3 h

m 1

"""" ]

Log # TXX-98263 File # 10010

. g j

916 7UELECTRIC Ref. # 10 CFR 50.90 10 CFR 50.36 L

2 O

C. Imace 'Ihrry senior nce Presiden:

December 11,1998

[

& Principal Nuclear Officer 3

I U. S. Nuclear Regulatory Commission 1

Attn: Document Control Desk 1

Washington, DC 20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES) 3 DOCKET NOS. 50-445 AND 50-446 j

TECHNICAL SPECIFICATION CONVERSION APPLICATION 3

ADDITIONAL INFORMATION FOR SECTION 3.8 g

m j

REF: 1) TU Electric letter, logged TXX-97105, from C. L. Terry to the NRC dated May 15,1997 i

I

2) NRC letter from T. A. Polich to C. L. Terry dated September 3,1998, concerning

']

section 3.8.4 through 3.8.8 j

j

3) NRC letter from T. A. Polich to C. L. Terry dated October 7,1998, concerning w

sections 3.8.1, 3.8.2, 3.8.3, 3.8.9 and 3.8.10 5

f Gentlemen:

0 TU Electric requested an amendment to the CPSES Unit 1 facility operating license (NPF-87) and

[

Unit 2 facility operating license (NPF-89) by incorporating changes to the CPSES Units 1 and 2 Technical Specifications (TS) as provided in reference 1.

The NRC staff requested additional lI information regarding Section 3.8, " Electrical Power Systems," of the proposed TS changes in j

references 2 and 3. The requested information is provided in the attachment to this letter as are any additional changes needed for Sections 3.8 as identified by TU Electric.

d This letter and the attachment are not a supplement to reference 1. A supplement to reference 1 3

will be provided at a later date. Any deviations from the responses provided in this letter will be g

discussed in the supplement.

'g The only commitment contained in this letter is to provide a supplement to reference 1 at a later date.

E

/

,n 9812160066 981211 PDR ADOCK 05000445 P

PDR

\\

COM ANClli Pl AK Sll AM I'l I CI RK S T A l'lON P O. Ikn 1(U2 Glen Rose, leus N40IW2

TXX-98263 Page 2 of 2 '

If you have any questions concerning the content of this letter, please contact Mr. Bob Dacko (254-897-0122).

Sincerely, 0, $,

C. L. Terry By:

R. D. Walker Regulatory Affairs Manager BSD/bd Attachment 1.

Section 3.8, " Electrical Power Systems" c-E. W. Merschoff, Region IV J. l. Tapia, Region IV Resident inspectors, CPSES T. J. Polich, NRR J. N. Donohew, NRR Mr. Arthur C. Tate Bureau of Radiation Control Texas Department of Public Health 1100 West 49* Street Austin, Texas 78704 l

i to TXX-98263 Page 1 of 14 i

6 JLS CONVERSION TO IMPROVED TECHNICAL SPECIFICATIONS CTS 3.8 - ELECTRICAL POWER SYSTEMS ITS 3.8 - ELECTRICAL POWER SYSTEMS RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION AND LICENSEE INITIATED ADDITIONAL CHANGES l

h l

l

_ to TXX-98263 l

Page 2 of 14 l

INDEX OF ADDITIONAL INFORMATION l

ADDITIONAL INFORMATION APPLICABILITY ENCLOSED l

NUMBER 3.8.G-1 DC, CP, WC, CA YES 3.8.1-01 DC DC NA 3.8.1-01 CP CP, WC, CA YES 3.8.1-01 WC 3.8.1-01 CW 3.8.1-02 DC DC NA 3.8.1-02 WC WC, CA NA 3.8.1-02 CW 3.8.1-03 DC DC,CP YES 3.8.1-02 CP 3.8.1-03 CP CP YES ~~

3.8.1-04 DC DC NA 3.8.1-04 CP CP YES 3.8.1-05 DC DC NA

' 3.8.1-05 CP CP YES 3.8.1-05 WC WC, CA NA 3.8.1-04 CW i

3.8.1-05 CW CA NA 3.8.1-06 DC DC NA 3.8.1-06 WC WC NA 3.8.1-06 CW CA, WC NA 3.8.1-07 DC DC NA 3.8.1-07 CP CP, WC YES 3.8.1-04 WC I

3.8.1-07 WC WC NA 3.8.1-07 CW CA NA 3.8.1-08 DC DC NA 3.8.1-08 WC WC NA l

3.8.1-09 DC DC NA i

l 3.8.1-09 WC WC, CA NA l

3.8.1-08 CW 3.8.1-09 CW CA NA 3.8.1-10 DC DC NA II

- Attachment 1 to TXX-98263 Page 3 of 14 INDEX OF ADDITIONAL INFORMATION ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER

'l 3.8.1-10 WC WC NA 3.8.1-11 DC DC NA 1

3.8.1-11 CP

.CP YES 3.8.1-11 WC WC NA 3.8.1-11 CW -

CA NA 3.8.1-12 DC DC NA 3.8.1-12 CP CP YES 3.8.1-12 WC WC NA.

