Forwards Revised TS Bases Pages Which Were Implemented by McGuire IAW 10CFR50.59,including ITS 3.7.11 LCO Bases Re Auxiliary Bldg Ventilation Exhauset Sys
ML20198B946
Person / Time
Site: McGuire, Mcguire  Duke Energy icon.png
Issue date: 12/09/1998
From: Barron H
DUKE POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20198B950 List:
References
NUDOCS 9812210241
Download: ML20198B946 (1)


Text

!

T l

gg Duke Energy Corpor tion McGuire Nudear Surion 12700 Hagers Ferry Road Huntersville, NC 28078-9340 (704) 875-4800 OFFICE (704) 875-4809 FAX 4.

I December 9, 1998 U.

S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555

Subject:

McGuire Nuclear Station Docket Nos. 50-369, 50-370 Revision to Technical Specification Bases Please find attached revised Technical Specification Bases pages which were implemented by McGuire in accordance with the provisions of 10CFR 50.59.

ITS 3.7.11 LCO Bases were revised to specify that an Auxiliary Building Filtered Ventilation Exhaust System (ABFVES) is considered OPERABLE when its associated two fans (1A and 1B, or 2A and 2B, or lA and 2A, or 1B and 2B, or any two fan combination provided that SR 3.7.11.4 has been performed for that combination prior to taking credit for that combination),

filters, ductwork, valves and dampers are operable.

ITS SR 3.7.11.4 Bases were also revised to specify that this surveillance requirement is required to be performed for each fan combination described in the LCO Bases.

Questions regarding this submittal should be directed to Kay Crane, McGuire Regulatory Compliance at-(704) 875-4306.

l H.

B.

Barron, Vice President McGuire Nuclear Station l

l 9812210241 981209

PDR ADOCK 050CO369 p

PDR_