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:

AHF-20A MUST BE RUNNING PRIOR TO STARTING AHF-44A rw

REFERENCES:

DRAWING 208-005 SHEET AH-98 SENSING ELEMENT:.AH-403-DPS AR-401 Rev. 20 Page 178

i ENCLOSURE 1

(

(Page 177 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM FAN TROUBLE EVENT POINT 1530 INDICATED CONDITION:

o AHF-448 EXHAUST FLOW <0.10" H,0 AS SENSED BY AH-544-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW FLOW ON LOCAL INDICATION FOR AHF-448 OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW FLOW o CONSIDERATION SHOULD BE GIVEN TO SWAPPING TO "A" SIDE CONTROL COMPLEX VENTILATION o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:

AHF-20B MUST BE RUNNING PRIOR TO STARTING AHF-448

REFERENCES:

- DRAWING.208-005 SHEET AH-99

,f -

k-SENSING ELEMENT: AH-544-DPS O

AR-401'-

Rev. 20 Page 179

. ~. -

h( J ENCLOSURE 1 (Page 178 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM FAN TROUBLE EVENT POINT 1531 INDICATED CONDITION:

o AHF-44B DUCTWORK TEMPERATURE >135'F AS SENSED BY AH-545-TS f

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o AHF-448 TRIPS o WHITE " TEMP NORM" LIGHT IS OUT FOR AHF-448 CONTROL STATION OPERATOR AcrIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH TEMP o IF FIRE CONDITIONS EXIST REFER TO AP-880 o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:

,ew

REFERENCES:

DRAWING 208-005 SHEET AH-99 b).

i SENSING ELEMENT: AH-545-TS AR-401 Rev. 20 Page 180

ENCLOSURE-1 (Page 179 of 183)

PSA F ANNUNCIATOR RESPONSF PSA-X-06-05 F-06-05 lNTERMEDIATE BLDG FAN TROUBLE i

EVENT POINT 0376 INDICATED CONDITION:

o AHF-24A BREAKER CLOSED AND DISCHARGE DAMPER AHD-67, CLOSED ON REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL DAMPEi, INDICATION OPERAIOR ACTIONS FOR A VALID ALARM:

o SHUTDOWN AHF-24A o SWAP TO "B" SIDE INTERMEDIATE BUILDING FANS PER OP-409

+

DISCUSSION:

OPERATION OF AHF-24A WITH THE DISCHARGE DAMPER CLOSED MAY CAUSE FAN DAMAGE.

q

REFERENCES:

DRAWIN(.'208-005-SHEET AH-51

'd SENSING ELEMENT:

2-AHF-24A, AHF-24A-KS AR-401 Rev. 20 Page-181 l.

l

O ENCLOSURE 1 (Page 180 of 183)

PSA-F ANNUNCIATOR RESPONSE-PSA-X-06-05 F-06-05 I

INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 0377 INDICATED CONDITION:

o AHF-248 BREAKER CLOSED AND ITS DISCHARGE DAMPER AHD-68, CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

~

o LOCAL DAMPER INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o SHUTDOWN AHF-24B o SWAP TO "A" SIDE INTERMEDIATE BUILDING FANS PER OP-409 DISCUSSION:

OPERATION OF AHF-24B WITH THE DISCHARGE DAMPER CLOSED MAY CAUSE FAN DAMAGE.

REFERENCES:

DRAWING 208-005 SHEET AH-52 V

SENSING ELEMENT:

2-AHF-248, AHF-248-KS AR-401' Rev. 20 Page 182 A

~

~ - -,_~ ~

l ENCLOSURE 1 O

(Page 181 of 183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 1

INTERMEDIATE BLDG FAN TROUBLE i

EVENT POINT 1548 INDICATED CONDITION:

o AHF-29A BREAKER OPEN WITH CONTROL HANDLE IN THE NORM /,L AFTER START POSITION REDUN7 ANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON AHF-29A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP TO "B" SIDE INTERMEDIATE BUILDING FANS PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP s

DISCUSSION:

c

REFERENCES:

DRAWING 208-005 SHEET AH-53 SENSING ELEMENT:

CONTROL STATION CONTAGS AR-401 Rev. 20 Page 183

'l ENCLOSURE 1

.(

(Page 182 of 183)

-PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 INTERMEDIATE BLDG FAN TROUBLE 5

EVENT POINT 1549 INDICATED CONDITION:

o ArlF-29B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION:

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON AHF-29B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o SWAP TO "A" SIDE INTERMEDIATE BUILDING FANS PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:

REFERENCES:

DRAWING 208-005 SHEET AH-54 SENSING ELEMENT: CONTROL STATION CONTACTS.

-AR-401.

.Rev. 20 Page 184

O

-ENCLOSURE 1 (Page 183 of.183)

PSA-F ANNUNCIATOR RESPONSE PSA-X-06-08 F-06-08 REACTOR BLDG -

PERSONNEL DOOR OPEN i

EVENT POINT 1212 INDICATED CONDITION:

o REACTOR BUILDING PERSONNEL OR EQUIPMENT HATCH INNER OR OUTER DOOR NOT CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RB DOOR INDICATICN PANEL MCB PSA SECTION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE OPEN HATCH o REFER TO OP-417 DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE-REQUIREMENTS.

.,q -_

REFERENCES:

DRAWING 208-064 SHEET ME-04 SENSING' ELEMENT:

ME-1,3,5,7,23,24,25 & 26-KS AR-401-Rev. 20 Page 185-(LAST PAGE) i

- _ _ _ - _ _ _ - - _ _ _ - _ _ _ _ - _ _ _