3.8.1-12 CW CA NA 3.8.1-13 DC DC NA 3.8.1-13 CP CP YES 3.8.1 13 WC WC NA 3.8.1-14 DC DC, CP, WC, CA YES 3.8.1-06 CP

. 3.8.1-03 WC

' 3.8.1-03 CW

~;

3.8.1-14 WC WC NA

' 3.8.1-14 CW CA NA 3.8.1-15 DC DC,CP YES 3.8.1-08 CP 3.8.1-15 CP CP YES 3.8.1-15 WC WC NA 3.8.1-15 CW CA NA j

- 3.8.1-16 DC DC,CP YES 3.8.1-09 CP 3.8.1-16 CP CP YES i

3.8.1-16 WC WC, CA NA

. 3.8.1-13 CW 3.8.1-17 DC DC NA i

3.8.1-17 CP CP YES 3.8.1-18 DC DC,CP YES 3.8.1-10 CP l

t.

s

.... _.. _. to TXX-98263 Page 4 of 14 INDEXOF ADDITIONALINFORMATION ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER 3.8.1-18 CP CP YES 3.8.1-19 DC

~DC NA 3.8.1-19 CP CP YES I

3.8.1-20 DC DC NA 3.8.1-21 DC DC NA 3.8.1-22 DC DC,CP YES 3.8.1-14 CP 3.8.1-23 DC DC NA 3.8.1-24 DC DC NA 3.8.1-25 DC.

DC NA 3.8.1-26 DC -

DC NA 3.8.1-27 DC DC,CA NA 3.8.1-10 CW i

3.8.1-28 DC DC NA 1

3.8.1-29 DC DC NA 3.8.1-30 DC DC NA 3.8.1-31 DC DC NA 3.8.1-32 DC DC NA 3.8.1-33 DC DC. CP, WC, CA YES 3.8.1-20 CP 3.8.1-17 WC

/

3.8.1-34 DC DC NA 3.8.1-35 DC DC NA 3.8.1-BSI -1 DC DC NA

~

3.8.2-01 DC '

DC. CP,'WC, CA YES 3.8.2-05 CP 3.8.2-02 WC 3.8.2-02 CW 3.8.2-01 CP CP, WC, CA YES

.3.8.2-01 WC 3.8.2-01 CW -

3.8.2-02 DC DC NA 3.8.2-02 CP CP YES

Attachtrent 1 to TXX-98263 Page 5 of 14.

INDEX OF ADDITIONAL INFORMATION ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER

. 3-.8.2-03 DC DC, CP, WC, CA YES 3.8.2-07 CP =

3.8.2-03 WC 3.8.2-03 CW 3.8.2-03 CP CP YES 3.8.2-04 DC DC NA 3.8.2-04 CP CP YES 3.8.2-04 WC WC NA 3.8.2-04 CW CA NA 3.8.2-05 DC DC NA 3.8.2-05 WC WC NA 3.8.2-06 DC DC NA 3.8.2-06 CP CP YES 3.8.2-07 DC DC NA 3.8.2-08 DC DC NA 3.8.2-08 CP

~

CP, WC, CA YES '-

3.8.2-06 WC 3.8.2-05 CW 3.8.2-09 CP CP YES 3.8.2-10 CP CP YES 3.8.3-01 DC DC, WC, CA NA

~ 3.8.3-01 WC 3.8.3-01 CW

~

3.8.3-02 DC DC NA 3.8.3-02 CP CP YES 3.8.3-02 WC WC, CA NA 3.8.3-02 CW 3.8.3-03 DC DC, WC, CA NA 3.8.3-03 WC 3.8.3-03 CW

- 3.8.3-03 CP CP YES 3.8.3-04 DC DC NA 3.8.3-04 CP CP YES

!i 3.8.3-04 WC WC NA e

, to TXX-98263 Page 6 of 14 lNDEX OF ADDITIONAL INFORMATION ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER 3.8.3-05 DC DC, CP, WC, CA YES 3.8.3-01 CP 3.8.3-05 WC

