b SEABROOK STATION Engin23 ring Office o;(

.)

June 16, 1986 Put2c SeMce of New Hampshke SBN-1117 T.F.

B7.1.2 NEW HAMPSHIRE YANKEE DIVISION United States Nuclear Regulatory Commission Washington, DC 20555 Attention:

Mr. Vincent S. Noonan, Projdct Director PWR Project Directorate No. 5

References:

(a) Construction Permits CPPR-135 and CPPR-136, Docket Nos. 50-443 and 50-444 (b) PSNH Letter (SBN-955), dated February 28, 1986,

" Level Measurement Error (SER Outstanding Issue No. 10)", J. DeVincentis'to V. S. Noonan (c) PSNH Letter (SBN-1004), dated April 15, 1986,

" Level Measurement Error (GER Outstanding Issue No. 10)", J.'DeVincentis to.V. S. Noonan (d) PSNH IStter (SBN-1085), dated June 3,1986,

" Level Measurement Error (SEk; 0utstanding Issue No. 10)", J. DeVincentis to V. S. Noonan

Subject:

Level Measur'ement Error;-Additional Information (SER Outstanding Issue No.10)

Dear Sir:

In' Reference (d), we committed to provide high containment pressure _

alarms and containment pressure indication. During subsequent discussions with the Staff we were asked to expand on this statement to indicate in more detail how this commitment will be met.

The containment pressure indications will be narrow range, ~5 psig to

+5 psig. The instrument channels and alarms which will provide this indi-cation will be classified as Class 1E, and will meet the design and qual-ification criteria in FSAR Section 7.5.4.4 for Design Category 1 accident monitoring instrumentation. High containment pressure alarms will be pro-vided from these channels to alert the operator upon the containment pres-sure exceeding the alarm trip point.

\\

06061 OCg O hDR~

PDR E

8ooI 0

Seabrook Station Construction Field Office. P.O. Box 700 ' Soabrook, NH O3874

e' United States Nuclear Regulatory Commission Attention:

Mr. Vincent S. Noonan Page 2 The c.antainment pressure indicators will be installed in the main control board. The alarms will be displayed on both the Video Alarm System (VAS) and the hard-wired annunciator. The VAS alarm will be assigned Priority I which requires immediate operator response. The hard-wired annunciator contains a minimal set of alarms all of which require immediate operator response. This assures that the operators will be alerted to, and will respond to, the abnormal containment conditions in a timely manner.

The actions that would be taken in response to the alarms indi-cating an abnormal condition inside the containment are delineated in l

Reference (b).

We trust this information is acceptable and request the resolution I

of the above referenced SER outstanding issue be reflected in the next l

supplement to Seabrook's SER.

l Very truly yours, l

1 John DeVincentis Director of Engineering cc: Atomic Safety and Licensing Board Service List

e

.Dign3 curecn, E:quiro Calvin A. Ctnnsy H:rmon & Weiss City Mantscr 2001 S. Street, W.W.

City Hall Butte 430 126 Daniel Street Wr.shington, D.C.

20009 Portsmouth, NH 03801 Sherwin E. Turk, Esq.

Stephen E. Merrill, Esquire Office of the Executive Legal Director Attorney General UsS. Nuclear Regulatory Commission George Dana Bisbee, Esquire Tenth Floor Assistant Attorney General Washington, DC 20555 Office of the Attorney General 25 Capitol Street Robert A. Backus. Esquire Concord, NH 03301-6397 116 Lowell Street P.O. Box 516 Mr. J. P. Wadeau Manchester, NH 03105 Selectmen's office 10 Central Road Philip Ahrens. Esquire Rye, NH 03870 Assistant Attorney General Department of The Attorney General Mr. Angie Machiros Statehouse Station #6 Chairman of the Board of Selectmen Augusta, NE 04333 Town of Newbury Newbury, MA 01950 Mrs. Sandra Gavutis Chairman, Board of Selectmen Mr. William S. Lord RFD 1 - Box 1154 Board of Selectmen Kennsington, NH 03827 Town Hall - Friend Street Amesbury, MA 01913 Carol S. Sneider, Esquire g

Assistant Attorney General Senator Gordon J. Humphrey Department of the Attorney General 1 Pillsbury Street One Ashburton Place, 19th Floor Concord, NH 03301 Boston, MA 02108 (ATTN: Herb Boynton)

Senator Gordon J. Humphrey H. Joseph Flynn Esquire U.S. Senate office of General Counsel Washington, DC 20510 Federal Emergency Management Agency (ATTN: Tom Burack) 500 C Street SW Washington, DC 20472 Richard A. Hampe Esq.

7 Paul McEachern, Esquire Hampe and McNicholas 35 Pleasant Street Matthew T. Brock, Esquire Concord, NH 03301 Shaines & McEachern 25 Maplewood Avenue Thomas F. Powers, III P.O. Box 360 Town Manager Portsmouth, NH 03801 i

Town of Exeter 10 Front Street Cary W. Holmes. Esq.

Exeter, NH 03833 Holmes & Ells 47 Winnacunnet Road Brentwood Board of Selectmen Hampton, NH 03842

~RFD Dalton Road Brentwood, NH 03833 Mr. Ed Thomas FEMA Region I 442 John W. McCormack PO & Courthouse J

Peter J. Mathews, Mayor City Hall Boston, MA 02109 Newburyport, MA 01950 Robert Carrigg Town Office Atlantic Avenua i

North Hampton, NH 03862

a -

y t

- -. ~ - - -.

-