' 3.8.3-04 CW 3.8.3-05 CP CP YES 1

3.8.3-06 DC DC NA 3.8.3-06 WC WC NA 3.8.3-07 DC DC NA 3.8.3-07 CW CA NA 3.8.3-08 DC DC NA 3.8.3-07 WC WC, CA NA i

3.8.3-05 CW 3.8.3-08 WC WC, CA NA 3.8.3-06 CW 3.8.3-09 DC DC NA 3.8.3-09 WC WC, CA ^

NA 3.8.3-08 CW 3.8.3-10 DC DC NA 3.8.3-10 CW CA NA 3.8.3-11 DC DC NA

]

3.8.3-12 DC DC NA 3.8.3-13 DC DC, WC, CA NA 3.8.3-10 WC 3.8.3-09 CW

.3.8.4-01 CA NA 3.8.4-02 DC, WC, CA NA 3.8.4-03 DC NA 3.8.4-04 CA NA 3.8.4-05 DC, CP, WC, CA YES 3.8.4-06 CA NA 3.8.4-07 DC NA 3.8.4-08 WC NA i

1' I.

'A

=

~-

.. -..-. to TXX-98263 I

Page 7 of 14 INDEX OF ADDITIONAL INFORMATION ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER l

'3.8.4-09 DC, CP, WC, CA YES I

3.8.4-10 CP,CA YES I'

3.8.4-11 DC NA 3.8.4-12 CA NA 3.8.4-13 WC-NA 3.8.4-14 CP YES 3.8.4-15 WC NA 3.8.4-16 DC,CA NA 3.8.4-17 WC NA 3.8.4-18 CA NA 3.8.4-19 CP YES 3.8.4-20 CP YES p

3.8.4-21 CA NA

-3.8.4-22 CA NA 3.8.4-23 DC NA 3.8.4-24 DC' NA r

3.8.4-25 DC NA i

3.8.4-26 DC NA l

3.8.4-27 DC NA 3.8.4-28 DC NA 3.8.4-29 WC NA 3.8.5-01 DC NA

.i 3.8.5-02 DC, CP, WC, CA YES i

3.8.5-03 CP YES f

3.8.5-04 WC NA 3.8.5-05 CA NA 3.8.5-06 DC NA 3.8.5-07 DC NA

'3.8.6-01 DC, CP, WC, CA YES 3.8.6-02 WC NA

'3.8.6-03 DC, CP, WC, CA YES 3.8.6-04 DC, CP, WC, CA YES Pl 3.8.6-05 DC, CP, WC, CA YES Ji.

3.8.6-06 DC, CP, WC, CA YES l

3.8.6-07 DC NA I

3.8.6-08 CP YES

[

3.8.6-09 DC,CP YES l

.3.8.6-10 WC NA

l 3.8.7-01 CP YES l

3.8.7-02 CP YES l

3.8.7-03 WC NA 3.8.7-04 CA NA c'

f-

)

... ~.

4 to TXX-98263 Page 8 of 14 INDEX OF ADDITIONAL INFORMATION i-ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER 3.8.8-01

~

CA,CP YES 3.8.8-02 CA NA 3.8.8-03 WC, CA NA 3.8.8-04 DC NA

~ 3.8.8-05 DC NA 3.8.9-01 DC DC NA 3.8.9-01 CP CP YES 3.8.9-01 WC WC, CA NA 3.8.9-01 CW 3.8.9-02 DC DC NA 3.8.9-02 CP CP YES 3.8.9-02 WC WC NA 3.8.9-03 DC DC NA 3.8.9-03 CP CP YES

-a

. 3.8.9-04 CP CP,CA' YES 3.8.9-02 CW 3.8.9-05 CP CP YES l

3.8.10-01 DC DC, CP, WC, CA YES i

3.8.10-01 CP

- 3.8.10-01 WC 3.8.10-01 CW 3.8.10-02 DC DC, CP, WC, CA YES 3.8.10-03 CP 3.8.10-03 WC

- 3.8.10-03 CW

3.8.10-02 CP CP, WC, CA YES 3.8.10-02 WC 3.8.10-02 CW I

3.8.10-03 DC DC NA 3.8.10-04 DC DC NA

(;

l-EY

' to TXX-98263 Page 9 of 14 4

INDtiX OF ADDITIONAL INFORMATION ADDITIONAL INFORMATI.QB APPLICABILITY ENCLOSED NUMBES 3.8.10-04 CP CP, WC, CA YES 3.8.10-05 WC 3.8.10-05 CW 4

3.8.10-04 WC WC, CA NA 3.8.10-04 CW.

3.8.10-06 WC WC NA i

1 3.8.B-01a CA NA l

3.8.B-01 b CA NA 3.8.8-01c CA NA 3.8.B-01d CA NA 3.8.B-01e CA NA 3.8.B-01 f CA NA-3.8.B-01g CA-NA 3.8.B-01h CA NA 2

3.8.B-011 CA NA 3.8.B-01]

CA NA 3.8.B-011 CA NA 3.8.B-01 m CA NA 3.8.B-01 n CA NA 3.8.B-01o CA NA 3.8.B-01 p CA NA 3.8.B-01q CA NA 3.8.B-01 r CA NA 3.8.B-01 s CA NA

. 3.8.B-01t CA NA 3.8.B-01 u CA NA 3.8.B-01v CA NA

. 3.8.B-01w CA NA 3.8.B-01x CA NA 3.8.B-01y CA NA 3.8.B-02a.

CP YES I

3.8.B-02b CP YES 3.8.B-02c CP YES 3.8.B-02d CP YES i

3.8.B-02e CP YES 3.8.B-02f CP YES 3.8.B-02g CP YES j

i a

i!

1

_. _ _ _ _ _.. ~.. _ _.. _.. _ _ _. _. _ _ _ _... _. _.. _ _... _.. _. _ _. _

!5 to TXX-98263 I

Page 10 of 14 INDEX OF ADDITIONAL INFORMATION i

ADDITIONAL INFORMATION APPLICABILITY ENCLOSED a

NUMBEB

'f 3.8.B-02h CP YES 3.8.B-02i CP YES 3.8.B-02j CP YES i

3.8.B-02k CP YES 1

3.8.B-021 CP YES 3.8.B-02m CP YES

' 3.8.B-02n -

CP YES

3.8.B-02o CP YES 3.8.B-02p '

CP YES i

3.8.B-02q CP YES 3.8.B-02r CP YES 3.8.B-02s CP YES i

3.8.B-02t CP YES 3.8.B-02u CP YES 3.8.B-02v CP YES

- 3.8.B-02w CP YES l

3.8.B-02x -

CP YES 3.8.B-02y CP YES ~~

3.8.B-02z CP YES

' 3.8.B-02aa CP YES 3.8.B-02bb CP YES 3.8.B-02cc CP YES

' 3.8.B-02dd CP YES 3.8.B-02ee CP YES 3.8.B-02ff CP YES 3.8.B-02gg CP-

-YES 3.8.B-02hh CP YES 4

3.8.B-02ii.

CP YES 3.8.B-02ij CP YES l

- 3.8.B-03a DC NA 3.8.B-03b DC NA 3.8.B-03c -

DC NA 3.8.B-03d DC NA 3.8.B-03e -

DC NA

- 3.8.B-03f DC NA 3.8.B-03g.

.DC NA 3.8.B-03h DC NA 3.8.B-031

'DC NA 3.8.B-03]

DC NA 3.8.B-03k DC NA 3.8.B-031 -

DC NA c

0n e

m -..

-y

.-m-,,

y g-

l i-to TXX-98263 0

Page 11 of 14 INDEX OF ADDITIONAL INFORMATION i'

ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER 3.8.B-03m DC NA 3.8.B-03n DC NA.

3.8.B-03o DC NA 3.8.B-03p DC NA 3.8.B-03q DC NA l

3.8.B-03r '

DC NA 3.8.B-03s DC NA i

3.8.B-04a WC NA

- 3.8.B-04b WC NA 3.8.B-04c WC NA 3.8.B-04d WC NA 3.8.B-04e WC NA 3.8.B-04f WC

'NA 3.8.B-04g WC NA 3.8.B-04h WC NA 3.8.B-041 WC NA 3.8.B-04J WC NA 2

3.8.B-04k WC NA 3.8.B-041 WC NA

. 3.8.B-04m WC NA 3.8.B-04n.

WC

'NA 3.8.B-04o WC NA 3.8.B-04p WC NA 3.8.B-04q WC NA 3.8.B-04r WC NA 3.8.B-04s WC NA 3.8.B-04t WC NA 3.8.B-04u WC NA

~

. 3.8.B-04v WC NA

- 3.8.B-04w WC NA 3.8.B-04x WC NA 3.8.B-04y WC NA

. 3.8.B-04z WC NA CA 3.8-001 CA, DC, WC NA

' CP 3.8-ED CP YES CP 3.8-002 CP YES CP 3.8-004 CP YES CP 3.8-005 -

CP YES j

_. _. - to TXX-98263 Page 12 of 14 INDEX OF ADDITIONAL INFORMATION ADDITIONAL INFORMATION APPLICABILITY ENCLOSED NUMBER

' DC ALL-001 (3.8 changes only)

DC

DC see DCL-98-003 DC ALL-004 (3.8 changes only)

DC NA DC ALL-005 (3.8 changes only)

DC NA DC 3.8-ED DC NA DC 3.8-001 DC NA DC 3.8-002 DC NA DC 3.8-003 DC NA DC 3.8-004 DC NA TR 3.8-003 DC, CP, WC, CA YES 1

WC 3.8-ED WC NA WC 3.8-001 WC NA WC 3.8-002 WC NA WC 3.8-003 CA, CP, DC, WC YES WC 3.8-004 WC NA

]

WC 3.8-006 WC NA l

i t

n i

?

1

-t

-4h

__ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ to TXX-98263 Page 13 of 14 JOINT LICENSING SUBCOMMITTEE METHODOLOGY FOR PROVIDING ADDITIONALINFORMATION The following methodology is followed for submitting additional information:

1. Each licensee is submitting a separate response for each section.
2. If an RAI does not apply to a licensee (i.e., does not actually impact the information that defines the technical specification change for that licensee), "NA" has been entered in the index column labeled " ENCLOSED" and no information is provided in the response for that licensee.
3. If a licensee initiated change does not apply, "NA" has been entered in the index column labeled " ENCLOSED" and no information is provided in the response for that licensee.
4. The common portions of the " Additional Information Cover Sheets" are identical, except for brackets, where applicable (using the same methodology used in enclosures 3A, 38,4,6A and 6B of the conversion submittals). The list of attached pages will vary to match the licensee specific conversion submittals. A licensee's FLOG response may not address all applicable plants if there is insufficient similarity in the plant specific responses to justify their inclusion in each submittal. In those cases, the response will be prefaced with a heading such as " PLANT SPECIFIC DISCUSSION."
5. Changes are indicated using the redline / strikeout tool of Wordperfect or by using a hand markup that indicates insertions and deletions. If the area being revised is not clear, the affected portion of the page is circled. The markup techniques vary as necessary, based on the specifics of the area being changed and the complexity of the changes, to provide the clearest possible indication of the changes.
6. A marginal note (the Additional Information Number from the index) is added in the right margin of each page being changed, adjacent to the area being changed, to identify the source of each change.
7. Some changes are not applicable to one licensee but still require changes to the Tables provided in Enclosures 3A,38,4,6A, and 6B of the originallicense amendment request to reflect the changes being made by one or more of the other licensees. These changes are not included in the additional information for the licensee to which the change does not apply, as the changes are only for consistency, do not technically affect the request for that licensee, and are being provided in the additionel information being provided by the licensees for which the change is applicable. The complete set of changes for the license amendment request will be provided in a licensing amendment request supplement to be provided later.

--- to TXX-98263 Page 14 of 14 JOINT LICENSING SUBCOMMITTEE METHODOLOGY FOR PROVIDING ADDITIONALINFORMATION (continued)

8. The item numbers are formatted as follows:

[ Source][lTS Section]-[nnn)

Source =

Q - NRC Question CA-AmerenUE DC-PG&E WC - WCNOC CP - TU Electric TR - Traveler ITS Section = The iTS section associated with the item (e.g.,3.3). If all sections are potentially impacted by a broad change or set of changes, "ALL"is used for the section number.

nnn = a three digit sequential number t

I l

i.

i

![

ADDITIONALINFORMATION COVER SHEET ADDITIONAL INFORMATION NO: Q 3.8.G-1 APPLICABILITY: DC, CP, WC, CA REQUEST:

ITS 3.8.X Bases General i

There have been a number of instances that the specific changes to the STS Bases are not properly identified with redline or strikeout marks.

Comment: Perform an audit of all STS Bases markups and identify instances where additions and/or deletions of Bases were not properly identified in the original submittal.

FLOG RESPONSE: Tha submitted ITS Bases markups for Section 3.8 have been compared to the STS Bases. Some differences that were identified were in accordance with the markup methodologies (e.g., deletion of brackets and reviewer's notes). Most of the differences were

{

editorial in nature and would not have affected the review. Examples of editorial changes are:

1 1)

Capitalizing a letter with only a " redline" but not striking out the lower case letter that it replaced.

3 2)

Changing a verb from singular to plural by adding an "s" without " redlining" the "s".

1-3)

Deleting instead of striking-out the A, B, C,.. etc. following a specification title (e.g.,

[

' SR3.6.6A.7).

'~

4)

Changing a bracketed reference (in the reference section) with only a " redline" for the new reference but failing to include the strike-out of the old reference.

5)

In some instances the brackets were retained (and struck-out) but the unchanged text within the brackets was not redlined.

6)

Not redlining a title of a bracketed section. The methodology calls for the section title to be red!ined when an entire section was bracketed.

J 7)

Additional text not contained in the STS Bases was added to the ITS Bases by the lead FLOG member during the development of the submittal. Once it was determined to not be applicable, the text was then struck-out and remains in the ITS Bases mark-up.

Differences of the above editorial nature will not be provided as attachments to this response.

The pages requiring changes that are more than editorial and are not consistent with the markup methodology are attached.

ATTACHED PAGES:

Enc! 5B B 3.8-1_

Bracketed information was not redlined (3 places) and bracketed information was deleted instead of being struckout (2 places)

B 3.8-2 Bracketed information was not redlined (2 places) and bracketed information was deleted instead of being struckout (1 place)

B 3.8-2a Bracketed information was not redlined (2 places)

- B 3.8-5 Bracketed information was not redlined

' B 3.8-9 _

. Bracketed information was deleted instead of being struckout I

B 3.8-16 Bracketed information was not redlined

-l B 3.8-17 Bracketed information was not redlined (5 places) and bracketed information was deleted instead of being struckout (1 piace)

B 3.8-18 Bracketed information was not redlined (1 place) and bracketed information was deleted instead of being struckout (1 place)

B 3.8-20 Bracketed information was not redlined B 3.8-21 Bracketed information was not redlined

- B 3.8-22 Bracketed information was not redlined B 3.8-23 Bracketed information was not redlined (2 places)

B 3.8-24 Bracketed information was not redlined (2 places) and bracketed information was deleted instead of being struckout (1 place) j B 3.8-25 Bracketed information was not redlined (3 places)

B 3.8-26 Bracketed information was not redlined (4 places)

B 3.8 Bracketed information was not redlined (2 places)

- B 3.8-28 Bracketed information was not redlined (6 places)

B 3.8-29 Bracketed information was not redlined (2 places)

B 3.8-39 Bracketed information was not redlined B 3.8-40 Bracketed information was not redlined (2 places)

B 3.8-45 Bracketed information was not redlined (2 places)

B 3.8-47 Bracketed information was not redlined (4 places) and bracketed information was deleted instead of being struckout (4 places)

B 3.8-48 Bracketed information was not redlined (4 places)

B 3.8-49 Bracketad information was not redlined (2 places)

B 3.8-51 Bracketed information information was deleted instead of being struckout.

- B 3.8-51a Bracketed information was deleted instead of being struckout B 3.8-52 Bracketed information was not redlined (4 places) and bracketed information was deleted instead of being struckout (2 places)

B 3.8-54 Bracketed information was not redlined B 3.8-57 Bracketed information was not redlined (2 places)

B 3.8-60 Bracketed information was not redlined (2 places)

B 3.8-62 Bracketed information was not redlined (3 places)

B 3.8-63 Bracketed information was not redlined

. B 3.8-64 Bracketed information was not redlined (2 places)

B 3.8-65 Bracketed informatiori was not redlined B 3.8-66 Bracketed information was not redlined (3 places)

= B 3.8-67 Bracketed information was not redlined (6 places) and bracketed information was deleted instead of being struckout (1 place)

B 3.8-68 Bracketed information was deleted instead of being struckout B 3.8-71 Bracketed information was not redlined (2 places)

' B 3.8-75 Bracketed information was not redlined (5 places)

B 3.8-76 Bracketed information was not redlined (2 places)

B 3.8-77

. Bracketed information was not redlined (2 places)

. B 3.8-79 Bracketed information was not redlined (2 places)

- B 3.8-80

. Bracketed information was not redlined B 3.8-82 Bracketed information was not redlined

- B 3.8-84 Bracketed information was not redlined (2 places) r,i,

-